ABB POLIM-D..PI MV HV Surge Arrester Line Discharge Class 1 AC Systems 52kV Indoor & Outdoor
ABB POLIM-D..PI surge arresters are used for the short-circuit protection of medium voltage and high voltage electrical equipment and cables against overvoltages caused by lightning, atmospheric discharges and switching conditions up to 52kV.
ABB POLIM-D..PI surge arresters are designed for indoor and outdoor use and with metal-oxide (MO) resistors without spark gaps molded in silicone rubber with a touch-proof metal clad design housing and tested according to IEC 60099-4 and is applicable for inner cone systems according to DIN EN 50181 and DIN 47637.
- IEC 60099-4:2014 – Part 4: Metal-oxide Surge Arresters Without Gaps For a.c. Systems
- DIN 50181:2011-04 – Plug-in type bushings above 1 kV up to 52 kV and from 250 A to 2,50 kA for equipment other than liquid filled transformers; German version EN 50181:2010
- DIN 47637:1986-01 – Separable accessories for power cable for bushing with inside cone; Uₘ= 36 kV, inside cone and fastening for the separable connector
ABB POLIM-D..PI surge arresters are available in cone size 2 or 3 and are for use with MV-HV cables, transformers, and metal-clas switchgear – T&D distribute cable joints, terminations and connectors to support the construction of electrical networks, substations and overhead lines for 11kV, 33kV and up to 66kV.
Surge arresters should be installed as close as possible to the medium/high voltage electrical equipment to be protected within the protective distance with sheds pointing downwards – minimum permissible distances between the surge arresters and the earth must be observed.
ABB POLIM-D..PI MV HV Surge Arrester
Technical Specification
Nominal Discharge Current /n 8/20μs | 10kA Peak |
Line Discharge Class (LD) | 1 |
High Current Impulse /hc 4/10μs | 65kA Peak |
Long Duration Current Impulse | 250A / 2000μs |
Short Circuit Rating /s 50 Hz | 16kA rms for 0.2s |
Ambient Air Temperature | -40 to +40ºC |
Frequency of System Voltage | 16.7/50/60Hz |
Weather Ageing Test | Metal Housing Tested according to test series A (1000 h salt fog) |
IP Grade (EN 60529) | IP67 |
ABB Surge Arresters Overview
Should you require assistance for the specification or supply of MV-HV surge arresters for 11kV, 33kV and up to 52kV voltages please do not hesitate to contact us.
Surge Arrester Type | |||||||||||
Technical Data | |||||||||||
System Voltage Us | ≤ 52kV | ≤ 52kV | ≤ 52kV | ≤ 52kV | ≤ 52kV | ≤ 7.5kV | ≤ 5kV | ≤ 72kV | ≤ 72kV | ≤ 1kV | ≤ 72kV |
Continuous Operating Voltage Uc | ≤ 44kV | ≤ 42kV | ≤ 44kV | ≤ 44kV | ≤ 44kV | ≤ 7.5kV | ≤ 4.8kV | ≤ 56kV | ≤ 56kV | ≤ 1kV | ≤ 58kV |
Nominal Discharge Current ln | 10kA | 10kA | 10kA | 10kA | 10kA | 10kA | 10kA | 10kA | 10kA | 20kA | 20kA |
High Current Impulse | 100kA | 65kA | 100kA | 100kA | 100kA | 100kA | 100kA | 100kA | 100kA | 100kA | 100kA |
IEC Line Discharge Class | 1 | 1 | 2 | 2 | 2 | 2 | 2 | 2 | 3 | 4 | 4 |
Application | Indoor & Outdoor | Indoor & Outdoor | Indoor & Outdoor | Indoor | Indoor & Outdoor | Indoor & Outdoor | Indoor | Indoor & Outdoor | Indoor & Outdoor | Indoor & Outdoor | Indoor & Outdoor |
Medium Voltage & High Voltage Applications – Recommended Overvoltage Protection 11kV 33kV 52kV | |||||||||||
Transformers | Yes | Yes | Yes | Yes | Yes | Yes | – | Yes | Yes | – | Yes |
Overhead Lines | Yes | – | Yes | – | Yes | – | – | Yes | Yes | – | Yes |
Cables | – | – | Yes | Yes | Yes | – | – | Yes | Yes | – | Yes |
Rotating Machines | – | – | – | Yes | Yes | Yes | – | Yes | Yes | – | Yes |
Capacitors & Capacitor Banks | Yes | – | Yes | Yes | Yes | – | – | Yes | Yes | – | Yes |
Cable Sheath Protection HV Cables | – | – | – | Yes | Yes | Yes | Yes | – | – | – | Yes |
Switchgear & Switching Cubicles | – | Yes | – | – | – | – | – | – | – | – | – |
Metal-Encapsulated Switchgear | Yes | – | – | – | – | – | – | – | – | – | – |
Inductances, Reactors, PLC Line Traps | – | – | – | – | – | – | Yes | – | – | – | – |
Transformers Of Arc Furnace | – | – | – | – | – | – | – | – | Yes | – | Yes |
Further Medium Voltage Apparatuses | Yes | – | Yes | Yes | Yes | Yes | Yes | Yes | Yes | – | Yes |
Component of Secondary Equipment | – | – | – | – | – | Yes | – | – | – | Yes | – |
Power Electronics | – | – | – | – | – | Yes | – | – | – | Yes | – |
Earthing Surge Arresters
Installers must observe national regulations and the requirements of the system owner/utility. ABB POLIM-D..PI surge arresters should be connected to the system ground via the shortest path – all contact surfaces should be cleaned and lubricated with acid-free contact grease.
Observe recommended minimum diameters for ABB POLIM-D..PI arresters:
- Copper Diameter 20mm
- Aluminium Diameter 40mm
Commissioning MV-HV Medium & High Voltage Surge Arresters
Due to the risk of electric shock only authorised personnel should work on ABB POLIM-D..PI surge arresters and observe BS EN 50110-1:2013 Operation of Electrical Installations – the MV-HV power system should be disconnected from the power supply, de-energised and grounded using portable short-circuit earthing kits for either substation or overhead line applications. If live-working is required and unavoidable around electrical equipment a calculation of arc risk should be sanctioned and appropriate arc flash protection clothing worn.