Testing Insulating Gloves | Guide to Safe Use & Care for Electrical Gloves

Published 20 Jul 2022

Electrical Insulating Rubber Gloves

Electrical Insulating Rubber Gloves

Testing Insulating Gloves

Guide To Safe Use of Classes 00, 0, 1, 2, 3 and 4 Electrical Gloves

Improper use of electrical rubber insulating gloves can be a matter of life and death.

Get them retested regularly to make sure that they are still electrically safe.

Treat your rubber insulating gloves well and they can last a long time. The testing of insulating gloves will help to prevent failure which could lead to electrical shock if the surface integrity has been comprised by “wear and tear”.

As Main UK Stockists for the CATU Electrical range of insulating gloves Thorne & Derrick regularly are requested to provide care and maintenance advice to ensure gloves provide adequate and ongoing electrical safety and protection to the wearer.

 

Any Brand of Insulating Glove can be tested. Here are some examples:

  • CATU
  • Regeltex
  • Honeywell Salisbury
  • Polyco
  • Clydesdale (Novax)

CATU Insulating Gloves

Electrical Insulation Tests For Gloves 

Class Of Gloves  Maximum Voltage Use AC DC  Test Voltage AC Proof Test Voltage AC Withstand
00 500V ac | 750V dc 2.5kV 5kV
0 1000V ac | 1500V dc 5kV 10kV
1 7500V ac | 11250V dc 10kV 20kV
2 17000V ac | 25500V dc 20kV 30kV
3 26500V ac | 39750V dc 30kV 40kV
4 36000V ac | 54000V dc 40kV 50kV

Special Properties Of Gloves

Special Property Of Insulating Glove Category Marking Code
Acid Resistance A
Oil Resistance H
Ozone Resistance Z
Acid, Oil & Ozone Resistance R
Extreme Low Temperature C

1 – Expiration Date

Insulating rubber gloves have no expiry date and may be used as long as they comply with the periodic inspection.

2 – Periodic Inspection

Class 00  and Class 0 Gloves

  • Verification regarding air leaks and a visual inspection
  • However, a routine dielectric test may be performed at the owner’s request

Class 1, 2 , 3 and 4 Gloves

  • Verification regarding air leaks and and a visual inspection
  • Verification via a dielectric test to verify electric properties
  • Every 6 months to be re-tested, since they were first worn
  • Every 12 months, even those held in storage and not worn to be re-tested
Testing Insulating Gloves | Glove Markings

Testing Insulating Gloves | Glove Markings

3 – Field inspection & Stock

Do not confuse the periodic inspection with the inspection before each use. Together with the periodic inspection, it is strongly recommended that a visual inspection of the gloves is carried out before each use.

It is important to store the gloves in their UV-Resistant polythene bag and keep the gloves away from light, heat, and ozone. Ideally, the user should use our pneumatic tester to inflate the gloves for a good visual inspection and keep the gloves in our polypropylene store box for both transportation and storage.

4 – Special Properties

Gloves that pass the special properties (acid, oïl, ozone, very low temperature) are not resistant to chemicals. The test is to guarantee electrical protection in case of accidental contacts. After completing the electrical work, it is recommended to replace the contaminated gloves.


A periodic dielectric inspection service

  1. On receipt of your gloves to our premises, the gloves and sleeves are documented and then washed and dried.
  2. They are then visually inspected by our technicians, using inflation equipment.
  3. The next stage is electrical testing. Test equipment is used and tests are carried out according to the correct voltage for the class of glove. After the electrical testing has been completed they are again inflated and visually inspected. The gloves are then stamped and packed for return.
  4. Documentation accompanies the gloves and sleeves through all stages of testing and any failures are recorded. Any glove that fails will be destroyed. If the customer wishes, failures can be replaced with new items from our stocks.

Arc Flash PPE & Electrical Safety

Main UK Stockists & Distributors of Electrical Safety Products

Thorne & Derrick provide Electrical Safety Equipment to substation engineers, cable jointers, overhead linesmen and utility workers with PPE and electrical safety equipment including insulating gloves, voltage detectors, insulating matting and portable earthing to ensure worker safety when carrying out maintenance on LV-HV switchgear, substations, cables and electrical equipment.