Medium Voltage MV Separable Connectors – 3M


3M Type C Separable Connectors – 12kV, 24kV & 36kV | 630A & 1250A

Product Range: 3M™ Asymmetrical T-Plug IEC Separable Connectors
3M™ Type C Asymmetrical T-Plug IEC Separable Connectors provide fully screened medium voltage cable connections for dead-front equipment including switchgear and transformers.
Available for 12kV, 24kV and 36kV systems with 630A and 1250A Type C interfaces, the range includes both front T-Plug and rear T-Plug configurations for conductor sizes from 25mm² to 630mm². Kits include range-taking cable adapters and mechanical shearbolt cable lugs to support simplified product selection and installation.
3M Type C Medium Voltage Separable Connectors
3M Medium Voltage Asymmetrical T-Plug IEC Separable Connectors are designed to terminate medium voltage power cables onto dead-front apparatus including MV switchgear, transformers and other electrical equipment.
The connector system interfaces with 3M Type C bushings manufactured in accordance with EN 50180 and EN 50181, providing a compact connection solution for IEC-compliant medium voltage networks.
The 3M Type C connector range covers 12kV, 24kV and 36kV voltage classes and is offered with 630A and 1250A current ratings. Front T-Plug and rear T-Plug configurations enable equipment connections to be extended where network design requires multiple cable connections at the same Type C bushing interface.
This range-taking design enables a relatively small number of kits to cover conductor cross-sectional areas from 25mm² through to 630mm², helping simplify connector selection, ordering and stockholding.
When correctly installed and mated with the appropriate bushing or connector, the system provides a fully shielded and submersible electrical connection.
Contact our trusted experts for assistance specifying the correct 3M Type C separable connector.
Thorne & Derrick supply specialist medium voltage cable joints, terminations, connectors and cable accessories
for switchgear, transformers, substations, utilities, renewable energy and industrial power networks throughout the UK and worldwide.
Technical Specifications
Key Benefits & Features
✔ Type C interface for IEC medium voltage equipment
✔ Suitable for 12kV, 24kV and 36kV system voltages
✔ Available with 630A and 1250A current ratings
✔ Front T-Plug and rear T-Plug connector configurations
✔ Conductor range from 25mm² to 630mm²
✔ Meets CENELEC HD 629.1 and IEC 60502-4 requirements
✔ Interfaces with Type C bushings to EN 50180 and EN 50181
✔ Range-taking cable adapters reduce the number of kit variants required
✔ Mechanical shearbolt cable lugs included within connector kits
✔ Compact connection design for MV switchgear and transformer cable boxes
✔ Fully shielded connection when correctly mated with the appropriate bushing or plug
✔ Submersible connection when correctly assembled and mated
✔ 100% electrically tested during production
Type C Interface for Medium Voltage Switchgear & Transformers
The 3M Asymmetrical T-Plug connector is designed for Type C equipment interfaces following EN 50180 and EN 50181. This makes the range suitable for connecting medium voltage cables to compatible dead-front switchgear, transformers and associated distribution equipment.
Range-Taking Cable Adapter Technology
Range-taking cable adapters allow individual connector kits to accommodate a defined range of cable insulation diameters and conductor sizes. This can reduce the number of connector kits required to support multiple cable sizes and helps simplify product selection, procurement and stockholding.
Mechanical Shearbolt Cable Connection
3M Type C connector kits include mechanical shearbolt lugs for the conductor connection. The mechanical connection system removes the requirement to select and use a conventional compression lug and matching crimping die arrangement for the connector kit.
Front & Rear T-Plug Configurations
Front T-Plugs provide the primary cable connection to the Type C equipment bushing. Where network configuration requires an additional connection, compatible rear T-Plugs can be installed behind the front connector to provide an extended separable connector arrangement.
Fully Screened MV Connection
When installed and mated with the correct bushing or plug, the connector system provides a fully shielded electrical connection. This screened construction is
specifically developed for medium voltage cable connection systems used within modern compact switchgear and transformer installations.
Applications
✔ Medium voltage switchgear cable connections
✔ MV transformer cable connections
✔ Dead-front medium voltage equipment
✔ Type C bushing interfaces
✔ 11kV / 12kV distribution systems
✔ 20kV / 24kV distribution systems
✔ 33kV / 36kV distribution systems
✔ Utility substations
Supplementary Earthing Kits
Standard 3M T-Plug kits are designed for copper wire screened cables. Additional supplementary earthing kits are available where the cable uses copper tape, aluminium tube or copper wire with aluminium laminate screen constructions.
| SAP Number | Item Code | Application |
| 7100414146 | 94-PAE 610-1 AL-CT | Size 1 supplementary earthing kit for copper tape and aluminium tube screened cables up to 36kV |
| 7100413978 | 94-PAE 620-1 AL-CT | Size 2 supplementary earthing kit for copper tape and aluminium tube screened cables up to 36kV |
| 7100413572 | 94-PAE 621-1 CW-ALF | Supplementary earthing kit for copper wire with aluminium laminate screened cables up to 36kV |
Standards & Performance
3M™ Medium Voltage Asymmetrical T-Plug IEC Separable Connectors are designed for IEC-compliant medium voltage cable connection systems and meet the relevant requirements of CENELEC HD 629.1 and IEC 60502-4. The connectors interface with Type C bushings according to EN 50180 and EN 50181 and are
electrically tested during manufacture.
IEC 60502-4
CENELEC HD 629.1
EN 50180 / EN 50181
3M Type C Separable Connectors – FAQs
| Q1: What are 3M Type C separable connectors? 3M Type C separable connectors are medium voltage cable connection systems designed to connect MV power cables to compatible dead-front equipment, including switchgear, transformers and other electrical equipment using Type C interfaces. |
| Q2: What voltage ratings are 3M Type C connectors available for? The 3M Type C connector range is available for 12kV, 24kV and 36kV medium voltage systems, with 630A and 1250A current ratings depending on the selected connector. |
| Q3: What cable sizes do 3M Type C separable connectors cover? Depending on the connector kit selected, the range covers conductor sizes from 25mm² to 630mm². Cable selection should also be confirmed against the actual diameter over primary insulation. |
| Q4: What is the difference between a front T-Plug and a rear T-Plug? The front T-Plug provides the primary cable connection to the Type C equipment bushing. A compatible rear T-Plug, also known as a sub-T plug, can be installed behind the front connector where an additional cable connection is required. |
| Q5: What equipment can 3M Type C separable connectors be used with? 3M Type C connectors are designed for compatible dead-front medium voltage equipment, including MV switchgear, transformers and associated distribution equipment fitted with suitable Type C bushings. |