HV Discharge Rods | 11kV 33kV High Voltage Cable & Equipment Discharge Rod
Thorne & Derrick | Electrical Safety Equipment Distributors | LV MV HV Electrical Applications | Safe Discharge Rods
HV Discharge Rods
11kV 33kV High Voltage Cable & Equipment Discharge Rod
The Seaward SDR Series of HV Discharge Rods are used for the safe damp discharge of Medium & High Voltage (MV HV) cables or equipment under test at 11kV, 33kV and up to 35kV.
This electrical safety equipment will allow you to conduct the safe damp discharge of the residual charge on the MV HV cable or electrical equipment by limiting the discharge current.
There are two models of discharge rods for high voltage power systems: Seaward SDR11 (up to 11kV) and Seaward SDR35 (up to 33kV) both of which feature high-grade glass fibre tubing and incorporate encapsulated resistor chains.
Both models of discharge rods are supplied as standard with earthing wire (10 sq.mmx 5mtr), yellow green wire and carry case.
➡ Thorne & Derrick distribute the most extensive range of High Voltage Electrical Safety equipment to ensure safe working and protection against electrocution during the installation, jointing, terminating and testing of medium/high voltage power cables and electrical equipment including switchgear and transformers.
➡ Data Sheet Download | HV Discharge Rods 11kV 33kV
More from Seaward Electrical Safety
- Seaward Solar Utility Pro | Solar Cable & PV Installation Tester
- Seaward PV200 | Solar Cable & PV Installation Tester 1500V
- Seaward PV150 | Solar Cable & PV Installation Tester 1000V
- Seaward AGL-5 | Air Field Ground Lighting Tester & Voltage Detector 5kV
- Live Line Testers | High Voltage Rail Cable Testing Instrument | Seaward LLT
hv Discharge Rod Features | 11kV 33kV Models
- Discharge rod supplied with flexible cable with heavy duty brass clamp for easy earth connection
- Robust single pole device
- No switches
- Suitable for voltages to 11kV 33kV 35kV
- Supplied with cushion soft carrying case
Standard Discharge Rod Accessories (Supplied with Seaward SDR11 and Seaward SDR35)
- Earthing wire 10 sq.mm x 5mtr
- Yellow green wire
- Carry case

Seaward soft discharge rod 11kv supplied with flexible cable with heavy duty brass clamp for easy earth connection
High Voltage Cable & Equipment Discharge Rod
Technical Specification
HV Discharge Rod | Part Reference | Seaward SDR11 | Seaward SDR35 |
Discharge Voltage | 11kV AC/DC Maximum | 35kV AC/DC Maximum |
Peak Discharge Current | 1.1A for 100ms | 3.5A for 100ms |
Bleeder Resistance | 10K ohm | 10K ohm |
Discharge Capacitance | 10 µF | 6 µF |
Leakage Current at 35 KV AC | <50 µA | <50 µA |
Discharge Energy | 3675J | 3675J |
Cooling | Neutral | Neutral |
Total Size | 32mm x 750mm | 32mm x 950mm |
Weight | 2.2 kg (Net) | 2.2 kg (Net) |
Temperature | -5°C to 70°C | -5°C to 70°C |
Safety | IEC 61230, EMC Not Applicable | IEC 61230, EMC Not Applicable |

Seaward SDR11 for 11kV Medium | High Voltage Cables & Electrical Equipment
Discharge Rods & Sticks for Medium & High Voltage Power Networks | MV HV
➡ See also static discharge sticks for use on MV HV Electrical Power Systems up to 33kV (CATU CM50) – supplied with 6m length copper cable fitted with insulated alligator clamp and Tested in accordance to IEC 60855. Additionally, the Westminster range of discharge sticks from PENTA manufactured from 1.2 metre-long lightweight insulating tubing and fitted with a dischargeable hook are available for use on 11kV/35kV medium/high voltage power cables.

Discharge Rods | Westminster | PENTA | 11kV (15kV) to 33kV (35kV)

Static Discharge Sticks | CM50 CATU Electrical Safety Equipment
Operating Poles
An extensive range of Operating Poles manufactured from lightweight resin-impregnated fibreglass provide highest levels of electrical safety and insulation across standard voltages: 11kV, 33kV 66kV. The operating poles can be inter-connected to achieve extended lengths for both Medium Voltage & High Voltage (MV-HV) overhead line and substation applications. The poles are compliant to ENA Technical Specification TS 41-21 which combines substation and overhead line portable earthing requirements (previously covered by ENA TS 43-81).

Operating Poles Sticks Rods | MV HV 11kV 33kV 66kV
Electrical Safety MV HV | Live Line Testers | Insulating Sticks | Portable Earthing | Voltage Detectors