CW Aluminium Cable Glands – Prysmian Bicon 432LSF Glands (LUL London Underground Approved)

CW Cable Glands – Prysmian Bicon 432LSF Glands (LUL London Underground Approved)

CW Aluminium Cable Glands

Prysmian Bicon CW cable glands are low smoke zero halogen cable glands for use with LS0H aluminium wire armoured cables and are LUL approved industrial cable glands.

CW cable gland kits are used for galvanised steel single wire armour plastic or rubber sheathed cables in dry, dust free and non-hazardous areas – the CW gland kit includes:

  • CW-AL Cable Gland
  • Aluminium Earth Tag
  • Aluminium Locknut
  • LSOH Low Smoke Zero Halogen Shroud (2 per kit up to and including 25mm gland size)

Cw aluminium Cable Gland Kits

LV Cable Terminations

Prysmian Bicon CW cable gland kits comply with BS EN 50262 & BS 6121-1: 1989. Suitable for glanding all Aluminium wire armoured cables inc: BS 6724, BS 7835 – stranded copper conductors can be terminated using Cembre crimp or Pfisterer shearbolt cable lugs. Constructed using 6082-T6 Alluminium alloy. CW cable gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface.

Saffire 6491B – Single Core Zero Halogen, Low Smoke Cable (OHLS®)

Saffire 6242B – Flat, Twin Core Zero Halogen, Low Smoke Cable (OHLS®)

Saffire BS6724 – Multi-Core Armoured Zero Halogen, Low Smoke Cable (OHLS®)

Saffire BS6724 Auxiliary – Multi-Core Armoured Zero Halogen, Low Smoke Cables (OHLS®)

Saffire Railsure – London Underground Approved Single Core Zero Halogen, Low Smoke Cable (OHLS®)

 

The gland kit is suitable for service temperatures from -20ºC to +90ºC.

Prysmian

Prysmian Cable Glands – Industrial, Hazardous Area & High Voltage Cable Terminations

Prysmian Bicon CW Cable Gland Kits (LUL London Underground Approved)

Technical Specification

Prysmian Bicon Reference Size Quantity Per Kit Under Armour Max Ø (A) Cable Dimensions (mm) CW Cable Gland Dimensions (mm)
Cable Diameter Ø (B) mm) Armour Wire Ø Entry Thread (D) Thread Length (E) Protrusion Length (F) Hexagon
Min Max A/F (G) A/C (H)
432LSF-52 20S 2 11.6 8.0 15.8 0.9 M20×1.5 10 46 25.7 29.2
432LSF-53 20 2 13.9 11.7 20.8 0.9/1.25 M20×1.5 10 46 30.5 34
432LSF-55 25 2 19.9 17.0 27.2 1.25/1.6 M25×1.5 10 51 37.6 42.2
432LSF-56 32 1 26.2 23.5 33.5 1.6/2.0 M32×1.5 10 56 47.3 53.6
432LSF-57 40 1 32.1 29.0 39.9 1.6/2.0 M40×1.5 15 59 56.4 61.5
432LSF-58 50S 1 38.1 38.0 46.2 2.0/2.5 M50×1.5 15 64 65.5 72.1
432LSF-59 50 1 44.0 39.5 52.6 2.0/2.5 M50×1.5 15 64 70.1 77.2
432LSF-61 63 1 55.9 51.3 65.3 2.5 M63×1.5 15 67 80 87.4
432LSF-63 75 1 67.9 62.5 78.0 2.5 M75×1.5 15 76 98.8 109.2
Prysmian Bicon CW (LUL) Cable Gland Kits - Dimensions Illustration

Prysmian Bicon CW (LUL) Cable Gland Kits – Dimensions Illustration

Prysmian Cable Glands

Cable Cleats

Terminating Low Voltage Cables

Prysmian cable gland kits available in brass, aluminium, nickel plated or stainless steel for cable termination of wire armoured, wire braided and unarmoured cables, including low smoke zero halogen cables in industrial non-hazardous areas. Flameproof and explosion proof Ex e/Ex d hazardous area cable glands with ATEX and IECEx certifications also available.

Also a complete range of Prysmian single, trefoil and bundled LV-HV cable cleats.

Prysmian Bicon BW Brass, CW Brass, CW Aluminium and A2 Brass Cable Glands

Prysmian Bicon BW Brass, CW Brass, CW Aluminium and A2 Brass Cable Glands

➡ For complete information, technical specifications and ordering details about CW (LUL) Cable Glands see the product sections below.