Lucy House Service Cut Out Single Pole CNE – 100A
Lucy House Service Cut Out Single Pole CNE – 100A
Lucy House Service Cut Outs Single Pole CNE are available in 100A ratings – house service cut outs single phase accept BS 1361 cylindrical cartridge fuses, have combined Neutral and Earth blocks and conform to BS 7657:2010.
Lucy House Service Cut Out Single Pole CNE
Lucy House Service Cut Out Single Pole CNE
Features & Benefits
- Two incoming and outgoing Phase and Neutral terminations which accept up to 35sqmm conductors in either copper or aluminium, stranded or solid
- Identical incoming and outgoing flange profile means that unit is rotatable through 180 degrees
- Silver plated Phase terminal contact block
- Serrated bores on Phase/Neutral terminal contact blocks with two M8 hexagon drive pinching screws per conductor
- Two incoming and two outgoing terminals on Earth block each accepting up to 25sqmm conductors
- Safety interlocked mouldings. N/E cover moulding cannot be removed until fuse carrier has been withdrawn
- Sealing wire facility
- Blanking plugs for unused cable entries provided
- Additional accessories include cable cover, cable sealing chamber and busbar extensions
Lucy House Service Cut Out Single Pole CNE – 100A
Technical Specification
Lucy House Service Cut Out Single Pole Rating | |
60/80A | 57 x 30mm Type IIb BS 1361 |
Construction | |
Body, base and cover | Glass reinforced polyester DMC in RAL 7035 colour |
Terminal blocks | Brass (silver plated on Phase) |
Fuse link contacts | Copper |
Performance | |
Rated voltage | 240/415V a.c |
Supply frequency | 50-60Hz |
Flammability rating | UL94 VO, self-extinguishing 30 seconds at 960°C |
Recommended terminal torque | 3.25Nm |
Fuse short circuit rating | 33kA at 0.3pf |
Dimensions | |
Height | 98mm |
Width | 85mm |
Depth | 96mm |
Weight (excluding fuse) | 0.73kgs |
Lucy House Service Cut Out Single Pole CNE – Dimensions