Cable Breakouts | Heat Shrink Cable Termination Breakouts – 4 Core Cables

Cable Breakouts | Heat Shrink Cable Termination Breakouts – 4 Core Cables
Heat Shrink Cable Breakouts & Moulded Parts – 3M SKE 4-Way Cable Breakouts
Cable Breakouts
3M SKE 4-Way cable breakouts and 3M cable end caps are designed for quick and easy insulation and sealing of 4 core cable end or crutches, and provide resistance to abrasion, weathering and chemical attack.
Each heat shrink cable breakout will cover a wide range of sizes and different types of cables – also 3 core cable breakouts are also available.
These 4 core heat shrinkable cable breakouts are made from semi-rigid, cross-linked modified polyolefin material which is internally coated with hot melt adhesive. The materials used are zero halogen. On application of heat the adhesive melts and the part shrinks forming a perfect watertight seal – the 4 core cable breakouts can be used for insulating/sealing of cable crutches for indoor and outdoor applications.
Thorne & Derrick distribute complete range of cable terminations in both heat shrink and Cold Shrink for LV (Low Voltage), MV (Medium Voltage) and HV (High Voltage) cables and power systems.
➡ Read about several methods including use of Cold Shrink to repair cable damage.
Heat Shrink Cable Breakouts
4 Core
Dimensions
| 3M Heat Shrink Breakout Part Number | Application Range on LV Cable |
Ø Neck Exp. |
Ø Neck Recov. |
Ø Finger Exp. |
Ø Finger Recov. |
Length Recov. |
Wall Thickness Neck Recov. |
Wall Thickness Finger Recov. |
| sqmm | mm | mm | mm | mm | mm | mm | mm | |
| SKE 4F/0 | – | 28 | 09 | 08 | 02 | 80 | 2.0 | 1.5 |
| SKE 4F/1+2 | 4 – 35 | 35 | 15 | 15 | 04 | 100 | 3.8 | 1.8 |
| SKE 4F/3+4 | 25 – 150 | 57 | 23 | 30 | 06 | 170 | 4.0 | 3.0 |
| SKE 4F/5 | 120 – 400 | 95 | 36 | 38 | 14 | 220 | 3.5 | 2.5 |
| SKE 4F/6 | – | 117 | 36 | 46 | 14 | 220 | 3.5 | 2.5 |

Heat Shrink Cable Termination Breakouts – 4 Core Cables
Heat Shrink Cable Termination Breakouts
Material Characteristics
| Physical Properties | Value | Test Method |
| Density | 1.05 ± 0.2 g/cm3 | ASTM D-1505/D=M/V |
| Hardness | 45 ± 3 shore D | ASTM D-2240 |
| Tensile strength | 10 N/sqmm | ASTM D-412 / ISO 37 |
| Ultimate elongation | 300 % | ASTM D-412 / ISO 37 |
| Water absorption | 0.15 % | ASTM D-570 / ISO 62 |
| Longitudinal Shrinkage | 10 % | – |
| Recovery Temperature | 120 °C | IEC – 216 |
| Peel strength | 100 N/25 mm | Rolling Drum method |
| Thermal Tests | ||
| Operating temperature range | – 30 °C, + 135 °C | DIN 53 466 |
| Thermal Ageing (150 °C for 168 hrs) | ||
| Tensile strength | 8 N/sqmm | ASTM D-412 / ISO 37 |
| Ultimate elongation | 200 % | ASTM D-412 / ISO 37 |
| Flammability | Not self extinguishing | ASTM D 876 |
| Low Temperature Flexibility | – 40 °C | ASTM D 2671C |
| Electrical Properties | ||
| Volume resistivity | 1 x 1013 Ohm-cm | ASTM D-257 / IEC 93 |
| Dielectric strength | 10 kV/mm | ASTM D-149 / IEC 243 |
| Chemical Properties | ||
| Corrosion | None | ASTM D 2671 |
Download