3M 93-EB63-3
11kV Cable Termination Cold Shrink – 3M 93-EB63-3
3 Core Outdoor Cable Termination
These 3M QTII type cable terminations utilise Cold Shrink technology to terminate and connect MV HV cables – 3M 93-EB63-3 is a medium voltage cold shrink cable termination suitable for connecting 3 core polymeric (XLPE EPR) insulated cables up to 11kV with copper wire or copper tape screen.
11kV
Cable termination suits 11kV cables with 50sqmm, 70sqmm 3 core conductors.
The versatile design of the prefabricated one piece cold shrink cable termination body allows installation on a wide range of cable sizes and types (without the need for special tools) and a fast and easy installation at temperatures ranging from – 20°C to + 50°C.
Order Code – 3M 93-EB63-3
Contact T&D Sales for further selection guidance on 3M Cold Shrink Terminations:
- Part Number – 3M 93-EB63-3
- 11kV Cable Termination (MV Medium Voltage)
- 6.6/11(12) kV Cables
- Cable Termination Type – Cold Shrink (Silicone)
- Manufacturer & Range – 3M QTII Termination
- Termination Outdoor & Indoor (Substation, Switchgear, Transformer, Motor 11kV)
- Number Of Cores – 3 Core
- Conductors – 185-300sqmm (Outdoor), 120-240sqmm (Indoor)
- Diameter Over Primary Insulation – 21.3-35mm
- Max. Lug Diameter Accepted (mm) – 35mm
- Includes integrated stress control device, silicone elastomeric insulation & silicone tape for moisture sealing
- Includes armour continuity components, re-jacketing tubes and three core cold shrink breakout boots
- Skirts are integrated for faster & easier installation
- Shelf Life – 3 years when stored between -40ºC to +50ºC
- Meets & exceeds European Standard CENELEC HD 629.1 and IEC 60502-4
- Single Core & Outdoor Pole-Mounted Terminations Available
- Also: 3M Cold Shrink Cable Joints MV HV
3M termination kits include sufficient components to terminate a 3 core cable, including breakout. Bushing boots optional.
Product Identification
3M QTII Series Cold Shrink Termination kits are marked with supplier name, cable cross section ranges (sqmm), voltage class and cable type, storage conditions and 3M manufacturing codes for product traceability.
Termination Performance Tests
3M™ QTII 93-EB Series Cable Terminations, manufactured using Cold Shrink technology, meet and exceed the requirements of the European standard CENELEC HD 629.1 as well as IEC 60502-4.
Cold Shrink Storage
The shelf life of 3M 93-EB63-3 cold shrink terminations is specified as 3 years. Temperature: – 40°C to +50°C.
3M 11kV Cable Termination Part Number | Application Range Guide (sqmm) 6.6/11kV Outdoor |
Application Range Guide (sqmm) 12/20kV Indoor |
Diameter Over Primary Insulation (mm) | Maximum Lug Diameter Accepted (mm) |
3M 93-EB61-3 | 50-70sqmm | 25-35sqmm | 16.0-28.4mm | 28mm |
3M 93-EB62-3 | 95-150sqmm | 50-120sqmm | 16.0-28.4mm | 28mm |
3M 93-EB63-3 | 185-300sqmm | 120-240sqmm | 21.3-35mm | 35mm |
Watch Video ➡ 3M Cold Shrink Terminations – QTII Standard Terminations

3M QTII Cold Shrink Cable Terminations | MV HV | 3.3/6.6(7.2)kV 11kV 33kV 26/45(52)kV
Medium & high voltage cable glands, cleats & accessories
➡ See full range of 3M Cold Shrink Cable Terminations or visit only 11kV 3 Core Outdoor Terminations.