Low Voltage LV Industrial Cable Joints – Prysmian JSTCC

Low Voltage LV Industrial Cable Joints – Prysmian JST

Low Voltage LV Industrial Cable Joints – Prysmian JST

Prysmian JSTCC industrial straight cable joints are used for LV cables with copper & aluminium conductors ranging from 1.5sqmm to 300sqmm and have transparent vacuum formed shells which offer greater working dimensions & interlocking flange seals.

JSTCC low voltage cable joints include low hazard isocynate free JEM resin which has extremely low viscosity and enhanced adhesion and comes with mechanical connectors which require no special tools.

T&D can offer the full range of Prysmian cable joints for low voltage industrial cable jointing applications.

Prysmian JSTCC Cable Joints

Technical Data

  • Low Voltage Straight Joints for 600/1000 Volt SWA cables to BS5467, BS6346 and IEC 502 – with Polymeric Insulation, aluminium or copper conductors.
  • Tested & Approved to BS EN 50393 & ENA ER C81
  • Includes Mechanical connectors (4 cores) requiring no special tooling and constant Force Spring Armour Bonds Included

Prysmian JEM Resin Features & Benefits

  • Easier resin mixing by the cable jointer in “Twin Pack” totally enclosed mixing in a clear laminate sachet.
  • Extremely low mix viscosity allows void free cable joint filling.
  • JEM Resin is insensitive to moisture and will cure under water.
  • Enhanced adhesion to XLPE, MDPE, PVC & lead covered cables.
  • High flash point, non-flammable liquid – no special storage or transport requirements.
  • Not classified as irritating to the skin or eyes.
  • Does not cause skin sensitisation.

CABLE JOINTS Dimensions

Prysmian Cable Joint Reference Dimensions
A B C Minimal Box Entry ∅ (D) Maximum Box Entry ∅ (E)
JST6CC 240mm 115mm 75mm 12mm 22mm
JST16CC 310mm 125mm 85mm 20mm 35mm
JST35CC 390mm 130mm 100mm 24mm 40mm
JST95CC 620mm 160mm 130mm 27mm 51mm
JST185CC 795mm 230mm 205mm 40mm 65mm
JST300CC 950mm 240mm 210mm 55mm 80mm

➡ Prysmian Cable LV MV HV Accessories | Cable Glands |  Cable Cleats | 11kV Terminations Heat Shrink

Prysmian JSTCC LV Cable Joints - Dimensions

Prysmian JSTCC LV Cable Joints – Dimensions

LOW VOLTAGE CABLE JOINTS Selection Table
Nominal Area of Conductor Two Core Ref Three Core Ref Four Core Ref
1.5sqmm JST6CC JST6CC JST6CC
2.5sqmm JST6CC JST6CC JST6CC
4sqmm JST6CC JST6CC JST6CC
6sqmm JST6CC JST6CC JST6CC
10sqmm JST6CC JST16CC JST16CC
16sqmm JST16CC JST16CC JST16CC
25sqmm JST16CC JST16CC JST35CC
35sqmm JST35CC JST35CC JST35CC
50sqmm JST95CC JST95CC JST95CC
70sqmm JST95CC JST95CC JST95CC
95sqmm JST95CC JST95CC JST95CC
120sqmm JST185CC JST185CC JST185CC
150sqmm JST185CC JST185CC JST185CC
185sqmm JST185CC JST185CC JST185CC
240sqmm JST300CC JST300CC JST300CC
300sqmm JST300CC JST300CC JST300CC

➡ For jointing all types of XLPE, EPR and PILC power, control and instrumentation cables in straight, branch or transition arrangement including zero halogen, fire resistant and hazardous areas see Resin Cable Joints