Low Voltage LV Industrial Cable Joints – Prysmian JSTCC
Prysmian JSTCC industrial straight cable joints are used for LV cables with copper & aluminium conductors ranging from 1.5sqmm to 300sqmm and have transparent vacuum formed shells which offer greater working dimensions & interlocking flange seals.
JSTCC low voltage cable joints include low hazard isocynate free JEM resin which has extremely low viscosity and enhanced adhesion and comes with mechanical connectors which require no special tools.
T&D can offer the full range of Prysmian cable joints for low voltage industrial cable jointing applications.
Prysmian JSTCC Cable Joints
Technical Data
- Low Voltage Straight Joints for 600/1000 Volt SWA cables to BS5467, BS6346 and IEC 502 – with Polymeric Insulation, aluminium or copper conductors.
- Tested & Approved to BS EN 50393 & ENA ER C81
- Includes Mechanical connectors (4 cores) requiring no special tooling and constant Force Spring Armour Bonds Included
Prysmian JEM Resin Features & Benefits
- Easier resin mixing by the cable jointer in “Twin Pack” totally enclosed mixing in a clear laminate sachet.
- Extremely low mix viscosity allows void free cable joint filling.
- JEM Resin is insensitive to moisture and will cure under water.
- Enhanced adhesion to XLPE, MDPE, PVC & lead covered cables.
- High flash point, non-flammable liquid – no special storage or transport requirements.
- Not classified as irritating to the skin or eyes.
- Does not cause skin sensitisation.
CABLE JOINTS Dimensions
Prysmian Cable Joint Reference | Dimensions | ||||
A | B | C | Minimal Box Entry ∅ (D) | Maximum Box Entry ∅ (E) | |
JST6CC | 240mm | 115mm | 75mm | 12mm | 22mm |
JST16CC | 310mm | 125mm | 85mm | 20mm | 35mm |
JST35CC | 390mm | 130mm | 100mm | 24mm | 40mm |
JST95CC | 620mm | 160mm | 130mm | 27mm | 51mm |
JST185CC | 795mm | 230mm | 205mm | 40mm | 65mm |
JST300CC | 950mm | 240mm | 210mm | 55mm | 80mm |
➡ Prysmian Cable LV MV HV Accessories | Cable Glands | Cable Cleats | 11kV Terminations Heat Shrink
LOW VOLTAGE CABLE JOINTS Selection Table
Nominal Area of Conductor | Two Core Ref | Three Core Ref | Four Core Ref |
1.5sqmm | JST6CC | JST6CC | JST6CC |
2.5sqmm | JST6CC | JST6CC | JST6CC |
4sqmm | JST6CC | JST6CC | JST6CC |
6sqmm | JST6CC | JST6CC | JST6CC |
10sqmm | JST6CC | JST16CC | JST16CC |
16sqmm | JST16CC | JST16CC | JST16CC |
25sqmm | JST16CC | JST16CC | JST35CC |
35sqmm | JST35CC | JST35CC | JST35CC |
50sqmm | JST95CC | JST95CC | JST95CC |
70sqmm | JST95CC | JST95CC | JST95CC |
95sqmm | JST95CC | JST95CC | JST95CC |
120sqmm | JST185CC | JST185CC | JST185CC |
150sqmm | JST185CC | JST185CC | JST185CC |
185sqmm | JST185CC | JST185CC | JST185CC |
240sqmm | JST300CC | JST300CC | JST300CC |
300sqmm | JST300CC | JST300CC | JST300CC |
➡ For jointing all types of XLPE, EPR and PILC power, control and instrumentation cables in straight, branch or transition arrangement including zero halogen, fire resistant and hazardous areas see Resin Cable Joints