Prysmian FP200 Flex Fire Resistant Cable – Standard Fire Proof Wiring Cable

Prysmian FP 200 Flex Fire Resistant Cables | Joints | Cleats | Glands
Fire Resistant Cable
Prysmian FP200 Flex
Prysmian FP200 Flex is fire resistant cable for use in fire detection and fire alarm systems for buildings, voice alarm systems, emergency lighting systems and other essential service circuits.
FP200 Flex is a hard skin, flexible, easy to install and easy to terminate fire resistant cable and incorporates Insudite cores and especially suitable where a more flexible cable is required.
Prysmian FP200 Flex Fire Resistant Cable
Features & Benefits
- Plain annealed copper stranded (class 2) conductor to meet the requirements of BS EN 60228 class 2
- High performance damage resistant Insudite insulation, British Standard Type E15
- FP200 cable is available in brown-blue, brown-black-grey or blue-brown-black-grey
- Aluminium / Polyester tape screen in contact with full size tinned annealed copper stranded circuit protective conductor
- Robust thermoplastic LS0H sheath – white or red with other colours available on special order. For external exposure the use of white sheath is recommended
- Temperature range -25 to +70ºC
- Bending radius fixed r=4D
- Medium mechanical impact protection
- Fire performance BS EN 60332-1-2, BS EN 50266-24
- Halogen free fire resistant cables – BS EN 60754-1
- Low smoke emissions – BS EN 61034-2
- Fire resistance – BS 6387 Category CWZ, BS EN 50200 PH30
Prysmian FP200 Flex Fire Resistant Cable
Performance Standards
- 300/500V
- BS7629-1
- BASEC Approved
- LPCB Approved

Prysmian FP Cables – FP200 Flex Fire Resistant Cables for Emergency & Essential Building Services
Prysmian FP200 Flex Fire Resistant Cable
Nominal Cross Sectional Area (sqmm) | Conceptual Construction (no./mm) | Mean Overall Diameter (mm) | Approximate Cable Weight (kg/km) | Maximum Conductor Resistance at 20ºC (ohms/km) | Current Rating DC or Single Phase AC (Enclosed Amps) | Current Rating Three Phase DC (Clipped Amps) | Volt Drop DC or Single Phase AC (mV/A/m) | Recommended Accessories | |
LS0H Fixing Clips (1) | Nylon LS0H Gland (2) | ||||||||
Two Core | |||||||||
1.5 | 7/0.53 | 8.2 | 99 | 12.1 | 16.5 | 19.5 | 29 | AP7 | 251/GL2520 |
2.5 | 7/0.67 | 9.6 | 145 | 7.4 | 23 | 27 | 18 | AP9 | 251/GL2520 |
Three Core | |||||||||
1.5 | 7/0.53 | 8.7 | 120 | 12.1 | 16.5 | 19.5 | 29 | AP8 | 251/GL2520 |
2.5 | 7/0.67 | 10.2 | 176 | 7.4 | 23 | 27 | 18 | AP10 | 252/GL2520 |
Four Core | |||||||||
1.5 | 7/0.53 | 9.7 | 149 | 12.1 | 16.5 | 19.5 | 29 | AP9 | 251/GL2520 |
2.5 | 7/0.67 | 11.4 | 218 | 7.4 | 23 | 27 | 18 | AP11 | 252/GL2520 |
- (1) Recommended clip spacing 300mm horizontal and 400mm vertical
- (2) Brass glands may be used as an alternative
- Minimum recommended cable installation temperature 0°C.
- Installation methods for current rating in accordance with BS7671/IEE wiring regulations
- The tabulated ratings are based upon a 30°C ambient temperature at 70°C operating temperature.
- For other ambient temperatures or where several circuits are grouped together, appropriate rating factors should be applied.
FP200 Flex Fire Resistant Cable – Temperature Ratings Factor
Ambient Temperature ºC | 25 | 30 | 35 | 40 | 45 | 50 | 55 | 60 |
Rating Factor | 1.03 | 1.00 | 0.94 | 0.87 | 0.79 | 0.71 | 0.61 | 0.50 |
FP200 Flex Fire Resistant Cable – Rating Factors For Groupings
Number of Circuits | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
Rating Factor | 0.80 | 0.70 | 0.65 | 0.60 | 0.57 | 0.54 | 0.52 | 0.50 |

Prysmian FP Cables | FP100Â | FP200 Gold | FP400 | FP600S
FP Cable Accessories For Fire Resistant Cables
CABLE jOINTSÂ ♦ CLEATSÂ ♦ GLANDS
In order to protect the integrity of Prysmian FP fire resistant cables they should be installed in accordance with the manufacturers guidance including the use of fire resistant cable cleats, joints and glands.
View the complete range of Prysmian Cable Accessories for LV MV HV Cables, including 11kV-33kV networks or see product groups:
âž¡ For offshore cables, including BFOU and RFOU see Prysmian Draka.