Prysmian FP600S is the ultimate fire resistant cable for power and control of emergency, life safety and fighting systems used in buildings.

FP600S has been designed and developed for the toughest British Standard fire test for cables, BS8491 F120. It meets or exceeds the fire resistance requirements of Category 1,2 and 3 which makes it suitable for power and control circuits as defined in BS8519:2010.

The cable is featured on the LU – Approved Products Register approved by London Underground meeting the criteria for LU 1-085 A3 and is suitable for use in section 12 (underground and surface) applications.

FP600S also meets or exceeds low fire hazard requirements of LS0H cable.

Prysmian FP600S Fire Resistant Cable

Features & Benefits

  • Plain annealed copper stranded conductor to meet the requirements of BS EN 60228 class 2
  • Mineral ceramic (Mica/Glass) fire resistant tape. 90°C cross-linked insulation
  • Extruded LS0H bedding and sheath with single layer of galvanised steel wire armour
  • FP400 cable is available in brown-black, brown-black-grey and blue-brown-black-grey as standard. Available to special order in red-black, red-yellow-blue or black-red-yellow-blue on request. 7-37 cores in white with printed numbers
  • Temperature range -25 to +90ºC
  • Bending radius 8D
  • High mechanical impact protection
  • Fire performance BS EN 60332-1-2, BS EN 60332-3-24
  • Halogen free fire resistant cables – BS EN 60754-1
  • Low smoke emissions – BS EN 61034-2
  • Fire resistant BS 7846 F120, BS 8491 120 min

Prysmian FP600S Fire Resistant Cable

Performance Standards

  • 600/1000V
  • BS7846 F120
  • BS8491 120minutes
  • Use for BS8519 category 1,2 & 3 power and control circuits
  • BASEC Approved
  • LPCB Approved
  • London underground approved LU 1-085A  (Previously ‘Section 12’)
  • Low smoke, zero halogen, flame retardant
Prysmian FP Fire Resistant Cables

Prysmian FP Cables – FP600S Fire Resistant Cables for Emergency & Essential Building Services

Prysmian FP600S Fire Resistant Cable – Single Core Cables

Nominal Cross Sectional Area (sqmm)Approximate Overall Diameter (mm)Approximate Diameter Under Armour (mm)Nominal Diameter of Armour Wires (mm)Approximate Cable Weight (kg/km)Maximum Conductor Resistance at 20ºC (Ω/km)Short Circuit Rating (1 second) of Conductor kACurrent Rating Three Phase AC Clipped Direct (Amps)Current Rating Three Phase AC Free Air or Perforated Tray (Amps)Volt Drop Three Phase AC (mV/A/m)Recommended Accessories
Claw Cleat Ref NumberBrass Gland Ref Number
Three Core
421151.258004.610.57424410370CG04LSF25CW
621151.258203.080.8653566.8370CG04LSF25CW
1023171.2510501.831.473784.0370CG05LSF25CW
1624191.2514001.152.294992.5370CG05LSF25CW
2529221.620000.7273.61241311.65370CG06LSF32CW
3531241.623000.5245.01541621.15370CG06LSF32CW
5032251.628000.3877.11871970.87370CG07LSF32CW
7036291.636000.26810.02382510.60370CG07LSF40CW
9540322.045000.19313.62893040.45370CG08LSF50SCW
12043352.054000.15317.23353530.37370CG08LSF50SCW
15048392.569000.12421.43864060.30370CG09LSF50CW
18552432.582000.099126.54414630.26370CG09LSF63CW
24057472.5101000.075434.35205460.21370CG09LSF63CW
30062522.5122000.060142.95996280.185370CG12LSF63CW
40069582.5150000.047057.26737280.165370CG13LSF75CW
Four Core
421151.258004.610.57424410370CG04LSF25CW
623171.259503.080.8653566.8370CG05LSF25CW
1024191.2512001.831.473784.0370CG05LSF25CW
1627201.2516001.152.294992.5370CG06N/A
2532241.624000.7273.61241311.65370CG07LSF32CW
3535271.628000.5245.01541621.15370CG07LSF40CW
5036291.632000.3877.11871970.87370CG07LSF40CW
7041321.645000.26810.02382510.60370CG08LSF50SCW
9544362.057000.19313.62893040.45370CG08LSF50SCW
12049402.073000.15317.23353530.37370CG09LSF50CW
15055442.586000.12421.43864060.30370CG10LSF63CW
18559482.5105000.099126.54414630.26370CG11LSF63CW
24064542.5129000.075434.35205460.21370CG12LSF63CW
30070592.5155000.060142.95996280.185370CG14LSF75CW
40079663.15201000.047057.26737280.165370CG15LSF85CW
Five Core
422171.259004.610.6424410370CG05LSF25CW
624181.2510703.080.953566.8370CG05LSF25CW
1027211.2513901.831.473784.0370CG06N/A
1630231.619001.152.294992.5370CG06LSF32CW
2534261.625000.7273.61241311.65370CG07LSF40CW
3537291.631000.5245.01541621.15370CG07LSF40CW
Nominal Cross Sectional Area (sqmm)Approximate Overall Diameter (mm)Approximate Diameter Under Armour (mm)Nominal Diameter of Armour Wires (mm)Approximate Cable Weight (kg/km)Maximum Conductor Resistance at 20ºC (Ω/km)Current Rating DC or Single Phase AC Clipped Direct (Amps)Current Rating DC or Single Phase AC Free Air (Amps)Volt Drop DC (mV/A/m)Volt Drop Single Phase AC (mV/A/m)Recommended Accessories
Claw Cleat Ref NumberBrass Gland Ref Number
Two Core
421151.258004.6149521212370CG04LSF25CW
621151.258003.0862667.97.9370CG04LSF25CW
1022161.258001.8385904.74.7370CG05LSF25CW
1623171.2510001.151101152.92.9370CG05LSF25CW
2526201.2513000.7271461521.851.9370CG06N/A
3530231.618000.5241801881.351.35370CG06LSF32CW
5031241.622000.3872192280.981.00370CG06LSF32CW
7033261.626000.2682792910.670.69370CG07LSF32CW
9535272.034000.1933383540.490.52370CG07LSF40CW
12039302.041000.1533924100.390.42370CG08LSF50SCW
15042332.047000.1244514720.310.35370CG08LSF50SCW
18546362.561000.09915155390.250.29370CG09LSF50CW
24051412.575000.07546076360.1950.24370CG09LSF50CW
30056452.590000.06016987320.1550.21370CG10LSF63CW
40061502.5110000.04707878470.1200.19370CG11LSF63CW
  • No LPCB approval for 5 Core, BASEC approval for 1.5-10mm² inclusive
  • Circular conductor 4.0 – 35sqmm. .
  • Shaped conductor 50sqmm and above.
  • Current ratings in accordance with BS 7671/IET Wiring Regulations.
  • The tabulated ratings are based upon a 30°C ambient temperature and 90°C operating temperature.
  • Minimum recommended installation temperature 0°C.
  • Suitable for indoor and outdoor installations. Should be installed in accordance with BS 7671/IET Wiring Regulations or any other appropriate national regulations.
  • Suitable for direct burial, trough, tray, ladder or other installations requiring a robust armoured cable.
Prysmian FP Cables

Prysmian FP Cables | FP100 | FP200 Flex | FP200 Gold | FP400

FP Cable Accessories For Fire Resistant Cables

FP Cables Cleats Glands Joints

CABLE jOINTS ♦ CLEATS ♦ GLANDS

In order to protect the integrity of Prysmian FP fire resistant cables they should be installed in accordance with the manufacturers guidance including the use of fire resistant cable cleats, joints and glands.

View the complete range of Prysmian Cable Accessories for LV MV HV Cables, including 11kV-33kV networks or see product groups:

➡ For offshore cables, including BFOU and RFOU see Prysmian Draka.

Data Sheets