Arc Flash Protection | A Whitepaper on Clothing & Garment Selection
Published 18 Aug 2020

Author: Hamilton Smith – Technical Sales Manager | 2020
Arc Flash Clothing and IEC 61482-2:2018 Explained
Arc flash protective clothing helps reduce the risk of serious thermal injuries when workers are exposed to electrical arc hazards.
However, selecting the correct clothing requires an understanding of arc flash risks, protective fabric performance and the relevant testing standards.
This technical article explains the principles behind IEC 61482-2:2018, including open arc testing, box testing and the different ratings used to describe protective clothing.
It also examines how fabrics, garment construction and clothing layers affect protection.
Originally published in 2020, the article includes technical guidance and product information from ProGARM, a manufacturer of arc flash protective workwear.
Why Is Arc Flash PPE Important?
An electrical arc can release intense heat in a fraction of a second. Workers exposed to this energy may suffer severe burns and other injuries.
Suitable arc flash clothing can help reduce thermal injury risks. However, PPE cannot prevent an electrical fault or eliminate every hazard.
For this reason, employers must assess the risks and implement appropriate safety controls before selecting protective garments.
What Is an Arc Flash?
An arc flash is the intense light and heat released during an electrical arc fault.
An arc can develop when electrical current passes through air between conductors or between an energised conductor and earth.
Depending on the fault conditions, this can release a large amount of energy very quickly.
Arc Flash Explained in Simple Terms
Electrical current normally travels through a conductor. However, an insulation failure or accidental contact can create an unintended path.
Under certain conditions, electricity can then arc through the surrounding air.
The resulting discharge may produce:
- Intense heat capable of causing serious burns.
- Bright light and ultraviolet radiation that can injure the eyes.
- Molten metal and hot particles released from electrical equipment.
- Pressure waves that may cause physical injuries.
- Fire and equipment damage resulting from the electrical fault.
The original article described arc temperatures reaching approximately 19,000°C. However, actual temperatures and energy exposure depend on the electrical fault and surrounding conditions.
Watch an Arc Flash in Slow Motion
The following video shows a 480V electrical arc flash event in slow motion.
It demonstrates how quickly an electrical fault can develop and why workers must follow suitable safety procedures.
Where and When Can Arc Flash Occur?
Arc flash hazards can arise wherever electrical equipment presents a risk of arcing.
For example, workers may encounter these hazards during installation, inspection, testing or maintenance.
Industries Exposed to Arc Flash Hazards
The original article identified several sectors where arc flash protection may be required.
- Manufacturing and industry: Electrical maintenance, machinery and power distribution systems.
- Power generation: Electrical equipment used in conventional and renewable energy installations.
- Utilities: Cable installation, excavation, street lighting and electrical distribution.
- Rail: Electrical infrastructure, electrification and maintenance activities.
- Petrochemical facilities: Electrical maintenance and operations involving relevant electrical hazards.
- Electric vehicle infrastructure: Electrical installation and maintenance work involving EV charging equipment.
Different tasks present different exposure levels. Therefore, PPE selection must reflect the actual work and electrical system.
Common Causes of Arc Flash
Several conditions can contribute to electrical arcing.
- Tools accidentally contacting live conductors.
- Incorrect or incomplete electrical isolation.
- Equipment failure or damaged insulation.
- Poor installation or deterioration over time.
- Dust, corrosion or other contamination.
- Accidental strikes on underground electrical cables.
These hazards reinforce the importance of inspection, maintenance and approved safe working procedures.

What Injuries Can an Arc Flash Cause?
The consequences of an arc flash depend on the incident energy, exposure duration and the worker’s position.
In severe cases, injuries can be life-changing or fatal.
Potential Arc Flash Injuries
- Thermal burns: Serious burns caused by intense heat or hot materials.
- Eye injuries: Damage caused by bright light, ultraviolet radiation or flying debris.
- Hearing damage: Injury associated with the sound and pressure effects of an electrical fault.
- Impact injuries: Harm caused by pressure waves, falls or flying objects.
- Molten metal injuries: Burns or wounds caused by hot particles.
- Secondary burns: Injuries from ignited clothing or other materials.
Arc-rated clothing primarily addresses specified thermal hazards. Other risks may require additional protective measures.
Consequently, employers must assess the complete work activity rather than relying on a garment’s arc rating alone.
How Can Employers Protect Workers from Arc Flash?
Employers must identify electrical hazards and put appropriate precautions in place.
This should begin before selecting PPE.
Three Key Steps for Arc Flash Risk Management
- Reduce exposure: Eliminate unnecessary contact with electrical hazards and use safe isolation wherever reasonably practicable.
- Establish safe working procedures: Assess electrical risks, introduce suitable controls and provide appropriate training.
- Select protective equipment: Provide PPE that matches the residual thermal hazards identified by the risk assessment.
Where appropriate, an arc flash assessment can help estimate potential incident energy and support PPE selection.
However, PPE remains the last line of defence. Protective clothing cannot replace electrical isolation, engineering controls or safe working methods.
IEC 61482-2:2018 – Arc Flash Protective Clothing Standard
IEC 61482-2:2018 specifies requirements for protective clothing used against the thermal hazards of an electric arc.
The standard addresses clothing performance and the assessment of materials and garments.
It is an important reference for electrical workers, employers and PPE specifiers.

How Is Arc Flash Clothing Tested?
The original article described two principal approaches to testing the thermal arc protection of clothing.
- Open Arc Test: Used to determine incident-energy-related arc ratings.
- Box Test: Used to assess clothing against specified directed arc test conditions.
These methods provide different forms of performance information.
Therefore, an open arc rating and a box test classification should not be treated as interchangeable.
Open Arc Testing – ATPV, EBT and ELIM Explained
The original article referenced BS EN IEC 61482-1-1:2019 for open arc testing.
This method assesses the response of clothing materials and protective garments to defined electrical arc exposure.
It provides ratings such as ATPV, EBT and ELIM.
What Is ATPV?
ATPV stands for Arc Thermal Performance Value.
It represents an incident energy level associated with a 50% probability of reaching the specified thermal burn injury criterion in the test.
ATPV is expressed in cal/cm².
For example, a garment with an ATPV of 8 cal/cm² has achieved that rating under the relevant test method.
However, the rating does not guarantee protection against every incident involving the same calculated energy.
What Is EBT?
EBT stands for Breakopen Threshold Energy.
It identifies an incident energy level associated with a 50% probability of the material breaking open under the test criteria.
Like ATPV, EBT is expressed in cal/cm².
The distinction is important because a material may break open before reaching the thermal transfer criterion used to determine ATPV.
What Is ELIM?
ELIM stands for Incident Energy Limit.
It is calculated from the test data using criteria that exclude recorded results reaching the specified thermal injury threshold or material breakopen within the relevant evaluation.
ELIM is also expressed in cal/cm².
However, an ELIM rating must not be interpreted as a guarantee of zero injury risk in an actual electrical incident.
ATPV vs EBT vs ELIM
| Rating | Meaning | What It Describes |
|---|---|---|
| ATPV | Arc Thermal Performance Value | Thermal energy transfer associated with the specified burn injury criterion. |
| EBT | Breakopen Threshold Energy | The energy level associated with the specified material breakopen criterion. |
| ELIM | Incident Energy Limit | An incident energy limit determined using the applicable test data criteria. |
These values help describe the tested thermal performance of protective clothing.
However, the correct PPE must be selected using the relevant risk assessment and product documentation.
Arc Flash Box Testing – APC 1 and APC 2
The second method discussed in the original article is the Box Test.
This assesses clothing using a directed electrical arc under specified conditions.
The original article referred to BS EN 61482-1-2:2014 and described two protection classes.
APC 1 – Arc Protection Class 1
The original article provided these test conditions:
- Test Current: 4kA.
- Test Voltage: 400V AC.
- Arc Duration: 500ms.
- Frequency: 50Hz or 60Hz.
These are controlled test conditions used to assess clothing performance.
APC 2 – Arc Protection Class 2
The original article described the following conditions:
- Test Current: 7kA.
- Test Voltage: 400V AC.
- Arc Duration: 500ms.
- Frequency: 50Hz or 60Hz.
APC 2 uses a higher test current than APC 1.
However, these classes are not equivalent to specific ATPV or ELIM values.
APC 1 vs APC 2 – Comparison
| Test Parameter | APC 1 | APC 2 |
|---|---|---|
| Test Current | 4kA | 7kA |
| Test Voltage | 400V AC | 400V AC |
| Arc Duration | 500ms | 500ms |
| Frequency | 50Hz or 60Hz | 50Hz or 60Hz |
The figures above reflect the original article’s test conditions. The permitted tolerances and current test requirements should be checked against the applicable standard.
Important: Neither APC 1 nor APC 2 indicates that a garment is safe for every electrical installation operating at 400V. The complete hazard assessment remains essential.
Learn more about IEC 61482-2 Arc Flash Protective Clothing Standards.
Arc Flash Fabrics – Treated vs Inherent Protection
The fabric used in protective clothing plays an important role in garment performance.
For example, some protective materials use chemical treatments to achieve specified flame-resistant characteristics.
Others use fibres with inherently flame-resistant properties.
What Are Treated Flame-Resistant Fabrics?
Treated fabrics receive a flame-resistant treatment during manufacturing.
The resulting performance depends on the material, treatment and garment care requirements.
For example, certain treatments may be affected by unsuitable washing or maintenance procedures.
However, not every treated fabric loses its protective performance after normal laundering.
Users should follow the garment manufacturer’s instructions and applicable certification requirements.
What Are Inherently Flame-Resistant Fabrics?
Inherent flame-resistant fabrics use fibres that possess flame-resistant characteristics as part of their material composition.
These properties are not dependent on a separately applied surface treatment.
However, the overall performance still depends on fabric construction, garment condition and proper care.
ProGARM VXS+ Fabrics
The original article introduced ProGARM’s VXS+ fabric technology.
ProGARM promoted this material as part of its inherent flame-resistant protective clothing offering.
The company’s emphasis was on combining protection, comfort and practical garment performance.

ProGARM 6458 Arc Flash Lineman Coverall
Arc Flash Clothing Layers – How Layering Works
Arc flash protective clothing may be worn as part of a layered garment system.
For example, a worker might wear an approved base layer beneath an arc-rated polo shirt or sweatshirt.
However, the protective performance of a combination depends on the specific garments being worn together.
Can Layering Increase Arc Flash Protection?
Suitable layers may provide greater thermal protection than individual garments.
The original article described this using the phrase “1 + 1 = 3”.
This illustrates the potential benefit of a tested layered system rather than a literal calculation of arc ratings.
However, workers must not simply add the arc ratings of individual garments together.
The complete combination should have appropriate evidence of its protective performance.
Example – ProGARM Polo Shirt and Sweatshirt
The original article featured a ProGARM polo shirt combined with a ProGARM sweatshirt.
This demonstrated how different protective garments could form part of a layered clothing arrangement.

ProGARM Arc Flash Clothing | Polo Shirts and Sweatshirts
Why Base Layers Matter
Incorrect underclothing can affect the protection provided by outer garments.
For example, some unsuitable synthetic materials may melt when exposed to heat.
Therefore, base layers must be compatible with the protective clothing system and relevant safety requirements.
The original ProGARM article also referenced protective garments ranging from underwear and thermal base layers to waterproof clothing.
However, current ratings and approved clothing combinations must be confirmed with the manufacturer.
What Makes a Good Arc Flash Protective Garment?
Protective fabric is important, but garment construction also influences performance.
For example, seams, fasteners, closures and pockets must be suitable for the garment’s intended use.
Comfort and fit also matter because workers may need to wear protective clothing for extended periods.
Arc Flash Clothing Design Features
The original ProGARM article identified several garment features.
- Triple-stitched seams for suitable garment construction.
- Inherent flame-resistant fabrics in selected products.
- Flame-resistant sewing threads where specified.
- ThermSAFE components designed for protective clothing applications.
- Adjustable wrist tabs and neck fastenings to help maintain garment coverage.
- Reflective tape for suitable high-visibility garments.
- SafetyICON markings to communicate product information.
- Internal labels and batch identification for traceability.
- Stretch panels for improved movement in applicable designs.
- Napoleon-style pockets for suitable applications involving harnesses.
- Different garment sizes to accommodate workers.
- Women’s garment options within the wider protective clothing range.
However, not every ProGARM garment includes all these features.
Customers should confirm the construction and certification of the exact product required.
Why Fit and Comfort Matter
PPE must provide appropriate coverage without unnecessarily restricting the worker.
For example, clothing that is excessively tight may restrict movement or compromise its intended fit.
Meanwhile, poor comfort can make protective workwear difficult to use throughout a working day.
Therefore, employers should consider garment sizing, mobility and the manufacturer’s wearing instructions.

ProGARM’s Approach to Arc Flash Protection
The original article highlighted ProGARM’s commitment to electrical safety education and protective clothing development.
Its stated priorities included:
- Educating workers and raising awareness of arc flash risks.
- Developing protective clothing and improving garment performance.
- Supporting customers with suitable product information.
- Maintaining a strong focus on worker safety.
These objectives reflect the manufacturer’s message at the time of the original 2020 publication.
However, effective protection still depends on suitable risk assessment, garment selection and correct use.
ProGARM Arc Flash Clothing and PPE
Thorne & Derrick supply ProGARM arc flash protective clothing for suitable electrical and industrial applications.
The range includes polo shirts, trousers, coveralls, sweatshirts, jackets, gloves and helmets.
However, the correct garment must match the protection criteria identified by the relevant electrical risk assessment.

Polo Shirts | Jackets | Coveralls | Trousers | Gloves | Sweatshirts | Helmets
Featured ProGARM Arc Flash Clothing Products
The following products appeared in the original article.
We’ve retained the model references, images and links. Current garment ratings and availability should be confirmed before ordering.
|
|
|
|
|
|
|
|
|
|
Download Your Guide to Arc Flash Protection
Understanding arc flash hazards and PPE ratings is important when planning safe electrical work.
Our guide provides further information about protective clothing and electrical safety.
DOWNLOAD YOUR GUIDE TO ARC FLASH
Further Reading – Arc Flash Safety
Explore our related technical articles on arc flash hazards, electrical safety and protective clothing.
- Arc Flash Clothing for Highways, Street Lighting and Utility Contractors.
- Arc Flash Dexterity Gloves from ProGARM.
- ProGARM Arc Flash Coveralls.
- Arc Flash Legislation and Regulations.
- Arc Flash PPE – Seven Top Considerations.
Thorne & Derrick – Arc Flash Clothing and Electrical PPE
Thorne & Derrick International supply arc flash protective clothing and specialist electrical equipment for LV, MV and HV applications.
Our customers include utilities, electrical contractors, cable jointers and industrial maintenance teams.
We also supply equipment used in cable installations, substations and electrical infrastructure projects.
Electrical Installation and Safety Equipment
Our wider product range includes:
- Arc Flash Clothing and Protection.
- Electrical Safety Equipment.
- MV and HV Cable Joints and Terminations.
- Cable Duct Seals.
- Cable Cleats and Supports.
- Cable Glands.
- Cable Jointing Tools.
- Cable Pulling Equipment.
Enquire About Arc Flash PPE
Need protective clothing for electrical installation or maintenance work?
Contact Thorne & Derrick to discuss suitable garment options, product specifications and availability.
For accurate product selection, provide the protection requirements identified by your electrical risk assessment.