11kV 24kV Connectors – Tee Connector MV HV Interface C – Prysmian Elascon

Prysmian Tee Connectors - 11kV 33kV Medium & High Cable Connectors (MV HV)

11kV 24kV Connectors – Tee Connector MV HV Interface C – Prysmian Elascon

Prysmian Separable Tee Connector MV HV Interface C are suitable for the connection of polymeric MV cables to transformers and switchgear units in outdoor or indoor installations with a continuous current rating of 630A.

Suitable for single polymeric insulation (PE, XPLE, EPR) with aluminium or copper conductors with sizes between 35 to 300mm² – insulation voltage up to 24kV and operated when de-energized.

The separable tee connector meets CENELEC HD 629.1 S2 ­ IEC 60502-4 — NF C 33-051 — NF C 33-001, Interface C meets CENELEC EN 50180 and EN 50181 and the metal conductor contact is compliant with IEC 61238-1 class A and HN 68-S-91.

Tee Connector MV HV Interface C 11kV 24kV

Tee Connector MV HV Interface C 11kV 24kV

Tee Connector MV HV Interface C – Features & Benefits

  • No need for special tools – no heating, taping or filling
  • Vertical, angled or inverted position
  • No minimum distance between phases
  • Energising may take place immediately after the connector is plugged into its bushings and dead end plug
  • Unplugged connector must not be energised
  • Supplied as a kit of single connectors containing all the necessary components
  • Shipping weight and volume (approx) of kit: 6kg /0.013m³

Separable Tee Connector (Interface C 630A) – Diagram

Separable Tee Connector (Interface C 630A)

1. Multi-section mechanical conductor contact Al/Cu 

Cover the section from 35 mm² to 300 mm². Copper or aluminium core. No need for special tools.

2. M16 Clamping screw

Steel silver-plated component threaded at both ends for attachment of the mating items: bushing, insulating plug, accessories. A uniform contact pressure is maintained for any combination.

3. Semi-conducting inner screen

Insert of semi-conducting EPDM enclosing the mechanical conductor contact connections so that ionization of the air remaining trapped inside is prevented.

4. Insulating body

Moulded from insulating EPDM, for integral reconstitution of insulation. It maintains a uniform contact pressure on the cable insulation and on the bushing interface, providing an excellent moisture seal.

5. Insulating plug

Epoxy component with a threaded metal insert for attachment to the clamping screw.

6. Cap

Moulded semi-conducting EPDM. Protects and earths the test point during normal use.

7. Moulded high permittivity reducer

Adapt the connector body to the different cables insulations diameters. Ensures watertight protection of the earthing device and enables the cable screen test.

Tee Connector MV HV Interface C - Overall Dimensions Installed On Bushing

Tee Connector MV HV Interface C – Overall Dimensions Installed On Bushing

 

Voltage Dia Over Insulation mm Conductor Size mm² Prysmian Elascon Kit Reference
Min Max
12kV 13 22.3 25 120 MCEAU/CE-630-C-12-rA-25/120
16.1 26.3 95 240 MCEAU/CE-630-C-12-rB-95/240
22.7 33.0 185 300 MCEAU/CE-630-C-12-rD-185/300
17kV 13 22.3 25 70 MCEAU/CE-630-C-17-rA-25/70
16.1 26.3 35 120 MCEAU/CE-630-C-17-rB-35/120
20.2 30.8 95 240 MCEAU/CE-630-C-17-rC-95/240
25.6 35.3 185 300 MCEAU/CE-630-C-17-rE-185/300
24kV 16.1 26.3 25 150 MCEAU/CE-630-C-24-rB-25/150
16.1 26.3 70 185 MCEAU/CE-630-C-24-rB-70/185
20.2 30.8 95 240 MCEAU/CE-630-C-24-rC-95/240
22.7 33.0 95 240 MCEAU/CE-630-C-24-rD-95/240
25.6 35.3 185 300 MCEAU/CE-630-C-24-rE-185/300
36kV 20.2 30.8 25 95 MCEAU/CE-630-C-36-rC-25/95
22.7 33.1 35 120 MCEAU/CE-630-C-36-rD-35/120
25.6 35.3 70 240 MCEAU/CE-630-C-36-rE-70/240
Prysmian Separable Connectors

T&D distribute the full Prysmian Separable Connector range including Tee Connectors, Straight Connectors & Elbow Connectors

11kV Transformers

Read Our Blog: The Next Generation Of 11kV Transformers For Medium & High Voltage Networks

Data Sheets