3M 92-NBA2

Contact us for 3M Cable Joints | Large Stocks | Competitive Prices | 3M Distributors
Resin Cable Joint
3M 92-NBA2 Scotchcast resin cable joints are used to straight joint, repair or splice single core and multi-core unarmoured cables with XLPE or EPR insulation and core conductors 6sqmm-16sqmm.
View our complete range of cable joints utilising resin cast, Cold Shrink and heat shrink type technology for the connection, repair and jointing of LV cables.
 See armoured cable joints for further information about cable joint kits suitable for SWA (steel wire armoured) power cables.
3M 92-NBA2 joint kit sELECTION
- Single Core Unarmoured Cable – N/A
- 2 Core Unarmoured Cable – N/A
- 3 Core Unarmoured Cable – N/A
- 4 Core Unarmoured Cable – 6-16sqm
- Cable Diameter – 12-25mm
- Cable Voltage 600/1000V (up to 3.3kV)
- 3M 92-NBA2 utilises Scotchcast 40G resin
- Hazardous Area Cable Joints also available
3M Scotchcast RoHS Compliant General Purpose In Line Joint Polyurethane Resin kit Series 91-NBA
Jointing Airfield Lighting Cables
3M 92-NBA2 resin cable joints are suitable for jointing and cable splicing XLPE, PVC and PE airfield lighting cables including cable duct, trench or direct burial cable installations, including standard single-core screened or non-screened cable.
Cable joints for 5kV primary circuits located between constant current regulators (CCRs) and transformers on the runways are also available.

Airfield lighting heat shrink joints are low voltage cable joint kits that are fully approved by DOE and PSA for use on civilian and military airfields.
3M 92-NBA2 SCOTCHCAST RESIN CABLE JOINTS (40G RESIN)
3M Cable Joint Kit Ref | Resin Cable Joint Conductor Cross Sectional Area (mm²) | Max Cable OD (mm) | |||
Single Core | 2 Core | 3 Core | 4 Core | ||
3M 92-NBA2 | N/A | N/A | N/A | 6-16sqmm | 12-25 |
3M 92-NBA 2 Scotchcast Low Voltage Resin Joint Shell Dimensions
Dimensions for 3M 92-NBA-2 cable joint with joint shell measurements:
Kit Size 3M 92-NBA 2 | 3M Scotchcast Resin Cable Joint Body Dimensions | Min-Max Accepted Cable Diameter (mm) |
|||||||
Li (mm) | L (mm) | Ø ID (mm) | Hs (mm) | H (mm) | B (mm) | D (mm) | E (mm) | ||
2 | 192 | 230 | 38 | 71 | 48 | 120 | 48 | 96 | 12-25 |
Image Dimensions | ![]() |
![]() |
![]() |
![]() |
âž¡ More: Cable Joints Unarmoured Cables (Hazardous Area).
3M Cable Joints | Zero Halogen | LSF | Fire Resistant | Flame Retardant | Hydrocarbon Resistant – Scotchcast Resin