3M LVI-3/2-IC

Resin Cable Joint

Hazardous Areas – Control & Instrumentation Cables

3M LVI-3/2-IC Scotchcast hazardous area control and instrumentation cable joints are used to straight joint, splice or connect multi-core or multi-pair armoured cables with core conductors 0.9sqmm-2.5sqmm – suitable for jointing marine, offshore and shipboard specification cables including NEK606, BS6883 and BS7917 specifications.

Where no “hot-working” is permitted in hazardous areas and potentially explosive atmospheres but hydrocarbon resistant resin cable joints are not required, we can recommend Cold Shrink type cable joints for cable connections, joints or repairs.

LVI-3/2-IC is an inline or straight cable joint kit with 1402FR resin for hazardous area locations manufactured by 3M Electrical  – the Scotchcast cable joint is designed for use with onshore and offshore control and instrumentation cables with flame retardant, hydrocarbon resistant and halogen free specification.

3M LVI-3/2-IC joint kit sELECTION
  • PE Cable Joint – Insulated Armoured Multi-Pair Cables – 1-2 Pairs, 0.9sqmm
  • PVC Cable Joint – Insulated Armoured Multi-Core Cables – 2-6 Cores, 1.5-2.5sqmm
  • Cable Diameter – 14-30mm
  • Cable Voltage 600/1000V (up to 3.3kV)
  • 3M LVI-3/2-IC utilises Scotchcast 1402FR resin
  • Hazardous Area Zone 1 & Zone 2 Areas
  • Hazardous Area Power Cable Joints also available for BFOU & RFOU Cables
Marine & Offshore Power Cables BFOU Mud Resistant NEK606

Marine & Offshore Power Cables BFOU Mud Resistant NEK606

Marine & Offshore Power Cables RFOU Mud Resistant NEK606

Marine & Offshore Power Cables RFOU Mud Resistant NEK606

Cable Joints - ATEX Zone 1 Zone 2 Hazardous Areas

3M 1402FR Hydro Carbon Resistant Cable Joints For Hazardous Areas

ATEX Cable Joints For Hazardous Areas

Zone 1 & 2 Hazardous Areas

3M LVI-3/2-IC INSTRUMENTATION CABLE JOINT

SELECTION FOR PE INSULATED ARMOURED MULTI-PAIR CABLES, 0.9MM2

3M LV-3-IC Joint Kit Reference Number of pairs Cable diameter (mm)
LVI-3/2-IC 1-2 pairs 14-30

 

3M LVI-3/2-IC CONTROL CABLE JOINT

SELECTION FOR PVC INSULATED ARMOURED MULTI-CORE CABLES, 1.5 – 2.5MM²

3M LV-3-IC Joint Kit Reference Number of cores Cable diameter (mm)
LVI-3/2-IC 2-6 cores 14-30

 

3M LVI-3/2-IC Hazardous Area Cable Joints Dimensions
3M LVI-3/2-IC Kit Size  3M LVI-3/x-IC Kit Part Number  Dimensions A (mm) Dimensions B (mm) Dimensions C (mm) Dimensions D (mm) Image Dimensions
Size 2 LVI-3/2-IC 14 32 49 276 3M LVI-3/x Hazardous Area Cable Joints - Dimensions