Network Rail Approved PADS Cable Joints | Multi Pair Pilot Joints

View Sub Products

3M LVI-0/x-NRUK Scotchcast Inline Resin Cable Joints (470W Resin) – Armoured Cables

3M LVI-0/x-NRUK Scotchcast Inline Resin Cable Joints (470W Resin)

CABLE JOINTS FOR LV Pilot CABLES

Network Rail Approved Pilot Cable Joints

3M LVI-0/x Scotchcast resin cable joint kits are designed to be used for multi-pair armoured pilot cables – Network Rail Approved PADS cable joints for connection, repair and jointing of 20 pair and 30 pair pilot cables.

The cable joints are also approved by Network Rail to connect and joint new paired cables to quaded cables.

Cable joints incorporate electrical insulation and mechanical protection using 3M Scotchcast resin with 3M Scotchlok connectors – rail cable joints can be used for indoor/outdoor, underground and submerged applications with high humidity or weather exposure.

3M Scotchcast hazardous area cable joints are also available for jointing power, pilot and instrumentation cables in Zone 1 and Zone 2 potentially explosive atmospheres.

3M LVI-0/x-NRUK Scotchcast Inline Resin Cable Joints (470W Resin)

Features

  • Scotchcast 470W resin in transparent two chamber bags for mixing
  • Two part translucent mould body with closing system for quick and easy handling
  • Closure cap to prevent any pollution
3M LVI-0 x-NRUK Scotchcast Inline Resin Cable Joints (470W Resin)

3M LVI-0 x-NRUK Scotchcast Inline Resin Cable Joints (470W Resin)

3MLVI-0/x-NRUK KIT CONTENTS

  • Mould body with closure cap
  • Scotchcast 470W resin bag
  • Scotch 23 Tape
  • Earth and arrmour connection components
  • Disposable gloves (EN394)
  • Detailed jointing installation instruction

3m Cable Joint description – LVI-0 x-NRUK

3M Scotchcast LVI-0 x-NRUK resin inline joint kit are supplied with a two part translucent cable joint mould body for simple and easy handling by the jointer.

3M Scotchcast Resin Cable Joints

Scotchcast Joints – Safe & Reliable Resins

Distances inside the body can be checked easily.

All necessary dimensions, like application range, cable preparation are given in the detailed jointing instruction.

The mould body can be adapted to the required cable diameter by cutting the marked areas of the joint mould.

Scotchcast 470W resin is delivered in a two chamber bag and aluminium guard bag for protection against humidity.

The re-openable seam and integrated spout with a membrane provides a 3M Closed, Mixing and Pouring (pictured) cable jointing system.

After the seam of the two chamber bag is opened, the Scotchcast resin components can be mixed.

To pour the resin into the mould body, the bag has to be cut open.

To provide resin handling without any skin contact, disposable gloves meeting EN394 are provided with the cable joint kit. The 3M Closed Mixing and Pouring System provides resin handling without any skin contact – for protection against pollution, a closure cap is applied onto the dome. After curing, the remaining joint resin in the bag can be disposed as household waste.

3M Cable Joints

3M Scotchcast Joints – resin cable joints for power, control and instrumentation cables in industrial and hazardous area Zone 1 and Zone 2.

3M LVI-0/x-NRUK Scotchcast Cable Joint Selection

3M Cable Joint Part Number Network Rail PADS
Catalogue Ref
Pilot Cable Range
0.9/1smm
(Pairs)
Maximum
Cable OD
(mm)
Recommended
Scotchlok
Connector
3M LVI-0/3-NRUK Cable Joint  PADS 054/212926 20 Pair 34 3M Scotchlok UR2
3M LVI-0/4-NRUK Cable Joint PADS 054/212927 30 Pair 45 3M Scotchlok UR2

 

3M LVI-0/x-NRUK Scotchcast resin cable joints are tested according to EN50393.

Type of Test According To EN50393 Table 3 / I / A1 Results
AC Voltage Withstand Test In Air 4kV AC / 1 min Passed
Insulation Resistance Test In Air 1kV DC > 10,000MΩ
Heat Cycle In Air 63 Cycles: 5h/3h Passed
Heat Cycle In Water 63 Cycles: 5h/3h Passed
AC Voltage Withstand Test In Water 4kV AC / 1 min  Passed
Insulation Resistance Test In Water 1kV DC > 10,000MΩ
3M Scotchcast 470W Resin

Scotchcast 470W resin is in compliance with EU regulation 1907/2007/EC (REACH) and has a shelf life of at least 36 months when stored between 15°C and 35°C with a humidity level < 75 % in the originally sealed bag.

The expiration date of each product appears on the product label. Storage beyond the date specified on the label does not necessarily mean that the product is no longer usable. In this case however, it is the responsibility of the user to determine applicability of the resin.

Cable Joints 3M - 3M LVI-1/x

T&D Stock & Distribute the complete range of 3M Cable Joints & Cable Terminations using resin and cold shrink for LV, MV & HV cables.