Ellis COL39-47 Colossus Trefoil Cable Cleats

Ellis Colossus COL39-47 Trefoil Cable Cleats

Ellis Cable Cleats

Trefoil Cable Cleats

Cable Cleat Maximum Short Circuit Test Level 104kA

Cleat Spacing 7800mm with Intermediate Cable Straps Every 1300mm

Ellis COL39-47 Colossus Cable Cleats are manufactured by Ellis Patents from heavy composite polymeric materials with integral stainless steel cleat closure – COL39-47 also includes a uniquely designed LSF LSOH (Low Smoke & Fume | Low Smoke Zero Halogen) polymer frame and able to withstand moderate levels of short-circuit according to IEC61914 calculations.

Ellis Patents COL39-47 cable cleats are suitable for securing single core power cables between 39-47mm in trefoil formation with an overall cable diameter onto cable containment including tray and ladder work in medium/high voltage power substations.

Colossus Cable Cleats form part of the Ellis Patents range of trefoil cable cleats.

ELLIS CABLE CLEAT COL39-47

TECHNICAL SPECIFICATION

  • Cable Cleat Diameter Min 39mm
  • Cable Cleat Diameter Max 47mm
Ellis Colossus COL39-47 Trefoil Cable Cleats

Ellis Colossus COL39-47 Trefoil Cable Cleats 39-47mm

ELLIS PATENTS COL39-47 CLEAT DIMENSIONS

  • Width 157mm
  • Height 122mm
  • Depth 60mm
  • P 25mm
  • 2 x M10 + M12
  • Weight 734g

Trefoil Cable Cleat Selection Table

Specification details for Ellis Patents Colossus COL39-47 cable cleat for trefoil cable applications:

Colossus Trefoil Cable Cleat Part Number Cable Range Dimensions Weight (g)
Min Dia (mm) Max Dia (mm) W (mm) H (mm) D (mm) P (mm) Ø Fixing Holes
COL39-47 39 47 157 122 60 25 2 x M10 + M12 734

 

Ellis COL39-47 Colossus Trefoil Cable Cleats

Ellis COL39-47 Colossus Trefoil Cable Cleats

COLOssus Cable Cleats – Installation Instructions

Installation instructions for trefoil cable cleats using Colossus type cleats manufactured by Ellis Patents:

Remove the closing flange nuts Fix the bottom half of the cable cleat Lay the cables in place Fit the top half of the cleat over the cables Do not over tighten the cleat
1.Remove the closing flange nuts and set screws. 2. Fix the bottom half of the cleat to the support structure using M10 or M12 fixings as appropriate. 3. Lay the LV MV HV cables in place. 4. Fit the top half of the cleat over the cables. Secure with the M12 setscrews and flange nuts (19mm spanner/socket for
setscrews, 16mm spanner/socket for flange nuts).
5. Important. Do not over tighten the cleat. The liner should be in contact with the cable but does not need to be so tight that the cable bulges at either side of the cleat liner.

 