Low Voltage LV Industrial Cable Joints – Prysmian FRZHMPJ

View Sub Products

Low Voltage LV Industrial Cable Joints – Prysmian FRZHMPJ

Low Voltage LV Industrial Cable Joints – Prysmian FRZHMPJ

Prysmian FRZHMPJ industrial straight cable joints are used for fire resistant LV cables with copper & aluminium conductors ranging from 4sqmm to 400sqmm and have Rigid glass reinforced phenolic joint shells which are both fire retardant and LS0H.

FRZHMPJ low voltage cable joints include low hazard isocynate free JEM resin which has extremely low viscosity and enhanced adhesion and are designed to allow use with compression connectors.

T&D can offer the full range of Prysmian cable joints for low voltage industrial cable jointing applications.

Prysmian FRZHMPJ Cable Joints

Technical Data

  • Low Voltage Straight Joints for 600/1000 Volt polymeric insulated copper conductors.
  • Tested and approved to BS EN 50393 & ENA ER C81
  • Fire tests on complete joints to BS 6387 categories C, W and Z
  • Includes constant force spring Armour Bonds.

Prysmian JEM Resin Features & Benefits

  • Easier resin mixing by the cable jointer in “Twin Pack” totally enclosed mixing in a clear laminate sachet.
  • Extremely low mix viscosity allows void free cable joint filling.
  • JEM Resin is insensitive to moisture and will cure under water.
  • Enhanced adhesion to XLPE, MDPE, PVC & lead covered cables.
  • High flash point, non-flammable liquid – no special storage or transport requirements.
  • Not classified as irritating to the skin or eyes.
  • Does not cause skin sensitisation.

Cable Joint Component Characteristics

Prysmian’s Fire Resistant Joints are tested to BS6387 categories C, W & Z  Performance Symbol FR Joint
Resistance to Fire – The joint is tested by exposure to gas burner flames while passing a current at its rated voltage 650°C for 3 hours
750°C for 3 hours
950°C for 3 hours
A
B
C
PASS
PASS
PASS
Resistance to Fire with Water Spray – The joint is exposed to flames at 650°C for 15 minutes whilst passing a current of 250MA at a rated voltage and then the spray is turned on to give exposure to both fire and water for a further 15 minutes 650°C W Pass
Resistance to Fire with Mechanical Shock – The joint is mounted on a back panel and exposed to flames whilst the bedding panel is struck with a solid steel bar every 30 seconds for 15 minutes 950°C Z Pass

CABLE JOINTS Dimensions

Prysmian Cable Joint Reference Dimensions
A B C
FRZHMPJ2 300mm 85mm 70mm
FRZHMPJ3 405mm 100mm 80mm
FRZHMPJ4 430mm 110mm 90mm
FRZHMPJ5 560mm 160mm 130mm
FRZHMPJ6 740mm 180mm 145mm
FRZHMPJ7 870mm 190mm 145mm
FRZHMPJ8 1015mm 205mm 180mm

Note: Prysmian FRZHMPJ joints are provided without connectors, compression connectors can be provided separately.

➡ Prysmian Cable LV MV HV Accessories | Cable Glands |  Cable Cleats | 11kV Terminations Heat Shrink

Prysmian FRZHMPJ LV Cable Joints - Dimensions

Prysmian FRZHMPJ LV Cable Joints – Dimensions

LOW VOLTAGE CABLE JOINTS Selection Table
Nominal Area of Conductor Two Core Ref Three Core Ref Four Core Ref Connector Reference
4sqmm FRZHMPJ2 FRZHMPJ2 FRZHMPJ2 BE-YS
6sqmm FRZHMPJ2 FRZHMPJ2 FRZHMPJ2 BT6CS
10sqmm FRZHMPJ2 FRZHMPJ2 FRZHMPJ2 BT10CS
16sqmm FRZHMPJ2 FRZHMPJ2 FRZHMPJ3 BT16CS
25sqmm FRZHMPJ2 FRZHMPJ3 FRZHMPJ4 BT25CS
35sqmm FRZHMPJ3 FRZHMPJ4 FRZHMPJ4 BT35CS
50sqmm FRZHMPJ3 FRZHMPJ5 FRZHMPJ5 BT50CS
70sqmm FRZHMPJ4 FRZHMPJ5 FRZHMPJ5 BT70CS
95sqmm FRZHMPJ4 FRZHMPJ5 FRZHMPJ5 BT95CS
120sqmm FRZHMPJ5 FRZHMPJ6 FRZHMPJ6 BT120CS
150sqmm FRZHMPJ5 FRZHMPJ6 FRZHMPJ6 BT150CS
185sqmm FRZHMPJ5 FRZHMPJ6 FRZHMPJ6 BT185CS
240sqmm FRZHMPJ6 FRZHMPJ7 FRZHMPJ7 BT240CS
300sqmm FRZHMPJ6 FRZHMPJ7 FRZHMPJ7 BT300CS
400sqmm* N/A N/A FRZHMPJ8 BT400CS

*Joint does not accommodate crossed core (phase to phase jointing)

➡ For jointing all types of XLPE, EPR and PILC power, control and instrumentation cables in straight, branch or transition arrangement including zero halogen, fire resistant and hazardous areas see Resin Cable Joints