Nexans AIN are single core cold shrink slip-on cable terminations for use indoor and specified to terminate and connect medium/high voltage cables in the following voltage classes:

  • 6/10 (12) kV
  • 6.35/11 (12) kV
  • 8.7/15 (17.5) kV
  • 12/20 (24) kV
  • 12.7/22 (24) kV
  • 18/30 (36) kV
  • 20.8/36 (42) kV

Slip-on terminations are cold applied terminations require no “hot-working” for safe use in potentially explosive atmospheres and hazardous area locations – the cable terminations are designed for use with polymeric insulated cables (XLPE & EPR). To enable the fault repair, extension, splicing and jointing of existing LV MV HV power cables up to 33kV we also stock a complete range of cold shrink joints.

Slip On Indoor Cable Terminations 11kV 33kV 42kV Euromold AIN - Design

Slip On Indoor Cable Terminations 11kV 33kV 42kV Euromold AIN – Design

Indoor slip-on cable termination kit list comprising:

  1. Cable lug (not included in the standard kit) – crimp lugs or shearbolt lugs are suitable
  2. High flexibility silicone rubber housing, allowing larger tolerances on cable insulation diameters, with integrated conductive rubber insert, providing stress relief
  3. Earthing lug (not included in the standard kit)

Nexans AIN COLD SHRINK TERMINATION SPECIFICATION

The following tables enable the selection of cable terminations using Cold Shrinkable technology manufactured by Nexans:

Euromold Termination
Slip On Cold Shrink 
Voltage
Um
(kV)
Conductor Sizes (sqmm)
min max
Nexans AIN 10 12kV 25sqmm 1200sqmm
Nexans AIN 20 24kV 35sqmm 1200sqmm
Nexans AIN 30 36kV 50sqmm 1000sqmm
Nexans AIN 36 42kV 150sqmm 1000sqmm

 

EUROMOLD AIN selection table

For Indoor MV HV Cable Terminations

Select the Euromold part number corresponding to both the system voltage and the cable insulation diameter in mm – the complete kit comprises of 3 termination housings, installation instructions, special lubricant, wiper, adhesive tape and field control mastic.

Voltage
Um
(kV)
Conductor
Sizes
(sqmm)
Diameter Over
Core Insulation
(mm)
Number Of Sheds L
(mm)
Dia. D (mm) Nexans AIN Ordering
Part Number
min max min max
12kV 25sqmm 95sqmm 12.7 21.0 2 150 37 3 x AIN 10-1
120sqmm 240sqmm 19.0 28.5 2 150 43 3 x AIN 10-2
300sqmm 500sqmm 27.0 37.0 2 150 60 3 x AIN 10-3
630sqmm 800sqmm 34.0 46.0 3 225 68 3 x AIN 36-4
1000sqmm 39.0 50.0 7 405 98 3 x AIN 36-5
1200sqmm 46.0 58.0 7 405 98 3 x AIN 36-6
24kV 35sqmm 70sqmm 18.0 23.5 3 225 47 3 x AIN 20-1
95sqmm 240sqmm 22.5 33.0 3 225 56 3 x AIN 20-2
300sqmm 500sqmm 31.0 41.0 3 225 68 3 x AIN 20-3
400sqmm 630sqmm 34.0 46.0 3 225 68 3 x AIN 20-4
630sqmm 800sqmm 39.0 50.0 7 405 98 3 x AIN 36-5
1000sqmm 1200sqmm 46.0 58.0 7 405 98 3 x AIN 36-6
36kV 50sqmm 70sqmm 23.5 29.0 6 300 74 3 x AIN 30-1
95sqmm 240sqmm 27.0 38.0 6 300 74 3 x AIN 30-2
240sqmm 400sqmm 32.0 43.0 6 300 81 3 x AIN 30-3
400sqmm 630sqmm 39.0 50.0 7 405 98 3 x AIN 36-5
630sqmm 1000sqmm 46.0 58.0 7 405 98 3 x AIN 36-6
42kV 150sqmm 300sqmm 31.5 41.0 7 405 98 3 x AIN 36-4
400sqmm 630sqmm 39.0 50.0 7 405 98 3 x AIN 36-5
630sqmm 1000sqmm 46.0 58.0 7 405 98 3 x AIN 36-6

 

Nexans

Thorne & Derrick distribute the complete range of medium/high voltage electrical equipment manufactured by Nexans – this includes Euromold bushings for use with oil fluid or gas insulated switchgear or transformers and associated screened separable connectors according to both IEC (Euromold) and IEEE (Elastimold) for the termination, connect+disconnect of MV-HV cables onto power distribution systems. To protect power systems against high voltage surges resulting from lightning or switching a complete range of surge arresters are available to be used with Euromold connectors in 11kV/12kV, 24kV and 33kV/36kV voltage classes.

Nexans Joints Connectors Terminations

Key Product Categories: Duct Seals | Cable Cleats | Cable Glands | Electrical Safety | Arc Flash Protection | Cable Jointing Tools | Cable Pulling | Earthing | Feeder Pillars | Cable Joints LV | Joints & Terminations MV HV 

 ➡ Read: Thorne & Derrick Announce Distribution Agreement & Contract With Nexans 

Thorne & Derrick International

 

Further Reading