Nexans OTK Cold Shrink Termination | XLPE Outdoor Single Core 12kV 24kV MV Cables

Published 05 Dec 2018

Cold Shrink Indoor Cable Terminations 11kV 24kV Euromold OTK

Cable Termination | Cold Shrink | Single Core | 11kV 24kV

Cable Terminations

Nexans OTK are single core cold shrink cable terminations for use indoor and specified to terminate and connect medium/high voltage cables in the following voltage classes:

  • 6/10 (12) kV
  • 6.35/11 (12) kV
  • 8.7/15 (17.5) kV
  • 12/20 (24) kV
  • 12.7/22 (24) kV

Cold Shrinkable terminations require no “hot-working” for safe use in potentially explosive atmospheres and hazardous area locations – the cable terminations are designed for use with polymeric insulated cables (XLPE & EPR). To enable the fault repair, extension, splicing and jointing of existing LV MV HV power cables up to 33kV we also stock a complete range of cold shrink joints.

Cold Shrink Outdoor Cable Terminations 11kV 24kV Euromold OTK - Design

Cold Shrink Outdoor Cable Terminations 11kV 24kV Euromold OTK – Design

Outdoor cold shrink cable termination comprising:

  1. Cable lug (not included in the standard kit) – both crimp cable lugs and shearbolt lugs are suitable
  2. Water sealing mastic
  3. Sheds which be installed upwards or down
  4. Silicone tube with sheds
  5. Silicone cold shrink tube
  6. Stress control mastic
  7. Conductive EPDM ring

Nexans OTK COLD SHRINK TERMINATION SPECIFICATION

The following tables enable the selection of cable terminations using Cold Shrinkable technology manufactured by Nexans:

Nexans Cold Shrink Cable Terminations Voltage
Um
(kV)
Creepage
Distance
A-B
(mm)
Strike
Distance L
(mm)
Number
Of Sheds
Fig.
No.
Diameter Over
Core Insulation
(mm)
Conductor Sizes (sqmm)
min max min max
OTK 212 11kV 12kV 420 300mm 3 1 14 33 50sqmm 400sqmm
OTK 312 11kV 12kV 890 650mm 6 2 30 50 400sqmm 1000sqmm
OTK 224 20kV 24kV 600 400mm 5 3 14 33 25sqmm 240sqmm
OTK 324 20kV 24kV 890 650mm 6 4 30 50 300sqmm 800sqmm

Nexans OTK selection table

For outdoor MV HV Cable Terminations

Select the Nexans part number corresponding to both the system voltage and the cable insulation diameter in mm.

Kit Contents For Euromold OTK Terminations

 

Euromold OTK Cold Shrink Cable Terminations Voltage
Um
(kV)
Diameter Over
Core Insulation
(mm)
Conductor Sizes (sqmm)
min max min max
3 x OTK 212 11kV 12kV 14 33 50sqmm 400sqmm
3 x OITK 312 11kV 12kV 30 50 400sqmm 1000sqmm
3 x OTK 224 11kV 24kV 14 33 25sqmm 240sqmm
3 x OTK 324 11kV 24kV 30 50 300sqmm 800sqmm

 

Euromold ITK - Cable Lugs

All commercialised European standard cable lugs can be used. Cable lugs should be within the dimensions specified (not applicable for Nexans OTK 312 and OTK 324).

Nexans

Thorne & Derrick distribute the complete range of medium/high voltage electrical equipment manufactured by Nexans – this includes Euromold bushings for use with oil fluid or gas insulated switchgear or transformers and associated screened separable connectors according to both IEC (Euromold) and IEEE (Elastimold) for the termination, connect+disconnect of MV-HV cables onto power distribution systems. To protect power systems against high voltage surges resulting from lightning or switching a complete range of surge arresters are available to be used with Euromold connectors in 11kV/12kV, 24kV and 33kV/36kV voltage classes.

Nexans Joints Connectors Terminations

Key Product Categories: Duct Seals | Cable Cleats | Cable Glands | Electrical Safety | Arc Flash Protection | Cable Jointing Tools | Cable Pulling | Earthing | Feeder Pillars | Cable Joints LV | Joints & Terminations MV HV 

 ➡ Read: Thorne & Derrick Announce Distribution Agreement & Contract With Nexans 

Thorne & Derrick International

 

Further Reading