HV Cable Termination 17.5kV Heat Shrink Kits 1 Core 25-70sqmm SPS 1TIS-17.5X-A

Cable Termination Cable Joints - Heat Shrink MV HV

17.5kV cable termination kits using heat shrink technology are suitable for terminating medium/high voltage (MV-HV) single core polymeric cables (XLPE EPR)  – this includes cables with copper wire/tape screen and armoured (wire armoured/braided) or unarmoured cable for indoor termination of 17.5kV cables, outdoor version also available.

SPS 1TIS-17.5X-A cable termination kit suits 15kV 17.5kV cables with 25sqmm, 35sqmm, 50sqmm, 70sqmm 1 core conductors.

15kV 17.5kV Cable Termination

HV High Voltage – indoor

  • Cable Termination Type – Heat Shrink
  • Termination Location – Indoor (Cable Box, Substation, Switchgear, Transformer, Motor)
  • Number of Cores – 1 Core
  • Conductors – 25sqmm, 35sqmm, 50sqmm, 70sqmm
  • Cable Type – XLPE EPR (Polymeric)
  • Heat Shrink Standard Tail Length – 410mm
  • Termination Kit Order Code – SPS 1TIS-17.5X-A
  • Suit MV HV Power Cables – BS6622, BS7835, BS7870, BS6883, BS7917 & IEC60502-2

➡ High Voltage Cable Termination 17.5kV Kit List

➡ 17.5kV Cable Terminations | 3 Core Indoor XLPE | 3 Core Outdoor XLPE 

15kV 17.5kV Cable Termination Kits

15kV Cable Termination Bushing Boots | Cable Glands | Screen Earth Kits | Cable Lugs

Single Core XLPE 15kV Terminations

15KV 17.5KV indoor CABLE TERMINATION KITS

The following enables the termination kit selection for 17.5kV 1 core indoor cables:

 15kV/17.5kV Cable Termination Indoor  Cable Termination Kit Range 15kV/17.5kV Cable Termination Outdoor 
1TIS-17.5X-A 1 Core 25-50sqmm 1TES-17.5X-A
1TIS-17.5X-B 1 Core 70-185sqmm 1TES-17.5X-B
1TIS-17.5X-C 1 Core 240-300sqmm 1TES-17.5X-C
1TIS-17.5X-D 1 Core 400-500sqmm 1TES-17.5X-D
Heat Shrink Terminations & Installation

Appropriate cable jointing tools should always be used when installing heat shrink terminations – use tools to ensure the removal of the semi-conductive screen to provide a reliable discharge free termination screen point.

Jointers should use propane type heat shrink gas torches with soft flame and avoid pencil like blue flames which are caused by unregulated heat supply and can cause burning or scorching to the heat shrink tubes.

Keep the flame on the move to ensure even shrinkage of the heat shrink shrink materials – allow termination to cool before applying mechanical strain.

Heat Shrink Cable Terminations 6.6kV 11kV 33kV

Cable terminations using heat shrink technology for MV-HV (6.6kV 11kV 33kV) cable connection to switchgear, transformers, overhead line and pole-mounted – see also Heat Shrink HV Cable Joints