3M LVI-0/x Scotchcast Resin Cable Joints (470W Resin) – Armoured Cables

View Sub Products

3M LVI-0/x Scotchcast Resin Cable Joints (470W Resin) – Armoured Cables

3M LVI-0/x Scotchcast Resin Cable Joints (470W Resin) – Armoured Cables

cABLE JOINTS FOR LV POWER CABLES

Steel Wire Armoured & Braided Power Cables 600V/1000V

3M LVI-0/x Scotchcast resin cable joint kits are used for jointing multi-core steel wire armoured (SWA) polymeric low voltage power cables, including XLPE wire armoured and EPR wire braided cables (600/1000 volts).

3M LVI-0 Scotchcast cable joints incorporate electrical insulation and mechanical protection and are compatible with both compression (crimp) or mechanical shearbolt connectors for conductor jointing of copper or aluminium cores.

Jointing kits can be used for indoor and outdoor, underground direct burial and submerged applications in non-hazardous area locations.

3M Scotchcast hazardous area cable joints are available for jointing power, pilot and instrumentation cables in Zone 1 and Zone 2 potentially explosive atmospheres.

3M LVI-0/x Scotchcast Resin Cable Joints (470W Resin) features

  • Scotchcast resin 470W in transparent two chamber bags for mixing
  • Two part translucent Mould Body with closing system for quick and easy handling
  • Closure cap to prevent any pollution
3M LVI-0/x Scotchcast Resin Cable Joints (470W Resin) Resin)

3M LVI-0/x Scotchcast Resin Cable Joints (470W Resin)

3m Cable Joint description – lvi-0/x

3M Scotchcast Resin Cable Joints

Scotchcast Joints – Safe & Reliable Resins

3M Scotchcast LVI-0/x resin cable joint kits are supplied with a one part translucent mould body for simple and easy handling. Distances inside the cable joint body can be checked easily.

All necessary dimensions, including kit application range, cable preparation are given in the detailed jointing instruction.

The two foam sealing elements can be adapted to the required cable diameter by removing the pre-cut adapter rings.

Scotchcast resin 470W is delivered in a two chamber bag with integrated spout and aluminium Guard Bag for protection of the resin against humidity.

The re-openable seam and integrated spout with a membrane provides a 3M Closed, Mixing and Pouring (pictured) cable jointing system.

After the seam of the two chamber bag is opened, the Scotchcast resin components can be mixed.

To pour the resin into the mould body, the spout is connected with the dome by turning 180°.

While turning, the membrane is cut open to pour the resin. The 3M Closed Mixing and Pouring System provides resin handling without any skin contact – for protection against pollution, a closure cap is applied onto the dome. After curing, the remaining joint resin in the bag can be disposed as household waste.

3M Cable Joints

3M Scotchcast Joints – resin cable joints for power, control and instrumentation cables in industrial and hazardous area Zone 1 and Zone 2.

3M LVI-0/x Scotchcast Resin Cable Joints (470W Resin)

CSA (sqmm) 3M Part Number & Cable Joint Kit Reference
1 Core 2 Core 3 Core 4 Core
1.5 LVI-0/1 LVI-0/1 LVI-0/1
2.5 LVI-0/1 LVI-0/1 LVI-0/1
4 LVI-0/1 LVI-0/1 LVI-0/2
6 LVI-0/2 LVI-0/2 LVI-0/2
10 LVI-0/2 LVI-0/2 LVI-0/2
16 LVI-0/2 LVI-0/2 LVI-0/3 LVI-0/3
25 LVI-0/2 LVI-0/2 LVI-0/3 LVI-0/4
35 LVI-0/2 LVI-0/3 LVI-0/4 LVI-0/4
50 LVI-0/2 LVI-0/3 LVI-0/4 LVI-0/4
70 LVI-0/2 LVI-0/4
95 LVI-0/2 LVI-0/4
120 LVI-0/3
150 LVI-0/3
185 LVI-0/3
240 LVI-0/4
300 LVI-0/4
400 LVI-0/4

3M LVI-0/x Scotchcast resin cable joints are tested according to EN50393.

Type of Test According To EN50393 Table 3 / I / A1 Results
AC Voltage Withstand Test In Air 4kV AC / 1 min Passed
Insulation Resistance Test In Air 1kV DC > 10,000MΩ
Heat Cycle In Air 63 Cycles: 5h/3h Passed
Heat Cycle In Water 63 Cycles: 5h/3h Passed
AC Voltage Withstand Test In Water 4kV AC / 1 min  Passed
Insulation Resistance Test In Water 1kV DC > 10,000MΩ

 

3M Scotchcast 470W Resin

Scotchcast 470W resin is in compliance with EU regulation 1907/2007/EC (REACH) and has a shelf life of at least 36 months when stored between 10°C and 40°C with a humidity level < 75 % in the originally sealed bag.

The expiration date of each product appears on the product label. Storage beyond the date specified on the label does not necessarily mean that the product is no longer usable. In this case however, it is the responsibility of the user to determine applicability of the resin.