Euromold 400TE Tee Connector 11kV 33kV

View Sub Products

Euromold 400TE

Euromold 400TE is a screened separable tee connector specified to terminate and connect medium/high voltage cables onto Interface B bushings in the following voltage classes:

  • 6/10 (12kV)
  • 6.35/11 (12kV)
  • 8.7/15 (17.5kV)
  • 12/20 (24kV)
  • 12.7/22 (24kV)
  • 18/30 (36kV)
  • 19/33 (36kV)

The Euromold 400TE tee connector with 400A current rating is designed for Interface B and covers voltages from 11kV/12kV to 33kV/36kV with a maximum conductor size of 185sqmm.

Euromold 400TE plug-in tee connectors can be supplied as an elbow connector (400LR) and plug-in type epoxy bushings – all suitable for use with Interface B type bushings on SF6 gas-insulated switchgear and medium/high voltage electrical equipment.

Euromold 400 Series MV HV Tee Connectors suitable for use up to 36kV 400Amps.

Designed to connect polymeric insulated cables (XLPE or EPR) with a copper wire screen but can be used on wire armoured, copper tape screen cables with the use of additional screen earth kits and accessories

Connector accessories include: dead-end receptacle, dead-end plug, stand-off plug and earthing plug for type B interfaces.

  • Manufacturer – Nexans Euromold
  • MV HV Equipment Bushing Connector – Interface B
  • Maximum Operating Current – 400A (Amps)
  • Voltage Classes – 12kV 24kV 36kV Maximum
  • Terminate & Connect Cables – Polymeric XLPE EPR
  • Conductor Cross Section Sizes – 25-240sqmm
  • Applications – MV HV Switchgear, Transformers, Motors

➡ See complete range of Nexans Euromold Connectors 

EUROMOLD 400TE Specification

Euromold separable
connector
type
Voltage
Um
(kV)
Current Ir (A) Conductor sizes (sqmm)
min max
400TE/G 11kV 400 Amps 70 240
K400TE/G 24kV 400 Amps 25 240
M400TE/G 36kV 400 Amps 35 185
Euromold 400TE Tee Connector 11kV 33kV - Design

Euromold 400TE Tee Connector 11kV 33kV – Design

Separable elbow connector comprising:

  1. Conductive EPDM insert
  2. Conductive EPDM jacket
  3. Insulating EPDM layer moulded between the insert and the jacket
  4. Type B – 400 A interface as described by CENELEC EN 50180 and 50181
  5. Conductor connector
  6. Basic insulating plug (with VD point)
  7. Cable reducer
  8. Conductive rubber cap
  9. Clamping pin contact
  10. Bail restraint
  11. Earthing lead

The thick conductive EPDM jacket provides a safe to touch screen which ensures safety for personnel, cables and electrical equipment in medium/high voltage installations.

Euromold 400TE Selection Table

For Screened MV HV TEE Connectors

Select the Euromold ordering part number which positions the cable most central to the minimum and maximum core insulation diameter, then substitute X using the table below. Add a ‘K’ for use up to 24 kV and add an ‘M’ for use up to 36 kV.

The complete Euromold 400TE tee connector kit comprises the following components – cable lubricant, wipers, installation instructions and crimp chart.

Kit Contents for Euromold 400TE Connectors

Kit Contents for Euromold 400TE Connectors

 

Euromold 400TE Connector
Part Number
Dia. over core insulation (mm)
min max
400TE/G-11-X 12.0 17.5
400TE/G-15-X 16.0 22.0
400TE/G-19-X 20.0 26.5
400TE/G-22-X 23.5 31.0
400TE/G-25-X 26.5 32.5
400TE/G-27-X 28.5 37.5

 

Conductor
sizes
(sqmm)
Aluminium Cables Copper Cables
DIN Hexagonal Crimp Deep Indent Crimp DIN Hexagonal Crimp
25sqmm 25(K)M-11-2
35sqmm 35(K)M-12-2 35KM-12-1 35(K)M-11-2
50sqmm 50(K)M-12-2 50(K)M-12-1 50(K)M-11-2
70sqmm 70(K)M-12-2 70(K)M-12-1 70(K)M-11-2
95sqmm 95(K)M-12-2 95(K)M-12-1 95(K)M-11-2
120sqmm 120(K)M-12-2 120(K)M-12-1 120(K)M-11-2
150sqmm 150(K)M-12-2 150(K)M-12-1 150(K)M-11-2
185sqmm 185(K)M-12-2 185(K)M-12-1 185(K)M-11-2
240sqmm 240(K)M-12-2 240(K)M-12-1 240(K)M-11-2

 

Euromold MV HV Cable Terminations, Connectors, Elbows & Joints

Euromold MV HV | Cable Terminations, Connectors, Elbows & Joints

Euromold | Connect | Joint | Terminate MV HV Cables – view our complete range of HV Joints & Terminations in heat shrink, cold shrink, push-on and plug-in versions.