Elastimold Elbows – 200 Amp Loadbreak Elbow Connectors

Elastimold Elbows - 200 Amp Loadbreak Elbow Connectors

Elastimold Elbows – 200 Amp Loadbreak Elbow Connectors 15kV 25kV 35kV

Elastimold 200 Amp Loadbreak Elbow Connectors provide a convenient method to connect and disconnect cables and equipment on MV-HV power distribution systems.

Elastimold loadbreak elbows allow for energised operation using standard hotstick tools, loadmake/break operation and a visible disconnect whilst components can be isolated using insulated caps, plugs and parking bushings.

Elastimold are also able to offer optional accessories for system grounding, testing, bypass, surge protection and current limiting fusing – additional connecting points and taps can be provided by use of junctions or feed-thrus.

See Also Deadbreak Elbow Version: Elastimold Elbows200 Amp Deadbreak Elbow Connectors

Elastimold

Power & High Voltage Underground Cable Accessories

Elastimold 200 Amp Loadbreak Elbow Connectors

Ratings Overview

 

  • Current Ratings

  • 200A Continuous, 10kA Sym. 10 Cycles

 

  • 15kV Class Voltage Ratings

    • 8.3kV Phase-to-Ground
    • 14.4kV Phase-to-Phase
    • 95kV BIL
    • 34kV AC Withstand
    • 53kV DC Withstand
    • 11kV Corona Extinction
  • 25kV Class Voltage Ratings

    • 15.2kV Phase-to-Ground
    • 26.3kV Phase-to-Phase
    • 125kV BIL
    • 40kV AC Withstand
    • 78kV DC Withstand
    • 19kV Corona Extinction
  • 35kV Class Voltage Ratings

    • 21.1kV Phase-to-Ground
    • 36.6kV Phase-to-Phase
    • 150kV BIL
    • 50kV AC Withstand
    • 103kV DC Withstand
    • 26kV Corona Extinction

 Elastimold Bushings – 200 Amp & 600 Amp High Voltage Switchgear Transformer Bushings

Elastimold Connectors

MV HV Joints | Terminations | Connectors | Elbows | Splices | Repairs | Fuses

200 Amp Elastimold Elbows

Should you require technical support with component product selection for Elastimold 200 Amp Loadbreak Elbows please contact us.

There is a complete range of MV-HV cable to electrical equipment bushing wells, loadbreak bushing inserts (standard, extended and feed-thru) which are compatible with loadbreak elbow connectors (including replacement, repair, fused and ground type elbows).

Surge arresters can be integrated with medium/high voltage power and electrical distribution systems, 15-35kV.

➡ Complete range of Euromold Connectors & Elbows available for connecting and terminating medium/high voltage cables onto outer cone bushings for SF6 gas insulated switchgear cable terminations.

Elastimold Elbows 200 Amp Loadbreak Elbow Connectors

The following image shows the bushings for cable to equipment connections and the operating accessories for 200-Amp loadbreak separable connector components.

Elastimold Elbows 200 Amp Loadbreak Elbow Connectors

The below image shows 4-point, 3-point and 2-point junction cable to cable connections for 200-Amp loadbreak separable connector components loadbreak bushing inserts.

Elastimold Elbows 200 Amp Loadbreak Elbow Connectors

200-Amp Loadbreak Elbows – Connector Range
Elastimold Connector Range Description Voltage Class Elastimold Part Number Notes
Elbow Connector Elbow Connector 15kV
25kV
35kV
165LR-W5X
275LR-W5X
375LR-W5X
N2, 3, 4, 5
N2, 3, 4, 5
N2, 3, 5
Elbow Connector With Test Point Elbow Connector With Test Point 15kV
25kV
35kV
166LR-W5X
276LR-W5X
376LR-W5X
N2, 3, 4, 5, 23
N2, 3, 4, 5, 23
N2, 3, 5, 23
Jacket Seal Elbow Connector Jacket Seal Elbow Connector 15kV
25kV
165LRJS-W5X
275LRJS-W5X
N2, N19
N2, N19
Jacket Seal Elbow Connector With Test Point Jacket Seal Elbow Connector With Test Point 15kV
25kV
166LRJS-W5X
276LRJS-W5X
N2, N19, N23
N2, N19, N23
Repair Elbow Connector Repair Elbow Connector 15kV
25kV
167ELR-W5X
273ELR-W5X
N5, N10, N18
N5, N10, N18
Jacket Seal Elbow Connector With Test Point Repair Elbow Connector With Test Point 15kV
25kV
168ELR-W5X
274ELR-W5X
N5, N10, N18, N23
N5, N10, N18, N23
Replacement Elbow Replacement Elbow Connector 15kV
25kV
167ELR-W5X
273ELR-W5X
N5, N11, N13
N5, N11, N13
Replacement Elbow With Test Point Replacement Elbow Connector With Test Point 15kV
25kV
168ELR-W5X
274ELR-W5X
N5, N11, N13, N23
N5, N11, N13, N23
Direct Test Elbow Connector Direct Test Elbow Connector 15kV
25kV
167DLR-W5X
273DLR-W5X
N2, N5, N21
N2, N5, N21
Direct Test Repair Elbow Connector Direct Test Repair Elbow Connector 15kV
25kV
167DELR-W5X
273DELR-W5X
N5, N10, N18, N21
N5, N10, N18, N21
Direct Test Repair Elbow Connector With Test Point Direct Test Repair Elbow Connector With Test Point 15kV
25kV
168DELR-W5X
274DELR-W5X
N5, N10, N18, N21, N23
N5, N10, N18, N21, N23

N2. W5X indicates that the catalog number includes 02500X long bi-metal compression lug as standard
For an all-copper lug, replace W5X with W2X in Table X1 to specify the all-copper 02702X lug
N3. Also available as housing only. Specify: 165BLR-W; 275BLR-W;
375BLR-W; 166BLR-W; 276BLR-W; 376BLR-W
N4. Also available as elbow/insert combination. Specify: 165A4-WX;
275A4-WX; 166A4-WX; 276A4-WX
N5. Also available with 200ECS jacket seal included. Add – “S” suffix to catalog number
N10. Repair elbow has extended length contact and elbow housing resulting in a net gain of
31⁄4″ in length
N11. Replacement elbow has extended-length contact and elbow housing resulting
in a net gain of 87⁄8″ in length
N13. Includes long bi-metal contact 00400X
N18. Includes 02509X long bi-metal contact
N19. Includes built-in jacket seal. Also available as housing only — specify: 165BLRJS-W, 166BLRJS-W,
275BLRJS-W or 276LRJS-W. Also available as elbow/insert combination — specify: 165JSA4-W5X,
166JSA4-W5X, 275JSA4-W5X or 276JSA4-W5X
N21. Direct Test Connectors, along with a 200TC-X series meter adapter, a properly rated
voltage meter and Hot-line Stick provide a means for direct conductor voltage testing
N23. Test Point Cap catalog number 156-7

 

MV HV – Medium & High Voltage Cable Joints, Terminations & Connectors (11kV 33kV EHV)

 ➡ Medium Voltage & High Voltage Cable Joints, Terminations, Elbows & Connectors MV HV EHV 

Thorne & Derrick Distributors & Suppliers | Pfisterer | 3M | Prysmian | Nexans Euromold

Data Sheets