11kV 12kV Outdoor Cable Termination Single Core 35-95sqmm SPS 1TES-12X-B
11kV cable termination kits using heat shrink technology are suitable for terminating medium/high voltage (MV-HV) single core polymeric cables (XLPE EPR) – this includes cables with copper wire/tape screen and armoured (wire armoured/braided) or unarmoured cable for outdoor termination of 11kV cables, indoor version also available.
SPS 1TES-12X-B cable termination kit suits 11kV cables with 35sqmm, 50sqmm, 70sqmm, 95sqmm single core conductors.
11kV Cable Termination
HV High Voltage – outdoor
- Cable Termination Type – Heat Shrink
- Termination Location – Outdoor (Pole Top, Overhead Line)
- Cable Voltage – 11kV
- Number of Cores – Single Core
- Conductors – 35sqmm, 50sqmm, 70sqmm, 95sqmm
- Cable Type – XLPE EPR (Polymeric)
- Heat Shrink Standard Tail Length – 400mm
- Termination Kit Order Code – SPS 1TES-12X-B
- Suit MV HV Power Cables – BS6622, BS7835, BS7870, BS6883, BS7917 & IEC60502-2
➡ High Voltage Cable Termination 11kV Kit List
➡ Cable Terminations | 3 Core 11kV Indoor XLPE | 3 Core 11kV Outdoor XLPE
11kV Terminations & Cable Lugs
When installing cable lugs, either crimp type or mechanical shearbolt lugs can be used, the 11kV cable should be cut to dimension L+X per below covered in the cable termination installation instruction – remove the XLPE cable insulation at X and install the 11kV lugs using appropriate crimping tools or method.
Cable lugs should be water-blocked without inspection holes to prevent migration of moisture into the 11kV cable and feature extended barrels for excellent conductivity when terminating copper conductor cables.
➡ 3M Scotch Electrical Tapes are used to splice, terminate, repair and insulate power cable and overhead conductors – here a lineman is shown using 3M Scotch 33 tape to enhance the medium voltage cable insulation on an outdoor installation.
Overhead Line Equipment
T&D accessories for medium/high voltage overhead line installations and maintenance include insulators, portable earthing, arc flash protection, current limiting devices, connectors, bird protectors, substation duct seals, conductor cutting and crimping tools.
Transmission and distribution equipment for MV HV voltages including 11kV, 33kV 66kV and 132kV.
Heat Shrink
Heat shrink cable terminations provide excellent electrical performance, stress control and moisture sealing of MV-HV cables installed outdoors and connected to exposed busbar, overhead line or pole-top hardware operating at 11kV/33kV – specified for termination of power cable exposed to prolonged UV and local weather conditions.
Single Core XLPE 11kV Terminations
11kV outdoor Cable Termination Kits
The following enables the termination kit selection for 11kV single core outdoor cables:
11kV Cable Termination Indoor | Cable Termination Kit Range | 11kV Cable Termination Outdoor c/w Rain Sheds |
1TIS-12X-A | 16-25sqmm | 1TES-12X-A |
1TIS-12X-B | 35-95sqmm | 1TES-12X-B |
1TIS-12X-C | 120-240sqmm | 1TES-12X-C |
1TIS-12X-D | 300-500sqmm | 1TES-12X-D |
1TIS-12X-E | 630-800sqmm | 1TES-12X-E |