This video by 3M Electrical shows how to splice a 15kV SHDC cable using 3M Mining Cable Splice Kit 3103 safely.
3M Mining Cable Splice Kit 3103 may be used for flexible conduit and mining jacket repairs, as well as for cable splicing and jointing mine and portable cable.
3M 3103 cable splices and joints are for use on 3-conductor mine and portable cables, type SHD-GC, MPF-GC and MPF; # 6 AWG-500 kcmil; 5kV, 8kV, 15kV.
3 rolls 3M Scotch 130C linerless rubber self-amalgamating tape – ¾” x 30 ft
Cable Preparation
Position cable end so that the colour rotation matches. Circle cut the cable jacket 12” from each end. Be sure not to damage the cable conductors. Measure 14” from the cable end and fully taper down to the circle cut.
Remove 12” of the cable jacket and cable fillers. Scuff and clean 4” of the cable jacket beyond the top of the taper. Hold back the grounds and ground check conductors and temporarily tape to cable with Temflex 1700P vinyl tape.
Select one conductor and cut at 9”. Match this conductor with the same colour conductor on the opposite end. Take the next conductor at 6”. Remove ¾” of the braid or tape metallic shielding from each conductor plus one half the connector length plus ¼”.
Remove cable semi con to ¼” of the shielding. Remove insulation for one half of the connector length plus ¼”. Pencil the insulation for ¾” and sand it smooth and even with electrical graded abrasive cloth.
Connecting Phase Conductors
Once the cable is prepared, join the power connectors with the proper connectors and cable crimping tool. Be sure the conductors butt up against the centre indents of the connector.
Note that ground wires and ground check will be joined later.
Applying Primary Insulation
Apply two highly stretched half lapped layers of Scotch 13 from the edge of one taper to the other, making sure to completely overlap the exposed semi conductive shield. Next apply highly stretched half lapped layers of Scotch 130C and up onto the tapers.
Build up half lapped layers building onto the existing insulation to 1/8” from the edge of the original cable semi con. The taper should be wrapped equal or greater than the original insulation.
Apply 2 highly stretched half lapped layers of Scotch 13 over the Scotch 130C overlapping the edges of metallic shielding.
Starting 2” up on the exposed metallic shielding wrap 1 half lapped layer of Scotch 24 over semi conductive tape continuing onto the opposite shielding for 2”.
Secure with a half inch square knot and trim the ends. Repeat connecting the phase conductors and applying primary insulation for the remaining phases.
Connecting Ground Connectors
Beforre cutting the ground wires reposition the spliced power conductors so that the conductors are returned to the natural helix of the cable. Lay the ground wires in their natural position in the valley between the two power conductors. Allow the ground to link staggered so as to avoid connection over the power conductor connections.
Join the conductors with the proper connectors and appropriate crimping tool. If present, connect the ground check conductor after trimming it to the proper length and remove one half connector length of the insulation from each lead.
On the ground check, clean the insulation 1” on both sides of the connection and apply one half lapped layer of 3M Temflex 1700P, one half lapped layer of Scotch 130C and one half lapped layer of 1700P over the connector and the clean insulation. Connect the remaining ground wires.
Jacketing The Splice
Bundle the cable assembly and bind it with 3M Temflex 1700P tape. Cover 1700P tape with one half lapped layer of Scotch 2228 and starting half way up the tapers, wrap half lapped layers of Scotch 130C building up and across the splice until the tape is equal to or greater than the original jacket thickness and extends 1” past the top of the jacket tapers.
Start 2” beyond the Scotch 130C tape and wrap one half lapped layer of Scotch 31 tape extending 2” beyond the 130C tape on the opposite end. Always wrap the Scotch 31 tape toward the machine end of the cable.
Start 1“ past the Scotch 31 and apply 3 half lapped layers of 3M Temflex 1700P to each end to temporarily secure the ends of the Scotch 31 tape jacket until the jacket reaches full bond.
Repairing Damaged Cable Jacket
Remove damaged cable jacket and taper the jacket approximately 2”. Scuff and clean 4” of the cable jacket beyond each split end. Bundle the cable assembly and bind with 3M Temflex 1700P tape.
Cover the Temflex 1700P tape with one half lapped layer of Scotch 2228. Wrap half lapped layers of Scotch 130C building up and across the splice until it is equal to or greater than then original jacket thickness and extends 1” beyond the top of the jacket tapers.
Start 2” beyond the Scotch 130C tape and wrap one half lapped layer of Scotch 31 tape extending 2” beyond the 130C tape on the opposite end. Always wrap the Scotch 31 tape toward the machine end of the cable.
Start 1“ past the Scotch 31 and apply 3 half lapped layers of 3M Temflex 1700P to each end to temporarily secure the ends of the Scotch 31 tape jacket until the jacket reaches full bond.
Cold Shrink – invented by 3M over 40 years ago and now the preferred technology for heat-free jointing, terminating, sealing and abandonment of LV HV cables
We hope you find this video informative and educational, contact T&D for technical support, quotations and stock availability for 3M Mining Cable Splice Kit 3103.
➡ Visit 3M Electrical for further information about joints, terminations, tapes and insulation to seal, repair, splice and connect LV MV HV cables.
This video by 3M Electrical shows how to apply3M Cold Shrink Cable Joints safely to splice, repair and connect low voltage power cables, 600V/1000V.
3M Cold Shrink cable joints utilise tool free cold shrink technology where no heat or gas torch is required for jointing cable in onshore and offshore locations with polymeric type cable insulation construction including both XLPE and EPR.
Cold shrink is an effective alternative to resin cable joints and can be used indoors, outdoors, overhead or used in cable trays.
Jointing Cables
Ensure all cables and conductors are free from dirt, residue and contaminants using cable cleaning wipes prior to preparing the cable to install the joint.
Cold shrink tubes and copper wire sleeves are first positioned over the cable.
The cable cores are then cut in such a way to stagger the position of the connectors – either mechanical shearbolt or crimp splice connectors are compatible. Check the proposed conductor connector is of suitable physical dimensions to be used with the cold shrink joint – on larger conductors due to volume displacement of multiple mechanical type connectors it maybe preferable for the jointer to use crimp/compression splices due to smooth profile design overcoming any potential bulging or distortion of the cold shrink tubes.
Accepted brands include Cembre, Arcus and Pfisterer Sicon type connectors.
The cable insulation is then removed and connectors are installed.
Most connector technology can be used providing they suit the requirements of the cable voltage, conductor construction and fit dimensionally within the 3M cable joint.
Scotch Electrical Tapes
Scotch 23 self-amalgamating tape is used to over tape the connectors. Layers of Scotch 23 are applied tightly around each connector overlapping into the primary insulation on each side of the connector position.
A piece of cable jacketing that has been saved from the cable preparation is then wrapped around the connectors for added mechanical protection.
Scotch 33+ premium insulation tape is applied across the lengths of the cold shrink joint to improve electrical insulation and water sealing protection.
The copper wire sleeve is then repositioned over the joint and secured onto the cable armours (either wire or braid armour) with constant force springs providing a 360º earth screen around the cold shrink cable joint for added protection.
Scotch 23 self-amalgamating tape is used to tape over the constant force springs ensuring the application is in the same direction as the constant force springs.
Scotch 2228 mastic tape is wrapped over the constant force springs to ensure a smooth profile and to achieve the required cable seal.
The 3M cold shrink protection tube is then positioned over the cable joint. The coil is then removed by hand to install. The live memory action of the specially formulated material shrinks the cold tube into position and ensures a constant radial pressure and seal.
Cold Shrink Joints Selection Table For Power Cables
Selecting the correct 3M LC type cable joint for use with single and multi-core type power cables, typically BS5467 (SWA) or BS6883 (GSWB).
Standard 3M Cold Shrink cable joints in the LC range can be over-protected by using cable joint moulds and then filled by pouring resin into the mould to encapsulate the joint – for example the cold shrink joint can be modified to provide resistance to hydrocarbon damage in hazardous area locations by using 3M Scotchcast 1402FR resin.
Can 3M Cold Shrink Joints Be Used To Joint Halogen Free & Flame Retardant Cables?
3M cold shrink joints can be used in conjunction with 3M STFF outer-protection sleeve – the joint sleeve is designed to protect the joint from fire. STFF sleeve is halogen free/zero halogen, flame retardant and does not emit toxic fumes in fire situations. Specified for onshore, offshore and rail tunnel applications where fire resistant protection of the cable joint is critical to overall performance, safety integrity and operational fire performance of the electrical cable and power system.
Can 3M Cold Shrink Be Used For Cable Repair?
Where cables have been subject to sheath degradation overtime due to electrical and mechanical stresses whilst in service a cold shrink tube can be used to re-instate the levels of cable insulation – note this requires access to an open-end of the cable or disconnection of the cable due to the tubular design of the cold shrink. If disconnection or isolation of the power cable system is not possible a heat shrink wrap-around type cable repair can be carried out. Read more about this subject in our detailed Blog covering solutions for repairing damaged cables.
Cold Shrink – invented by 3M over 40 years ago and now the preferred technology for heat-free jointing, terminating, sealing and abandonment of LV HV cables
We hope you find this video informative and educational, contact T&D for technical support, quotations and stock availability for 3M Low Voltage Cold Shrink Cable Joints.
➡ Visit 3M Electrical for further information about joints, terminations, tapes and insulation to seal, repair, splice and connect LV MV HV cables.
Learn more about the benefits and applications of Cold Shrink: