THORNE & DERRICK are national distributors LV, MV & HV Cable Installation, Jointing, Earthing & Lightning Protection, Substation & Electrical Equipment – we service UK and global businesses involved in cable installations, cable jointing, substation, overhead line and electrical construction at LV, 11kV, 33kV and EHV.
uploaded by Chris Dodds - Thorne & Derrick Sales & Marketing Manager
Medium Voltage Terminations
A Cause For Concern
MV HV Application: Electric Arc Furnace Power 48 MVA 13.8kV
The heat shrink cable terminations are connecting the 13.8kV high voltage power cable to Siemens Circuit Breakers (3AH2 Type) with vacuum ruptors located in the MV-HV control room – notice the bleeding mastic melting from the cable terminations suggesting overheating potentially caused by sub-standard jointing at the semicon screen cut of the MV-HV cable. The client has used suitable electrical cable cleaners to remove the mastic however the situation is recurring and the client is extremely concerned about the potential risk of a critical power outage caused by eventual failure of the cable in the furnace vacuum circuit breaker.
Although no diagnostic results are available for this application the information is posted to highlight the potential shortcomings with respect to cable preparation prior to the installation of the cable terminations – medium voltage terminations and cable joints should only ever be installed by Trained & Competent Cable Jointers using the correct cable preparation tools.
“The bulge at the bottom of the cable termination will be the red mastic applied over the constant force spring. Definitely too much yellow mastic over the semi-conductive screen ends (large bulge), really no need to fit that much by the cable jointer. I witnessed some testing some years ago in the Elcon HV lab (see Elcon listed on the anti-track heat shrink tube) and the jointer applied less than half that was in the termination kit, just enough to fill the small semicon screen cut void. But the partial discharge (PD) reading was near zero. Apply too much and the PD readings were far above acceptable test standards but not enough to cause this heating issue. Would have liked to have seen some more pictures further out and different angles. But with the red mastic flowing and the discolouration of the heat shrink tubes, a lot of heat there and could be an earthing issue and high circulating currents present as a result.” Richard Poulter, Shrink Polymer Systems.
Medium Voltage Electrical Equipment
Siemens 3AH2/3AH4 Vacuum Circuit-Breakers
In the voltage range up to 24kV, up to 60,000 operating cycles are possible with Siemens 3AH2 circuit-breakers. Minimum maintenance work, such as greasing of operating mechanisms after 10,000 operating cycles and replacement of vacuum interrupters after 30,000 operating cycles, preserves the reliability of these circuit-breakers throughout their entire service life – despite high mechanical stress.
Siemens vacuum circuit-breaker type 3AH4 up to 33kV/36kV is designed for extremely high numbers of operating cycles – the circuit-breaker controls 120,000 operating cycles. 3AH4 circuit-breakers master this extreme stress throughout their entire service life.
Greasing of the operating mechanism is not required until 10,000 operating cycles have been reached – vacuum interrupters just have to be replaced after 30,000 operating cycles.
Note: Due to low quantities, the 3AH2 medium voltage vacuum circuit-breaker will be discontinued by December 31, 2007. As of January 1, 2008, Siemens will offer this circuit-breaker type for another 10 years for replacement purposes only.
MV Medium Voltage Jointing, Terminating & Electrical Equipment Specialists
Medium Voltage Product Categories
Thorne & Derrick are specialist distributors of Medium Voltage Cable Accessories, Copper Earthing Products and Electrical Equipment for use with 11kV/33kV underground cables and overhead lines – including an extensive range of heat shrink, cold shrink joints, terminations and connectors for LV MV HV cables.
uploaded by Chris Dodds T&D Sales & Marketing ManagerÂ
The Video kindly contributed by Watkins & Jacomb CPC shows the cable jointer using Alroc tools to effectively strip and remove the bonded semicon screen from the XLPE insulated 11kV cable prior to installing heat shrink cable terminations.
Alroc ASC R1 | ASC R2 Tool
The Alroc ASC cable tool removes the bonded semi-conductor from MV and HV cables and creates a chamfer on the semi-conductor layer to facilitate the installation of joint, termination or connector.
âž¡ View the complete range of cable jointing tools for the removing of sheath, insulation and semicon screen from medium/high/extra high voltage power cables.
Cable Tools
Cable Tool Model
Alroc ASCR1
Alroc ASCR2
Semi Conductor Diameter
14 – 44mm
20 – 50mm
Cable Conductor Cross Section Area (CSA)
25 – 240sqmm
50 – 630sqmm
Tool Length
205mm
220mm
Width
110mm
120mm
Height
135mm
135mm
Weight
620g
800g
Video Contributed By: Watkins and Jacomb Construction Power & Consultancy. WJCPC are specialist LV HV Cable Termination & Jointing contractors with over 20 years experience in the High Voltage Electrical Industry covering the utilities, renewable energy, rail, data centre and general industry sectors – UKPN competent for LV & HV Termination and Jointing Of Cables, Confined Spaces, Substation Entry and Cable Fault Finding.
âž¡ Thorne & Derrick stock and distribute a complete range of Armoured Cable Joints (SWA)Â in resin cast, cold shrink or heat shrink types for the connection and jointing of multicore and single core XLPE insulated power cables with armour and stranded copper conductors up to 600/1000V – joint kits are available for both AWA (aluminium armoured) and SWA (steel armoured) cables.
Complete supporting range of electrical compression connectors manufactured by Cembre are available and compatible with all types of armoured cable joints.
Thorne & Derrick are Specialist Stockists & Distributors of Hazardous Area Electrical Equipment with international classifications according to ATEX and IECEx – we distribute an extensive range of LV, MV & HV Jointing, Earthing, Substation & Electrical Eqpt.
This includes LV MV HV Cable Accessories such as cable glands, joints, terminations and cleats for safe installation in potentially explosive atmospheres in the hazardous area industries including oil, gas and petrochemicals – we specialise in medium/high voltage cables accessories including 11kV/33kV.
♦ ATEX Cable Glands – watch and learn how to gland cables in hazardous areas using CMP Triton cable glands.
EXPERTS IN EQUIPMENT FOR EXPLOSIVE ATMOSPHERES
LEADERS IN ATEX INNOVATION TO THE HAZARDOUS AREA INDUSTRIES
Thorne & Derrick are leaders in the development and distribution of Product Innovations that deliver significant improvements to clients plant, people and operational safety in the explosive atmosphere industries.
Your proactive problem solvers experienced in succession planning for the replacement of obsolete, non-conformant and legacy equipment in hazardous areas.
Your first-choice provider of innovative and competitive solutions to ensure ATEX & IECEx Compliance for Hazardous Area Electrical, HVAC & Process Instrumentation Equipment to UK and international projects.
What Is Arc Flash PPE and Why Is It Important? Arc flash PPE is specialist personal protective equipment designed to help protect electrical workers against the thermal hazards of an electric arc. It includes arc-rated clothing, protective helmets, face...
Voltage detectors are electrical safety instruments used to identify the presence or absence of voltage on electrical equipment and conductors. They are used by electricians, electrical engineers, utilities and maintenance teams working on low voltage (LV), medium voltage (MV)...