33kV Terminations Single Core XLPE EPR Heat Shrink Cable Terminations
Cable Terminations 11kV 33kV | Single & 3 Core | Medium & High Voltage Cables MV HV
Nexans cable terminations are suitable for connecting and terminating 33kV single core polymeric cables with stranded copper or aluminium conductors, 16-800sqmm.
33kV terminations connect medium/high voltage power cables with polymeric insulation including XLPE and EPR to MV-HV switchgear, transformers and cable boxes – suits single core bonded or easy strip semi-conductive screens.
MV-HV cables distributing 33kV power should always be prepared using correct cable jointing tools.
33kV cable terminations suit both copper tape screened (CTS) and copper wire screened (CWS), armoured (steel wire/braid) or unarmoured cables – single core heat shrink cable terminations are supplied in sets of 3 phases with sufficient materials to effectively terminate 3 single core cable ends.
33kV terminations are tested to international standards including CENELEC HD629.1 and IEC60502-4.
33kV Terminations Single Core Cables
- 33kV Single Core PVC XLPE AWA Armoured Cable BS6622 IEC60502
- 33kV Single Core LSZH Zero Halogen XLPE AWA Armoured Cable BS7835 IEC60502
- 33kV Single Core EPR Insulated Copper Wire Screen Cables
- 33kV Cables with copper tape screen require Nexans SE solderless screen earth kits
- Indoor Air Termination Cable Boxes, Switchgear, Transformers, Motors, Junction Box Enclosures & Substations
- Outdoor Overhead Line (OHL) & Pole Mounted Cable Terminations
- GIS Gas Insulated Switchgear Bushings – see Nexans Euromold Separable Connectors
- More MV HV Cable Terminations
Also: 11kV Single Core Terminations |11kV 3 Core Terminations | 33kV 3 Core Terminations
Complete range of 33kV cable accessories are available to support the installation and termination of singe core cables.
Cable Glands | Screen Earth Kits | Cable Lugs (Crimp Shearbolt) | Bushing Boots
33kV Cable Cleats & Glands
T&D distribute an extensive range of 33kV cable cleats for trefoil cleating of single core cables and fault-rated cable glands for high voltage power systems | Ellis Patents Cleats | CMP Cable Glands
The following selection tables enable the correct specification of 33kV single core cable terminations:
33kV Indoor Terminations
Nexans Order Code | Cable Voltage | Conductor Range – Single Core Cables | Cable Termination Tails |
SREI 36 16-25 | 33kV | 16, 25sqmm | 650mm |
SREI 36 35-95 | 33kV | 35, 50, 70 95sqmm | 650mm |
SREI 36 120-240 | 33kV | 120, 150, 185, 240sqmm | 650mm |
SREI 36 240-500 | 33kV | 240, 300, 400, 500sqmm | 650mm |
SREI 36 400-630 | 33kV | 400, 500, 630sqmm | 650mm |
SREI 36 630-800 | 33kV | 630, 800sqmm | 650mm |
33kV Outdoor Terminations
Nexans Order Code | Cable Voltage | Conductor Range – Single Core Cables | Cable Termination Tails |
SREF 36 16-25 | 33kV | 16, 25sqmm | 650mm |
SREF 36 35-95 | 33kV | 35, 50, 70 95sqmm | 650mm |
SREF 36 120-240 | 33kV | 120, 150, 185, 240sqmm | 650mm |
SREF 36 240-500 | 33kV | 240, 300, 400, 500sqmm | 650mm |
SREF 36 400-630 | 33kV | 400, 500, 630sqmm | 650mm |
SREF 36 630-800 | 33kV | 630, 800sqmm | 650mm |
- * Outdoor cable terminations – where cable termination core lengths need extending to permit connection of cable to overhead line networks standard 33kV termination kits can be supplied with lengthened tails (anti-track heat shrink). Nexans SREI range of heat shrink cable terminations are suitable for following medium/high voltage power cable voltages:
- 6/10 (12kV)
- 6.6/11 (12kV)
- 8.7/15 (17.5kV)
- 12/20 (24kV)
- 12.7/22 (24kV)
- 18/30 (36kV)
- 19/33 (36kV)
Cable Termination 33kV Design
- Cable Lugs (Cembre Crimp Lugs or Pfisterer Sicon Mechanical Lugs)
- Water Sealing Mastic
- Anti Tracking Heat Shrink Tube (Red)
- Stress Control Heat Shrink Tube (Black)
- Stress Control Mastic
- Anti-Track Rain Sheds (Outdoor Cable Terminations)
Installing HV Heat Shrink Cable Terminations 33kV
- 33kV Cables With Copper Wire Screen or Copper Tape Screens
Copper Wire Screen Cables
- Remove the outer cable sheath with 33kV sheath stripping pliers over a distance L + X (L= see table below, X = depth of cable lug barrel + 5mm). Remove bedding tape and copper strip. Clean the outer cable sheath over a distance of 50mm and apply a layer of red thermoplastic tape (with a 50% overlap).
- Bend back the copper wire screens over the cable sheath in a parallel way so that each wire rests upon the thermoplastic tape. Fix with a wire wrapping (2 or 3 windings) at about 50mm below the cutback edge of the 33kV cable sheath. Twist and bind the copper wire screens together, cut at the correct length, install the 33kV cable lugs and connect to earth. For cable terminations located outdoors with armour (SWA or AWA) also connect the earth braid/wire screen to the 33kV cable armour by soldering or solderless earth connection.
- The 33kV cable jointer should then remove the conductive tapes and elements for longitudinal water tightness.
Copper Tape Screen Cables
- Remove the outer cable sheath with sheath stripping pliers over a distance L + X (L= see table below, X = depth of cable lug barrel + 5mm). Remove bedding tape. Clean the outer cable sheath over a distance of 50mm and apply a layer of red thermoplastic tape (with a 50% overlap). Carefully remove the 33kV copper tape screen over a distance up to 20mm from the outer sheath.
- Connect the earth braid to the copper tape screen, by using a copper wire binder and soldering or by a constant force spring. For 33kV cables with armour (SWA or AWA) also connect the earth braid to the cable armour by soldering or other equivalent method. Apply solder to the braid to form a moisture block at about 10mm below the cable sheath edge. Attach the braid with a wire wrapping at 50mm below the outer cut back edge.
- The high voltage cable jointer should then remove the conductive tapes and elements for longitudinal water tightness.
33kV Cable Termination Stripping Dimensions
Cable Termination Voltages (Max kV) | L Indoor Termination (mm) | L Outdoor Termination (mm) |
6.6kV/7.2kV | 250 | 300 |
11kV/17.5kV | 250 | 300 |
24kV | 300 | 350 |
33kV/36kV | 350 | 480 |
♦ Cable Jointing Instruction: 33kV Cable Termination Single Core