66kV Cable Termination – Slip-on Cable Termination Nexans AFN72 (Dry Type Indoor Outdoor)

Euromold AFN72

Euromold AFN72 is a 66kV slip-on cable termination for use indoors, outdoors and exposed to prolonged sunshine and other weather conditions – suitable for connecting polymeric insulated cable to equipment and for the outdoor

The Euromold AFN72 slip-on cable termination is designed for Interface F and covers voltages up to 72.5kV with a maximum conductor size of 2000sqmm.

Euromold AFN72 is compact and modular design supports the suitability for different pollution levels. All termination housings are tested for AC withstand and partical discharge prior to leaving the factory.

66kV connector accessories include: dead-end receptacle, dead-end plug, stand-off plug and earthing plug for type F bushing interfaces.

  • Manufacturer – Nexans Euromold
  • MV HV Equipment Bushing Connector – Interface F 66kV Cable Connectors
  • Voltage Classes – 66kV 72.5kV Maximum
  • Terminate & Connect Cables – Polymeric XLPE EPR
  • Conductor Cross Section Sizes – 95-1200sqmm
  • Applications – 66kV Switchgear, Transformers, Motors

➡ See complete range of Nexans Euromold Connectors 

EUROMOLD AFN72 Specification

Euromold termination
type
Voltage
Um
(kV)
Ø over core
insulation (mm)
Conductor sizes (sqmm)
min max min max
AFN72 66kV 72.5kV 31.5mm 82mm 95sqmm 1200sqmm
Euromold AFN72 Slip-On Cable Termination 66kV - Design

Euromold AFN72 Slip-On Cable Termination 66kV – Design

Separable slip-on cable termination comprising:

  1. Longitudinally sealed mechanical cable lug (topbolt or crimped cable lugs available on request)
  2. Water sealing cover
  3. Silicone shed modules providing different pollution levels
  4. Silicone housing with sheds and integrated conductive silicone rubber insert providing stress relief for the cable
  5. Water sealing mastic
  6. Earthing clamp
  7. Earthing lug

The AFN72 slip-on termination is type tested acc. to IEC 60840, and meets the requirements of IEC/TS 60815-3; SPS class d and e. According to IEC 60112: CTI > 600

Euromold AFN72 Selection Table

Select the Euromold by ordering part number which gives you the best centring of your core insulation diameter and substitute X using table X, according to the conductor cable lug size and type and add the screen wire cable lug.

Order one outdoor termination for a 72.5 kV – 630 mm² stranded aluminium cable with 50 mm² copper wire screen to be used in pollution class environment d. The diameter over core insulation is 54 mm. Order code AFN72-6-D + C400-630×16 + 1070/1x10MS

The complete Euromold AFN72 slip-on termination kit comprises the following components – 1 termination housing, modules with sheds, conductor cable lug, screen wire cable lug, water sealing sleeve, installation instructions, special lubricant, wiper, earthing clamp, water sealing mastic and adhesive tape.

Euromold AFN72 Cable Termination Part
Number

Ø over core
insulation* (mm)
Ø D(mm) Length LAFN
(mm)
Creepage
distance
(mm)
Site
pollution
servey (SPS)
class**
min. max.
AFN72-4-D-X 31.5 41 127 915 1975 d (Heavy)
AFN72-4-E-X 31.5 41 127 1040 2300 e (Very heavy)
AFN72-5-D-X 39.0 47 127 915 1975 d (Heavy)
AFN72-5-E-X 39.0 47 127 1040 2300 e (Very heavy)
AFN72-6-D-X 46.0 55 127 915 1975 d (Heavy)
AFN72-6-E-X 46.0 55 127 1040 2300 e (Very heavy)
AFN72-7-D-X 53 60 172 805 1965 d (Heavy)
AFN72-7-E-X 53 60 172 965 2475 e (Very heavy)
AFN72-8-D-X 59 67 172 805 1965 d (Heavy)
AFN72-8-E-X 59 67 172 965 2475 e (Very heavy)
AFN72-9-D-X 66 73 172 805 1965 d (Heavy)
AFN72-9-E-X 66 73 172 965 2475 e (Very heavy)
AFN72-10-D-X 72 82 172 805 1965 d (Heavy)
AFN72-10-E-X 72 82 172 965 2475 e (Very heavy)

** after cable preparation
** acc. to IEC/TS 60815-3: 2008