Euromold 400TR & 400TR-LB Test Rods 11kV 24kV

Euromold 400TR & 400TR-LBEuromold 400TR & 400TR-LB are medium voltage test rods specified to find cable fault location, phase checking and cable testing. Connections may be made with a cable lug, 4mm plug or spring clips.

Euromold 400TR test rod can be used with 400TB and 440TB tee connectors whilst the 400TR-LB can be used with 400LB – all suitable for use with Interface C Symmetrical type bushings on SF6 gas-insulated switchgear.

Connector accessories include: dead-end receptacle, dead-end plug, stand-off plug and earthing plug for type C interfaces.

  • MV HV Equipment Bushing Connector – Interface C
  • Voltage Class A.C. – 36kV Max
  • Voltage Class D.C. – 96kV Max
  • Terminate & Connect Cables – Polymeric XLPE EPR
  • Applications – MV HV Switchgear, Transformers, Motors

➡ See complete range of Nexans Euromold Connectors 

EUROMOLD 400TR & 400TR-LB Specification

Euromold test rod
type
Maximum A.C.
test voltage
(50 Hz – 1 min)
Maximum D.C.
test voltage
(8 x
U0
– 30 min)
Impulse voltage
(1.2 x 50 µs)
min
400TR 36kV 96kV 95kV
400TR-LB 36kV 96kV 95kV

 

Euromold 400TR & 400TR-LB Test Rods 11kV 24kV - Design

Euromold 400TR & 400TR-LB Test Rods 11kV 24kV – Design

  1. Insulating shroud
  2. Threaded rod for test connection
  3. Two nuts M12
  4. Insulation
  5. Copper test rod stem
  6. Wing nut

An insulating shroud is provided to allow the application of test voltages when bushings are closely spaced.

CONSTRUCTION CHARACTERISTICS
Connector type Male
Technology Slip-0n
Conductor material Copper or Aluminum
DIMENSIONAL CHARACTERISTICS
Conductor cross-section, range 0 .. 0sqmm
ELECTRICAL CHARACTERISTICS
Rated Voltage Uo/U (Um) 12 / 20 (24) kV
Dielectric withstand voltage, 50Hz 1mn 36kV
Impulse voltage 95kV
USAGE CHARACTERISTICS
Interface C (630 – 1250A)

Euromold 400TR & 400TR-LB

Installation

The test rod is mounted on to the clamping screw in the type C interface tee and coupling connectors. The test cable is connected to the threaded stem and the insulating shroud moved to its final position over the end of the test rod.

Euromold MV HV Cable Terminations, Connectors, Elbows & Joints

Euromold MV HV | Cable Terminations, Connectors, Elbows & Joints

Euromold | Connect | Joint | Terminate MV HV Cables – view our complete range of HV Joints & Terminations in heat shrink, cold shrink, push-on and plug-in versions.