IMCORP – Providers of Factory Grade® technology, bringing MV HV power cable and accessory manufacturers’ QC reliability to field installations worldwide.
by Chris Dodds T&D - estimated reading time 5 minutes
OVERVIEW 0.1 Hz VLF test and IMCORP’s Factory Grade® technology are compared side-by-side at utility solar site.
CHALLENGE VLF test passes cables, but cable terminations were still failing.
RESULTS. Based on distribution system experience, utility uses IMCORP’s Factory Grade® technology to identify workmanship defects and VLF test induced damage.
A utility client of IMCORP asked them to commission medium voltage cable systems at a new generation facility after experiencing several MV cable termination failures.
The cable installation contractor had already tested the MV cable systems with a very low frequency (VLF) test.
Uninformed contractors often make a claim based on a common myth that ‘proper’ VLF testing would detect serious MV-HV cable defects while not harming healthy cable insulation or aggravating minor defects.
In addition, the misguided claim often states that passing a VLF test means the medium or high voltage cable system will deliver years of trouble free service.
Wrong.
Unfortunately the owner initially believed these commonly held myths, energised the MV power system and subsequently experienced several catastrophic failures that damaged switchgear, costing them significant down time and losses in generation revenue.
Substandard MV HV cable jointing and installation necessitated the replacement of multiple HV heat shrink cable terminations after a succession of in-service cable termination failures.
Pictured opposite the heat shrink anti-track tubing has been removed shown the tracking between the medium voltage heat shrink and XLPE cable insulation.
When the cable terminations were dissected the technician not only found cable jointer workmanship issues, including insufficient shrinkage of heat shrink layers, but clear evidence of damage caused by the VLF test that passed the medium voltage cable terminations a short time before.
Ben Lanz (Director, Applications Engineering at IMCORP) comments, “a VLF test passed this heat shrink termination. An offline 1.5Uo 50/60Hz PD partial discharge assessment with 5pC sensitivity identified this MV cable termination which is why we have the picture. The original installation defect and VLF test damage are plainly visible. This case along with many others is the reason IMCORP recommend a factory comparable PD test for critical medium/high voltage power installations and QC spot checks for newly trained cable jointers and installers of MV-HV joints, terminations and connectors. I acknowledge that a VLF test was the best the utility and power industry had 10 years ago but with the evidence we have now, I generally don’t recommend going over the operating voltage with a VLF test since it can not find most MV-HV cable detects found by a factory comparable PD test.”
The 2 most serious cable termination anomalies were small voids on the medium voltage XLPE cable insulation shield interface and “fall-in” cable insulation problem at the conductor shield interface.
Could a failure to remove the semicon screen from the XLPE insulation of MV-HV cables contribute to this type of cable failure?
Here, the semicon screen was removed sufficiently from the MV-HV cable using correct cable jointing tools. Most likely the VLF test burned a track in voids caused by insufficient void filling mastic at the semicon cutback and/or insufficient shrinking of the heat shrink tube with the green zinc oxide (ZnO) stress controlling layer on the inside of the cable termination.
MV Cable Termination Failures
Here, failure of the heat shrink stress control component of the cable termination was poorly placed in relation to the semi-conductor screen cut causing termination failure of the substation cables linked to a generation plant on an onshore windfarm.
Manufacturers Standards
Component Standard
Testing Frequency
Sensitivity
Voltage
Cable Terminations IEEE 48
50/60 Hz
5pC
< 1.5 Uo
Cable Joints IEEE 404
50/60 Hz
5pC
< 1.5 Uo
Separable Connectors IEEE 386
50/60 Hz
5pC
< 1.3 Uo
MV Extruded Cable ICEA S-97/94-682/649
50/60 Hz
5pC
< 4.0 Uo
HV EHV Extruded Cable ICEA S-108-720
50/60 Hz
5pC
< 2.0 Uo
Reducing Cable Termination Failures
Of course site standards and international working procedures vary but the following professional advice has universal methodology:
“There are three main components to reducing the risk of failure during the infant mortality phase of an installation’s life (bathtub curve): 1) Have policies that ensure you only procure high quality equipment 2) Ensure that equipment is installed by qualified, trained and experienced personnel who work to high standards 3) Commission it thoroughly with a view to exposing flaws and weaknesses and then correcting them. As has been proven many times before, thousands saved today may cost you millions tomorrow.”
Jason St Martin (Senior Electrical Inspector at DMIRS Building and Energy State of Western Australia)
Since 1985 T&D have serviced UK and international businesses involved in cable installations, earthing, duct sealing, jointing, substation, overhead line and electrical construction at LV, MV & HV.
Our customers are contractors, specifiers and end-users involved in cable installations, cable jointing, substation, overhead line and electrical construction at LV, MV & HV.
Medium voltage power cables can fail for several reasons – pictured below is a common installation error near the outer semicon screen cutback by the cable jointer on the heat shrink cable termination – the highest electrical stress point in an open air cable termination.
To prevent this IMCORP recommend MV HV Jointer Training coupled with a factory comparable partial discharge test after installation to provide feedback to the cable installer – 50/60Hz offline PD test with better than 5pC sensitivity.
Partial Discharge (PD) at the crossed cores of the HV cable causing failure of the heat shrink cable termination
Contributed By: Watkins and Jacomb Construction Power & Consultancy
WJCPC are specialist LV HV Cable Jointing contractors with over 20 years experience in the electrical industry covering the utilities, renewable energy, rail, data centre and general industry sectors – with UKPN competency for LV HV Jointing, Confined Spaces, Substation Entry and Fault Finding.
The video below shows WJCPC cutting a section of BS6622 11kV 3 core medium voltage power cable using the battery operated Cembre B-TC950 tool prior to terminating into the MV cable box using heat shrink terminations.
The Cembre B-TC950 battery operated cable cutting tool has a capacity to cut up to 95mm outside diameter power cables including 11kV and 33kV. The Cembre tool features a dual speed cutting action – the two speed operation and automatic switching from a rapid advancing speed of the ram to a slower, more powerful speed for cutting copper and aluminium conductors.
Not suitable for cutting steel wire armour (SWA) or live/energised cables.
Cembre B-TC950 has a cutting power of 880 bar (12,700 psi).
How To Use Cembre Cutting Tools
Cutting Blade Advancement
The user or jointer should press the operating button (5) to activate the motor-pump – the ram will gradually move forward until the lower cable cutting blade (3) touches the cable conductor. To halt the advancement of the tool blade, release the button (5)and the motor will cut out. Ensure the cutting blade is exactly positioned on the desired cutting point of the cable – if not re-open the blade following instructions and reposition it.
Cable Cutting
Firmly hold the Cembre tool and operate the button (5) to gradually move the lower cutting blade (4) to cut through the conductor. When the conductor cut is clean and complete, release the button (5), otherwise the maximum pressure relief valve has activated.
Blade Retraction
By operating the pressure release button (6), the ram will retract and open the lower cutter blade of the tool.
Cembre B-TC950 Cable Cutting Tools – Distributed by T&D
T&D distribute a complete range of cable cutters including ratchet, hydraulic and battery operated for precise and clean cutting of power, control and instrumentation cables with steel wire armour or braid and lead covered sheathings – ratchet cable cutters are recommended for cropping cable conductors of LV-HV cables where working space and access is confined in high voltage cable end termination boxes.
11kV Cable Preparation
Training & Tools
Failure to effectively and precisely prepare MV-HV cables by the jointer is a common cause of 11kV cable failure – images 1+2 below are clear examples of jointers workmanship deficiencies on a recent project which WJCPC were contracted to correct and complete following the condemning of the 11kV cable installation by the main contractor.
The 11kV 3 core XLPE medium voltage power cables show a reckless finish to the easy peel semiconductor screen with a toxic mixture of jagged edges, scoring marks and deep ringing – this could have been caused by the jointers using fully bonded screen removal tools with incorrect depth setting rather than the correct semicon stripping tool. The use of the correct cable jointing tools for each stage of cable preparation is critical to ensure safe and reliable installation and service of MV joints and terminations.
Compare images 1+2 with the perfect uniformity of MV cable preparation in image 3 achieved by WJCPC.
Critical to the long term stability and field performance of 11kV cable terminations and joints is perfect preparation of cable – care should be taken to ensure appointed MV HV Cable Jointing contractors are suitably trained and equipped with the required jointing, cutting and crimping tooling to perform medium/high voltage cable installations.
THORNE & DERRICK are national distributors of LV, MV & HV Arc Flash Clothing, Cable Installation, Jointing, Substation Duct Seals & Electrical Equipment – we service UK and global businesses involved in cable installations, cable jointing, earthing substations, overhead line and electrical construction at LV, 11kV, 33kV and EHV.
Since 1985, T&D have established an international reputation based on SERVICE | INTEGRITY | TRUST.
Contact us for 3M Electrical, ABB, Alroc, AN Wallis, CATU Electrical, Cembre, Centriforce, CMP, CSD, Elastimold, Ellis Patents, Emtelle, Euromold, Filoform , Furse, Lucy Electric & Zodion, Nexans, Pfisterer, Polypipe, Prysmian, Roxtec, Sicame, WT Henley.
The original article included an electrical arc flash incident video from CATU Electrical.
The footage illustrates the potential severity of electrical arc hazards.
It also reinforces the importance of safe working procedures and suitable protective equipment.
NFPA 70E and IEEE 1584 – Arc Flash Assessment
NFPA 70E and IEEE 1584 are important references in electrical arc flash risk management.
However, they serve different purposes.
NFPA 70E – Electrical Safety in the Workplace
NFPA 70E addresses electrical safety practices in the workplace.
It includes requirements and guidance relating to electrical hazards, risk assessment and protective measures.
For example, it supports a structured approach to electrical safety planning.
However, organisations must also follow the legal and technical requirements applicable in their jurisdiction.
IEEE 1584 – Arc Flash Hazard Calculations
IEEE 1584 provides methods for calculating arc flash incident energy and related parameters within its defined scope.
The original article referred to IEEE 1584-2002.
However, this historical edition should not be treated as the current calculation standard.
Engineers must confirm the applicable edition, calculation model and software implementation before conducting an assessment.
The original reference can be found through IEEE 1584-2002.
Arc Flash PPE – The Last Line of Defence
Arc flash PPE helps protect workers against specified thermal hazards.
However, it does not eliminate the possibility of an electrical arc or prevent every type of injury.
For this reason, organisations must first identify and control electrical risks wherever reasonably practicable.
Paul Hopton – Electrical Safety UK
Paul Hopton, Principal Electrical Consultant at Electrical Safety UK Limited, explained the importance of risk assessment before PPE selection.
“PPE is the last item on the list when putting in place arc incident control measures. Your arc flash risk assessment should measure the severity of the hazard (incident energy levels) and then look how that incident energy can be minimised. You should then consider what activities you carry out that could expose you to any residual arc flash risk that may be controlled with PPE.”
This approach helps businesses assess the hazard before selecting protective clothing.
It also reinforces the importance of reducing risk rather than relying entirely on PPE.
Reducing Arc Flash Risk
Suitable risk reduction measures may include:
Eliminating the need for exposed energised work where practicable.
Applying approved safe isolation procedures.
Using suitable equipment design and protection arrangements.
Reviewing protective device settings and fault clearing times.
Implementing suitable operating and maintenance procedures.
Providing appropriate training and supervision.
Selecting task-specific arc flash PPE for remaining hazards.
The final PPE arrangement must reflect the actual risk assessment and applicable requirements.
Service Branch: up to 185sqmm Waveform 2 x Single Phase Services up to 35sqmm (The 2 services from same phase)
164997
Service Branch: up to 185sqmm Waveform with up to 4 x Single Phase CNE Services
165646
Service Branch: 300sqmm Waveform with up to 4 x Single Phase CNE/SNE or 1 x 3-Phase CNE/SNE Services
165970
Service Branch: up to 95sqmm PILC with up to 4 x Single Phase Services
166189
Service Branch: up to 185sqmm PILC with 1-2 Single Phase Services
166259
Service Branch: up to 300sqmm PILC with 1 or 2 Single Phase CNE or 1 x 3-Phase CNE Services
165788
Service Branch: 70/120sqmm Consac with up to 4 x Single Phase Services
165858
Service Branch: 185/240sqmm Consac with up to 4 Services
Triple Concentric Cable Joints
168289
Stop End: Paper Lead Triple Concentric up to 0.12Sq in
168291
Service Breeches Joint: Triple Concentric Paper Lead up to 0.12in with 3-Core CNE Branch up to 35sqmm
168291
Service Breeches Joint: Single Phase Concentric Paper Lead up to 0.15in with Single Phase CNE Branch up to 35sqmm
168290
Straight Joint: Transition; Triple Concentric up to 0.12Sqin to Waveform Cable up to 95sqmm ( with single phase service if required)
Cable Pulling & Laying Equipment LV HV
T&D supply Utilities & Approved Contractors with cable pulling products including cable rollers, cable socks and drum lifting jacks to enable the installation of low voltage and high voltage cables intro trench or duct: this includes single core, 3 core and Triplex 11kV/33kV power cables and LV waveform, mains and service cables.
See our online UK DNO Register of Approved Joints, Terminations & Electrical Equipment
3M CSCAK cold shrink cable abandonment kits are used to temporarily or permanently seal power, control and instrumentation cables – especially the abandonment of redundant or decommissioned low voltage offshore, marine and shipwiring power, control and instrumentation cables.
3M CSCAK kits are complete with all components to provide temporary or permanent abandonment of cables – this ensures cables are safe even if re-energised using cold shrink end caps and pre-stretched tubes.
The 3M Electrical video explains how cables are effectively short circuited using 3M Scotch Electrical Tapes and earthing products, including Scotch 24 and constant force springs.
The 3M Electrical video also shows the “live memory” action of Cold Shrink providing reliable and durable cable end seals without need for “hot working” permits in potentially explosive atmospheres or hazardous area zones located onshore and offshore.
Cold Shrink – invented by 3M over 40 years ago and now the preferred technology for heat-free jointing, terminating, sealing and abandonment of LV HV cables
Watch Video ➡
We hope you find this video informative and educational, contact T&D for technical support, quotations and stock availability for 3M Cable Abandonment Kits.
Cable Abandonment Kit Selection Table
Should you require support about selecting the correct cable abandonment kit from the 3M Cold Shrink product range for use with low, medium or high voltage cables please contact us – a complete range of Cold Shrink cable joints and terminations is available for MV-HV cables, including 11kV/33kV.
Where additional mechanical protection for connecting underground power cables in cable trench is required we can recommend Scotchcast cable joints with resin encapsulation to resist impact damage during backfill or future excavation and digging works.
For jointing cables in hazardous area locations go to our Blog about ATEX cable joints utilising advanced specification Scotchcast resins to provide a hydro carbon resistant joint or repair to damaged or extended cable circuits.
➡ Visit 3M Electrical for further information about 3M cable joints, terminations, tapes and insulation to seal, repair, splice and connect LV MV HV cables.
What Is Arc Flash PPE and Why Is It Important? Arc flash PPE is specialist personal protective equipment designed to help protect electrical workers against the thermal hazards of an electric arc. It includes arc-rated clothing, protective helmets, face...
Voltage detectors are electrical safety instruments used to identify the presence or absence of voltage on electrical equipment and conductors. They are used by electricians, electrical engineers, utilities and maintenance teams working on low voltage (LV), medium voltage (MV)...