EHV Joints – 132kV Extra High Voltage Cable Joints Using 3M Cold Shrink

EHV Joints – 132kV Extra High Voltage Cable Joints Using 3M Cold Shrink
132kV Cable Joints
132kV high voltage power cables are installed indoor or outdoor in open air in cable containment tray, cable trough and conduit or for direct burial underground in free draining soil or inside cable duct where no mechanical damage is to be expected.
132kV cables provide power for utilities high voltage underground distribution systems and in commercial buildings, industrial plants, power stations and substations.
3M high voltage 132kV cable joints have been designed for XLPE polymeric insulated cables up to 145kV Umax according to IEC 60840 with or without lead sheath and with or without copper screen wires – this includes super-clean XLPE insulation with bonded semi-conductive screens and either copper or aluminium conductors up to 1600sqmm.
3M offers 145kV Class high voltage cold shrink cable joints that are designed to fit a universal cable and can be kitted specifically to meet the high voltage application.
Silicone joint body is manufactured from Cold Shrink Technology.
The outer re-jacketing is installed using heat shrink tube or polyurethane 2 part Scotchcast resin or other.
Joint kits are available with, or without shield break for cross bonding and are based on the SC/SS 145-II cable joint body family.
The 3M High Voltage 132kV cable joints 98-AD xxx-1/x are in compliance to EU regulation 1907/2007/EC (REACH).
All components of the 3M Cold Shrink 98-AD xxx-1/x range are recommended to storage and stock rotation under temperature condition of -40°C up to 50°C.
The shelf life of the 3M EHV loaded inline cable joint body is specified as 18 month. All other components are specified to 36 month.
Jointing XLPE To Gas Compression & Oil Filled Cables
As utilities adopt modern technology polymeric (XLPE insulated cables) the process of 132kV asset replacement of aged gas compression and oil filled cable circuits demands transition type cable joints – we can support all your requirements for the jointing, termination and connection of 132kV high voltage cables.
Gas compression cables were generally installed from the early 1950s to the mid 1960s and oil filled cables were installed from the 1950s through to the late 1990s. From the late 1990s onwards a new type of non-pressurised XLPE cable was installed.

132kV Cold Shrink Inline Cable Joint with Heat Shrink or Resin Re-jacketing for Cables up to 145kV

132kV Extra High Voltage Cable Joints Using 3M Cold Shrink
EHV Joints
3M Cold Shrink Features
- One piece Cold Shrink 132kV cable joints and splice body
- Special cable jointing tools required for installation and preparation
- Shearbolt connectors or crimp connector included
- Connectors for round compacted or round segmented cable available
- Flexible design accommodates different shielding and cable re‐jacketing systems
- Re‐jacketing with 3M Cold Shrink, heat shrink or resin filled enclosure metal housing
Cable Joint Applications
- For inline 132kV cable joints underground
- Application range from 240sqmm up to 1600sqmm copper or aluminium conductors
- Solutions for fibre optic connections are available on request
- In‐line and cross bond cable joint design available
3M COLD SHRINK Technical Specification
Rated Voltage U0/U | 64/110kV and 76/132kV |
Max. System Voltage Umax | 145kV |
Application Range Primary Insulation | 98-AD xxx-1/1 57.0 – 67.0mm 98-AD xxx-1/2 67.0 – 79.0mm 98-AD xxx-1/3 71.0 – 86.0mm |
Application Range Cross Section | 240sqmm – 1600sqmm The application range varies depending on the cable insulation diameter. |
Earth Screen | Jointing kits are available with a copper meshed earth screen or with copper housing |
Type Test | According to IEC 60840 completed successfully |
The 132kV Joint Bay
➡ Image: 132kV Underground Cable Installation Typical Direct Buried Details & Construction Swathe (General Arrangement National Grid) – the high voltage power cables should be overprotected using high impact resistant HV cable covers, such as Stokbords.
Contact us for cable joint dimensions to enable optimum design of cable joint bays for underground cable installations up to 132kV.

Inline Joint SC/SS-145 3M Cold Shrink
3M COLD SHRINK Selection Guide
The following tables enable the selection of 132kV cable joints – should you require any further information, technical support or 132kV jointer training courses please contact us.
Inline Jointing Kits Without Shield Break & Heat Shrink Re-Jacketing
3M 132kV Cold Shrink Kit Reference | 132kV Cable Dimensions for Polymeric Cable | Connector Dimensions | |||||
Type of Metal Screen | Diameter Over Primary Insulation (mm) | Cross Section (1) 123kV Umax (sqmm) | Cross Section (1) 145kV Umax (sqmm) | Diameter Over Cable Jacket (2) Max (mm) | Maximum Diameter (mm) | Maximum Length (mm) | |
98-AD 210-1/1 | Cu-Wire Screen | 57.0-67.0 | 300-630 | 240-630 | 80 | 67.0 | 230 |
98-AD 210-1/2 | Cu-Wire Screen | 67.0-79.0 | 630-1200 | 630-1200 | 89 | 79.0 | 230 |
98-AD 210-1/3 | Cu-Wire Screen | 71.0-86.0 | 1000-1600 | 1000-1600 | 100 | 86.0 | 230 |
98-AD 211-1/1 | Metal Screen | 57.0-67.0 | 300-630 | 240-630 | 80 | 67.0 | 230 |
98-AD 211-1/2 | Metal Screen | 67.0-79.0 | 630-1200 | 630-1200 | 89 | 79.0 | 230 |
98-AD 211-1/3 | Metal Screen | 71.0-86.0 | 1000-1600 | 1000-1600 | 105 | 86.0 | 230 |
Inline Jointing Kits With Shield Break & Heat Shrink Re-Jacketing
3M 132kV Cold Shrink Kit Reference | 132kV Cable Dimensions for Polymeric Cable | Connector Dimensions | |||||
Type of Metal Screen | Diameter Over Primary Insulation (mm) | Cross Section (1) 123kV Umax (sqmm) | Cross Section (1) 145kV Umax (sqmm) | Diameter Over Cable Jacket (2) Max (mm) | Maximum Diameter (mm) | Maximum Length (mm) | |
98-AD 230-1/1 | Cu-Wire Screen | 57.0-67.0 | 300-630 | 240-630 | 80 | 67.0 | 230 |
98-AD 230-1/2 | Cu-Wire Screen | 67.0-79.0 | 630-1200 | 630-1200 | 89 | 79.0 | 230 |
98-AD 230-1/3 | Cu-Wire Screen | 71.0-86.0 | 1000-1600 | 1000-1600 | 100 | 86.0 | 230 |
98-AD 231-1/1 | Metal Screen | 57.0-67.0 | 300-630 | 240-630 | 80 | 67.0 | 230 |
98-AD 231-1/2 | Metal Screen | 67.0-79.0 | 630-1200 | 630-1200 | 89 | 79.0 | 230 |
98-AD 231-1/3 | Metal Screen | 71.0-86.0 | 1000-1600 | 1000-1600 | 105 | 86.0 | 230 |
Inline Jointing Kits Without Shield Break, Cu-Casing & Heat Shrink Re-Jacketing
3M 132kV Cold Shrink Kit Reference | 132kV Cable Dimensions for Polymeric Cable | Connector Dimensions | |||||
Type of Metal Screen | Diameter Over Primary Insulation (mm) | Cross Section (1) 123kV Umax (sqmm) | Cross Section (1) 145kV Umax (sqmm) | Diameter Over Cable Jacket (2) Max (mm) | Maximum Diameter (mm) | Maximum Length (mm) | |
98-AD 241-1/1 | Metal Screen | 57.0-67.0 | 300-630 | 240-630 | 80 | 67.0 | 230 |
98-AD 241-1/2 | Metal Screen | 67.0-79.0 | 630-1200 | 630-1200 | 89 | 79.0 | 230 |
98-AD 241-1/3 | Metal Screen | 71.0-86.0 | 1000-1600 | 1000-1600 | 105 | 86.0 | 230 |
Inline Jointing Kits With Shield Break, Cu-Casing & Heat Shrink Re-Jacketing
3M 132kV Cold Shrink Kit Reference | 132kV Cable Dimensions for Polymeric Cable | Connector Dimensions | |||||
Type of Metal Screen | Diameter Over Primary Insulation (mm) | Cross Section (1) 123kV Umax (sqmm) | Cross Section (1) 145kV Umax (sqmm) | Diameter Over Cable Jacket (2) Max (mm) | Maximum Diameter (mm) | Maximum Length (mm) | |
98-AD 251-1/1 | Metal Screen | 57.0-67.0 | 300-630 | 240-630 | 80 | 67.0 | 230 |
98-AD 251-1/2 | Metal Screen | 67.0-79.0 | 630-1200 | 630-1200 | 89 | 79.0 | 230 |
98-AD 251-1/3 | Metal Screen | 71.0-86.0 | 1000-1600 | 1000-1600 | 105 | 86.0 | 230 |
Inline Jointing Kits Without Shield Break & Resin Re-Jacketing
3M 132kV Cold Shrink Kit Reference | 132kV Cable Dimensions for Polymeric Cable | Connector Dimensions | |||||
Type of Metal Screen | Diameter Over Primary Insulation (mm) | Cross Section (1) 123kV Umax (sqmm) | Cross Section (1) 145kV Umax (sqmm) | Diameter Over Cable Jacket (2) Max (mm) | Maximum Diameter (mm) | Maximum Length (mm) | |
98-AD 410-1/1 | Cu-Wire Screen | 57.0-67.0 | 300-630 | 240-630 | 80 | 67.0 | 230 |
98-AD 410-1/2 | Cu-Wire Screen | 67.0-79.0 | 630-1200 | 630-1200 | 89 | 79.0 | 230 |
98-AD 410-1/3 | Cu-Wire Screen | 71.0-86.0 | 1000-1600 | 1000-1600 | 100 | 86.0 | 230 |
98-AD 411-1/1 | Metal Screen | 57.0-67.0 | 300-630 | 240-630 | 80 | 67.0 | 230 |
98-AD 411-1/2 | Metal Screen | 67.0-79.0 | 630-1200 | 630-1200 | 89 | 79.0 | 230 |
98-AD 411-1/3 | Metal Screen | 71.0-86.0 | 1000-1600 | 1000-1600 | 105 | 86.0 | 230 |
Inline Jointing Kits With Shield Break & Resin Re-Jacketing
3M 132kV Cold Shrink Kit Reference | 132kV Cable Dimensions for Polymeric Cable | Connector Dimensions | |||||
Type of Metal Screen | Diameter Over Primary Insulation (mm) | Cross Section (1) 64/110kV 123kV Umax (sqmm) | Cross Section (1) 76/132kV 145kV Umax (sqmm) | Diameter Over Cable Jacket (2) Max (mm) | Maximum Diameter (mm) | Maximum Length (mm) | |
98-AD 430-1/1 | Cu-Wire Screen | 57.0-67.0 | 300-630 | 240-630 | 80 | 67.0 | 230 |
98-AD 430-1/2 | Cu-Wire Screen | 67.0-79.0 | 630-1200 | 630-1200 | 89 | 79.0 | 230 |
98-AD 430-1/3 | Cu-Wire Screen | 71.0-86.0 | 1000-1600 | 1000-1600 | 100 | 86.0 | 230 |
98-AD 431-1/1 | Metal Screen | 57.0-67.0 | 300-630 | 240-630 | 80 | 67.0 | 230 |
98-AD 431-1/2 | Metal Screen | 67.0-79.0 | 630-1200 | 630-1200 | 89 | 79.0 | 230 |
98-AD 431-1/3 | Metal Screen | 71.0-86.0 | 1000-1600 | 1000-1600 | 105 | 86.0 | 230 |
Inline Jointing Kits Without Shield Break, Cu-Casing & Outer Polymeric Housing with Resin
3M 132kV Cold Shrink Kit Reference | 132kV Cable Dimensions for Polymeric Cable | Connector Dimensions | |||||
Type of Metal Screen | Diameter Over Primary Insulation (mm) | Cross Section (1) 64/110kV 123kV Umax (sqmm) | Cross Section (1) 76/132kV 145kV Umax (sqmm) | Diameter Over Cable Jacket (2) Max (mm) | Maximum Diameter (mm) | Maximum Length (mm) | |
98-AD 440-1/1 | Cu-Wire Screen | 57.0-67.0 | 300-630 | 240-630 | 80 | 67.0 | 230 |
98-AD 440-1/2 | Cu-Wire Screen | 67.0-79.0 | 630-1200 | 630-1200 | 89 | 79.0 | 230 |
98-AD 440-1/3 | Cu-Wire Screen | 71.0-86.0 | 1000-1600 | 1000-1600 | 100 | 86.0 | 230 |
98-AD 441-1/1 | Metal Screen | 57.0-67.0 | 300-630 | 240-630 | 80 | 67.0 | 230 |
98-AD 441-1/2 | Metal Screen | 67.0-79.0 | 630-1200 | 630-1200 | 89 | 79.0 | 230 |
98-AD 441-1/3 | Metal Screen | 71.0-86.0 | 1000-1600 | 1000-1600 | 105 | 86.0 | 230 |
Inline Jointing Kits With Shield Break, Cu-Casing & Outer Polymeric Housing with Resin
3M 132kV Cold Shrink Kit Reference | 132kV Cable Dimensions for Polymeric Cable | Connector Dimensions | |||||
Type of Metal Screen | Diameter Over Primary Insulation (mm) | Cross Section (1) 64/110kV 123kV Umax (sqmm) | Cross Section (1) 76/132kV 145kV Umax (sqmm) | Diameter Over Cable Jacket (2) Max (mm) | Maximum Diameter (mm) | Maximum Length (mm) | |
98-AD 450-1/1 | Cu-Wire Screen | 57.0-67.0 | 300-630 | 240-630 | 80 | 67.0 | 230 |
98-AD 450-1/2 | Cu-Wire Screen | 67.0-79.0 | 630-1200 | 630-1200 | 89 | 79.0 | 230 |
98-AD 450-1/3 | Cu-Wire Screen | 71.0-86.0 | 1000-1600 | 1000-1600 | 100 | 86.0 | 230 |
98-AD 451-1/1 | Metal Screen | 57.0-67.0 | 300-630 | 240-630 | 80 | 67.0 | 230 |
98-AD 451-1/2 | Metal Screen | 67.0-79.0 | 630-1200 | 630-1200 | 89 | 79.0 | 230 |
98-AD 451-1/3 | Metal Screen | 71.0-86.0 | 1000-1600 | 1000-1600 | 105 | 86.0 | 230 |
(1) The application range varies depending on the primary insulation diameter.
(2) Maximum cable jacket diameter can change depending on the screen cross section.

132kV Surge Arresters | Cable Socks | Insulating Poles | Voltage Detectors | Link Boxes | Duct Seals
Oil Filled Circuits
Thorne & Derrick supply a complete range of cable jointing materials to enable the refurbishment and jointing of 132kV oil filled cable circuits – this includes reinforcement for plumbs (Prysmian Araldite DBF/Aradur HY956EN Epoxy Compound), Pirelli G123 box filling jointing compound, Prysmian G38A box filling compound, BICCASEAL solid set putty, Bitugel bitumen paint, Scotch 69 glass fibre tape and tinned copper binder wire.
From 132kV Up to 500kV
Included in our 132kV range are taped cable joints and a range of joints for paper insulated (PILC) cables and transitions from paper to polymeric (XLPE) insulated cables. A complete range of factory tested pre-molded EPDM or silicone rubber cable joints up to 500kV both in standard or shieldbreak version for cross-bonding are also available. Different types of outer joint covers to suit various customer requirements are also available – this includes heat-shrinkable, synthetic tubes or a plain metallic cover with external sheathing.
Also: 3M Cold Shrink Cable Terminations for medium and high voltage 11kV 33kV 66kV cable terminating.
➡ Should you require customer service or technical support on the selection or specification of LV MV HV Cable Accessories please contact us – view the full range of 3M Cold Shrink Cable Joints below.
♦ For LV Low Voltage Cables | Cold Shrink Cable Terminations MV | Cold Shrink Cable Abandonment | Cold Shrink Tubes

3M Cold Shrink