uploaded by Chris Dodds - Thorne & DerrickÂ
In the UK the Distribution Network Operators permit appropriately accredited ICP’s to carry out live cable jointing onto service and mains connections on their low voltage electrical distribution systems – those cable jointers must be trained, assessed and authorised as competentto work on live cables with a professional working knowledge (practical and theoretical) of the electrical safety considerations when jointing energised cables.
Furthermore, contractors must use approved and tested insulated tools, jointing tools and electrical safety equipment to prevent workplace risk becoming workplace accident.
Insulated tools will protect workers against contact with live circuits and cables. Without them you could be risking serious injury, liability or even death.
Typical 400v low voltage cables jointed under live conditions are waveform, wavecon, PILC STA and Consac – live working is essential but not encouraged and suitable arc flash clothing should be worn when carrying out maintenance on energised substations, cables and electrical equipment. See the UK HSE HSG85 document for further information about safe working near dead or live electrical equipment.
The following series of site photographs kindly contributed by Billy Ayling, an authorised Live Cable Jointer, shows the stages of cable stripping, preparation, shrouding and branch jointing of wavecon cables. The photo’s were taken by the Jointers mate.
Cable Jointer: Billy Ayling (Self Employed – DNOÂ (SSE) Trained Live LV / 11kV Jointer
About Billy,
Billy has worked in the utility industry since leaving school in 2001 and has been a cable jointer since 2010. Professionally trained at SSE Thatcham Jointing School and authorised to fault find, repair and cable joint wavecon, consac, PILC SWA and associated services with additional skills including operating and linking on the low voltage electricity network.
Cable Jointing In The Danger ZoneÂ
With nerves of steel and the concentration powers of a chess Grandmaster a live cable jointer must maintain a steady hand and focussed mind when working on live cables.
Billy comments, “the main risk during live cable jointing is losing concentration – generally I would not speak to my Jointers mate whilst live working on cables unless something critical to the cable joint installation is required. All adjacent conductive metal work must be shrouded using rubber insulating shrouds UV stabilised suitable for outdoor and underground use in cable trenches. Only one phase should be worked on at a time.”
Typically, when working on Live LV Conductors insulating gloves should be used when working on, or in close proximity to cables – UK DNO’s such as Scottish Power Energy Networks (SPEN) according to their policy guideline Rubber Gloves For Electrical Purposesrecommend jointers wear Class 1 insulated gloves (7.5kV) to the British Standard BS EN 60903 (2003).
Hand protection is vital as is the use of dielectric boots where there is a real risk to the cable jointer of electrical shock from either low voltage or high voltages – see insulating boots for further information on suitable PPE for jointers.
An 11kV JointerÂ
Billy has ascended the voltages and is currently a high voltage cable jointer authorised to work on 11kV polymeric (XLPE) and 11kV paper (PILC PICAS) insulated cables.
1 View From The Trenches – working conditions complicate but do not prevent skilled cable jointers from live working in cramped and confined underground cable trenches. Here, the cable fault has been located and the damaged cable excavated prior to jointing. In the field, jointer training centre conditions are never replicated with an onus on the jointer to maintain high skill levels, concentration and dexterity in the face of bad weather and under pressure to restore power to our homes or businesses with minimum disruption.
2 – Mud, Mud, Glorious Mud – plodging in muddy holes with conditions favoured by hippo’s the cable jointer must maintain complete awareness of the electrical safety precautions and considerations required for safe live working on LV cables. The centre of the wave is accurately located on the cable – this must be done to ensure correct cable stripping and separation of the copper neutral earth wires. Also, the waveform cable is marked up for where to strip the cable prior to jointing.
3 Get Stripped! – the cables are carefully prepared using jointers tools to remove the cable sheath and expose the cable and conductors to allow the cable joint to be installed. Here, the jointer has relied on insulated cable knives to safely remove the waveform cable sheath. Correct cable preparation is essential to avoid malfunction of the cable joint post-energisation.
4 Shocking Risks – the cable jointer uses insulated tools to work on the live cables to avoid potential electrocution when live working. The jointer uses insulated cable wedges to space cores for testing (hence the lamps) and provide space for the ‘w’ breech connectors. Insulated tool kits would usually include insulated pliers, cable cutters, sockets, spanners, wrenches and screwdrivers – contact us for further information.
5 Shrouded For Safety – the jointer uses Boddingtons rubber insulating shrouding to protect against live voltages up to 1000V when underground cable jointing. Insulated clamps hold the protective shrouding in position covering the live cables so the LV cable joint can be positioned and installed.
6 Insulated Tools – the jointer has used an insulated ratchet tool to tighten the shear off bolts on the mechanical shearbolt connectors. Insulated wedges to were used to separate the cable cores and an insulated knife used to strip insulation from the cores. Cable joint is manufactured by TE Connectivity and approved by SSE – this is a completed wavecon to wavecon 95sqmm 3 core mains breech joint.
7 Hometime – the branch joint is completed with the shell encapsulating the jointing resin and ready for trench backfilling. Live cable jointing should only ever be carried out by competent and certified Jointers using the correct jointing, insulated tools and electrical safety equipment.
SSE Scottish & Southern Energy– a live low voltage 185sqmm wavecon straight joint prior to filling the joint shell with cable joint resin.
Cable Joints – The Birdcage.Here, the cable jointer ensures the binders are cut off before cable joint is ‘complete’ making a cage around the crutch rather than just split apart as per the previous photo. Although forming part of the SSE jointers trade test at the Jointing School this is rarely used in the field. The neutral earths are formed as a “bird-cage” type arrangement at the cable crotch using wire binders. Image:Lee Richards (LV 33kV Competent Cable Jointer).
Insulated Tools & IEC 60900
IEC 60900 Symbol
Quality insulated tools should be tested to IEC 60900 – this standard controls hand tools for live working up to 1000 V a.c. and 1500 V d.c.
Look for the official 1000V symbol, this will ensure the tools protect workers against accidental or incidental contact with electricity voltages up to 1000V.
T&D also distribute the complete range of Class 0, 1, 2, 3 and 4 ranges of insulating matting to provide protection to utility workers, substation workers and cable jointers working on low, medium and high voltage cables and power systems.
Thorne & Derrick
Specialist Electrical Distributor
LVÂ ♦ MVÂ ♦ HV
T&D distribute the most extensive range of LV, MV & HV Cable Joints & Terminations for repairing, jointing and connecting 11kV/33kV cables in underground cable trenches or substations, switchgear and transformers – the extensive range of cold shrink and heat shrink joints and terminations are supported by a complete range of cable jointing tools to enable the removal of sheath, insulation and screen from LV, MV & HV cables.
Customised & Standard Insulated Tool Sets – Tested To IEC 60900: 2012.
Cable Jointing Tools for Low, Medium & High Voltage Jointers – Boddingtons Electrical
132kV Ericsson Transition Joint – 3 Core Cable Joint XLPE To Oil Filled Cable
Uploaded by Chris Dodds T&D
Contractor: Energi Cable Services
Contributed By:Â Dan Chessher
Energi Cable Engineering
Energi Cable Engineering have developed a strong and close relationship with two of the leading manufacturers of high voltage cable systems: NKT of Denmark and LS Cable & Systems of South Korea. Through these partnerships Energi Cable Engineering can design, specify, procure and deliver high voltage cable systems up to 500kV to provide solutions for XLPE, Oil Filled and Gas filled cable systems.
Energi Cable Engineering provides a complete range of cable accessories for XLPE, oil filled and gas filled cable systems. The highly experienced team of cable design engineers ensures that a fully engineered solution is provided to meet customer requirements, including all the ancillary equipment.
Switchgear Type:Air Insulated 11kV High Voltage Switchgear Siemens NXAIR
Credit: Peter McKenna (Operations Manager) & John Bower (Manager & 33kV SAP)
All Images Courtesy:Â ISS Industrial Switchgear Services Ltd
11kV Terminations
ISS were contracted to carry out the Design, Build & Installation of 10 new low voltage switchboards and a 24 panel 11kV high voltage switchboard, cabling and terminations installation.
The high voltage cables were connected using 11kV cable terminations into Siemens NX air insulated switchgear – the armoured 3 core 11kV cables with polymeric insulation (XLPE) were glanded using top-hat type cable glands and terminated into the switchgear using 11kV indoor heat shrink cable terminations.
Careful selection of the correct cable lugs are required – 11kV lugs tested to relevant international standards should be used with extended barrels for excellent connection and circuit conductivity.
The 11kV cable containment design and erection shown in the image below was carried out by ISS – 11kV cable spacings and cable cleat ratings were calculated and correctly specified by ISS to protect and restrain the high voltage cable circuits in the event of a short circuit.
ISS design engineers created and installed a bespoke A frame arrangement located on the ground floor to support the bottom cable entry of 11kV cables into the switchgear units located on the first floor.
A total of 22 new 11kV/415V high voltage transformers manufactured by Wilson Power Solutions were installed by ISS and all associated new low voltage (LV) power supply cables.
The LV cables were BS5467 type single core XLPE insulated power cables with aluminium wire armour and stranded copper conductors, 300-500sqmm.
High Voltage Cable Chamber – showing 11kV high voltage switchgear, terminations, cable cleats and containment
HV Switchgear – Siemens NXAIR Air Insulated Switchgear
Siemens NXAIR circuit-breaker switchgear is used in medium/high voltage transformer and switching substations up to 24kVÂ for primary electricity distribution.
All HV switchgear from the Siemens NXAIR air-insulated range are approved with internal arc classification IAC A FLR, loss of service continuity category LSC 2B and partition class PM.
Some features of the high voltage switchgear include:
1 As an electrical insulating medium – air is always available 2Type-tested HV switchgear according to IEC 62271-200 or VDE 0671-200 3 Use of standardised block-type current transformers 4 450,000+ air-insulated switchgear panels of Siemens in operation worldwide 5 Uses maintenance-free high voltage vacuum circuit-breakers or contactors 6 Testing of the vacuum circuit-breaker and make-proof earthing switch in switchgear panel 7Pressure-resistant partitions 8Flexibility regarding the low-voltage equipment (removable compartment, plug-in wires) 9Quality assurance in accordance with DIN EN ISO 9001
11kV 24kV Air Insulated High Voltage Switchgear – Siemens NXAIR
Industrial Switchgear Services
ISS Ltd are a HV/LV Power Engineering company operating nationwide, undertaking Turnkey Electrical Distribution Projects and Site Service activities including installation, commissioning, pre-commissioning, final commissioning, HV/LV switching, maintenance, repairs, refurbishment of HV/LV AC & DC Switchgear, power transformers, SCADA systems, control panels, HV/LV cabling, cable terminations and associated ancillary equipment.
ISS Ltd manufacture low and high voltage switchgear, protection cubicles, LV generator changeover panels, marshalling cabinets and bespoke protection and control equipment.
HV Switchgear & Cable Terminations 11kV 33kV
LV Switchgear & Cable Gland Terminations
Transformer & Rectifiers
Substation Construction 11kV 33kV
Protection & Control
22kV Rail Cable Installation
“ISS have completed further 22kV high voltage protection upgrades, upgrading 5 circuits at this particular site, all communicating back to a new 22kV switchboard installed a few miles away on the cable network. ISS removed the existing MBCI Translay, MCRI Overcurrent, MRTP Pilot Wire Supervision, KCEG Directional Overcurrent/Earth Fault MVTW Destabilising Relays. These have been replaced with a new Line Differential ABB RED615 Relay and Modem and Agile P14D Back Up Protection Relays.”
“New multicore cables have been installed from the switchboard back to the Marshalling cubicle, with ISS successfully proving the SCADA signals back to the RTU and control room. ISS commissioned the circuit into service, carrying out On Load Line Diff stability checks. A great team effort, from the design and manufacture of the protection fascia’s from our Manchester HQ, to the installation and commissioning of the circuits for a London based rail network. Great collaborative interfacing and planning between everyone involved to upgrade 22kV cable circuits on an operational railway” – Peter McKenna (ISS Operations Manager).Â
22kV Rail Cable Installation
More ISS project information:
Commissioning 25kV AIS Switchgear On Containerised Rail Traction HV High Voltage Substations
Flood Defence & Replacement Of Low & High Voltage
11kV Switchgear & Cables
The disaster recovery project involved the replacement of water damaged high voltage electrical equipment and cables – this included replacement of primary high voltage switchgear, cable terminations, associated power transformers and distribution cables.
Watch, listen and learn more about the project:
Should you require any further information about 11kV Cable Termination, Switchgear, Substation & High Voltage services provided by ISSÂ please call 0161 344 1117.
Application: Using Copper Earthing Tapes, Rods & CADWELD To Earth 33kV Substation, Switchgear & Transformer
Contractor: Power Jointing Services Ltd (Hampshire UK)Â Â
Image Courtesy: Robert Coleman LV HV Cable Jointer at Power Jointing Services Ltd
Featured Product: Earthing & Lightning Protection MV HV
Copper Earthing Tapes & Earth Rods
33kV substation earthing is provided around the transformer bund and new building structure using copper earthing tapes, electrode rods and exothermic welding (CADWELDing) of the earth rods to tape – 50mm x 4mm earth tapes are installed as a ring and cross earthing design with 40mm x 4mm copper tape braised for additional stairs and walkway earthing.
The 33kV switchgear housing within the high voltage substation is earthed and bonded to a new transformer ring and Neutral Earth Resistors (NER). The copper tapes and earthing cables are shown connected to the 10 way earth bar. To achieve the required earth resistivity reading 3 x 1.2 metre length coupled copper earth rods were driven into the ground.
Driven earth rods are used to exploit lower resistivity ground conditions where present to reduce the earth potential rise (EPR) on substation earthing and lightning protection projects from 11kV/33kV up to 400kV.
Substation Earthing
Earthing of low, medium and high voltage electrical networks is critical to ensure safe and correct operation preventing and minimising against the consequences of a direct lightning strike to equipment and buswork within substations. UK DNO’s publish primary and secondary substation earthing designs for the application of earthing systems to HV and LV underground cables and overhead line networks, typically operating at 33kV, 20kV, 11kV, 6.6kV, 3kV and 2kV.
Similarly, the National Grid publish an Earthing Technical Specification for the lightning protection of transmission and distribution systems located in the busbar protection zone of the electricity grid operating at nominal voltages of 400kV, 275kV 132kV and 66kV. The general requirements of the substation earthing systems are compliance with technical standard EA TS 41-24 and British Standards BS EN 50522 and BS7430.
Energy Network Association (ENA) Technical Standard (TS) 41-24 (Substation Earthing) – the standard provides guidelines for the design, installation, testing and maintenance of main earthing systems in substations
BS EN 50522:2010 – the British Standard provides guidance for Earthing of Power Installations Exceeding 1kV a.c
BS 7430:2011+A1:2015 – the British Standard is a code of practice for Protective Earthing of Electrical Installations
Copper Earth Tape – the earthing tape 40mm x 4mm shown bonding to the existing medium/high voltage substation earth bar
Copper Earth Tape Dropper – 50mm x 4mm earth tape is shown earthing switch 1 of 3 on the 33kV distribution board
Earth Tapes – the 50mm x 4mm copper tapes are routed back to the rebar earths on the earth bar
Transformer Earthing – using 40mm x 4mm copper earthing tape on the 33kV high voltage transformer
Power Jointing Services Ltd
Power Jointing Services Ltd established in 2007 specialising in 33kV-400V electrical network construction, establishing industrial and commercial supplies, installing residential service connections and street lighting connections. Also:High voltage service alterations, cable fault finding and replacement of assets including transformers, low voltage distribution boards and link boxes.
Copper Earthing Tapes & Products
T&D provide competitive prices and fast delivery from stock for Earthing & Lightning Protection products including copper tapes, rods, electrodes, earth bars and ancillary items for low, medium and high voltage substations.
T&D distribute the most extensive range of LV, MV & HV Cable Jointing, Terminating, Installation & Cable Pulling Equipment – we service UK and international clients working on underground cables, overhead lines, substations and electrical construction at LV, 11kV, 33kV and EHV transmission and distribution voltages.
by Chris Dodds T&D - estimated reading time 6 minutes
Earthing Substations
Thorne & Derrick International are distributors for the ABB Furse and AN Wallis range of Earthing & Lightning Protection Systems – this includes earth rods, earth bars, earth tapes and a full supporting range of accessories to comprise the complete earthing system for electricity transmission and distribution systems.
The copper products are used typically to provide electricity substation earthing to medium/high voltage grids containing electrical infrastructure, cables, switchgear and transformers. Furthermore, it is usual for all exposed and normally un-energised metalwork inside the substation perimeter, including doors, staircases, ventilation ducts, cable supports etc to be be bonded to the main earth grid to avoid any potential differences between different items of metalwork.
Guidelines and policies vary according to the Distribution Network Operator – specialist contractors using modern earthing techniques compliant with relevant British and international standards, including BS 7430:2011+A1:2015 Code of Practice For Earthing and IEEE80-2000 Guide for Safety in AC Substation Grounding should be employed to calculate specific substation earthing requirements.
A final design of the earthing system can only be undertaken when sufficient knowledge is available of the proposed physical and electrical requirements of the substation – as an absolute minimum the earthing system desginer must have knowledge of:
value of fault current and supply arrangements (overhead and/or underground cable)
fault duration (or protection settings)
soil resistivity
substation dimensions
The specification for fixed earthing systems within EHV, HV, HV/MV and LV substations also applied to terminal towers adjacent to substations and cable sealing end compounds, pole mounted transformer or air-break switch disconnector installations and pole mounted reclosers with ground level control.
âž¡ View our complete range of Substation Earthing products including substation and overhead line earth clamps, telescopic sticks and portable earthing kits – see also Exothermic Welding.
Full range of bare copper, printed and covered earth tapes are available
Copper Earthing Products
Example – Substation Earthing 11kV. Image:Â SPE Electrical Ltd
For MV & HV Substations
Earthing products and systems can be supplied by T&D for all substation voltages:
MV Medium Voltage 11kV 33kV
High Voltage 66kV 132kV
Extra High Voltage EHV 275kV 400kVÂ
T&D provide expert technical support, competitive prices and delivery from stock for substation earthing projects – all earthing products are available to meet the design criteria and construction specification of the earthing systems for substations and equipment for 33kV and 132kV substations.
This include copper earth tapes with typical dimensions 32mm x 4, 40mm x 6mm, 50mm x 4mm and 50mm x 6mm.
With respect to high voltage earthing applications in the power utility sector the following items would normally be earthed or bonded to the main earth grid:
Overhead line termination structures including towers, gantries and earthed wood pole structures adjacent to the substation
Power cable sheaths and armours
Transformer and reactor banks, cooler and radiators, tap changers, earthing resistors, earthing reactors, high voltage transformer neutral connections
Metal clad switchgear assemblies and cases, isolators and earth switch bases
Metal gantries and structures and metalwork mounted on wood structures
Metallic structures including steel frames (bonded at each corner) rebars and piles
Panels, cubicles, kiosks, LV AC equipment, lighting and security masts
It is usual for critical items such as medium/high voltage transformer tanks and terminal towers to have duplicate connections to the main earth grid.
11kV Substations
Pictured above is a diagram showing the typical layout of a high voltage GRP electricity substation distributing 11kV power – an outer ring of 70sqmm copper earthing conductor plus 4 earth rods of standard depth are shown with a 10 metre tail in the HV cable trench accompanied by a layout for the concrete rebar. Here, the HV substation is contained within a GRP enclosure with potential touch and step voltage risks.
Earth tapes are available stamped with the UK DNO ownership details to discourage copper metal theft – earth tapes printed “National Grid Property” are also available.
Full range of copperbond earth rods, couplings and driving studs are available for grid and primary substation earthing depending upon the calculated fault level.
E – Earth electrode (copper earth rod)
UE – Earth potential rise (EPR)
S1, S2, S3 – Potential grading earth electrodes connected to the earth electrode E
US Touch – Source voltage for touching (Touch Voltage)
US Step – Source voltage for stepping (Step Voltage)
Touch Voltage
The potential on the surface of the soil near a copper earth rod during the time that fault current flows. If a person were to touch a rod (or any exposed metalwork connected to it), then the potential difference experienced between hands and feet is termed the touch voltage. Touch voltages are calculated assuming that the feet of the person are 1 metre away from the metalwork being touched. Touch voltages are normally reduced by using potential grading electrodes.
Step Voltage
Potential differences are established on the surface of the soil whilst fault current is flowing. Step voltage in a particular direction is defined as the potential difference between two points a metre part. Step potentials can be reduced by using potential grading copper electrodes or installation electrodes, such as copper earth rods, at a greater soil depth.
Transfer Potential
A potential rise of an earthing system caused by a current flowing to earth, transferred by means of a connected conductor (eg metallic sheath or pipe), which enters a substation area, with little or no potential rise relative to reference earth, and which is not connected to earth in that area. This results in a potential difference occurring between the conductor and its surroundings at the remote position.
Electrical Safety – Maintaining & Repair Of Earthing Systems
Substation earthing systems are the victim of operational and intentional damage – copper theft is rife and earthing maintenance work is often identified during routine site checks and inspection. Earth faults can be weekly occurrences on primary substations supplying extended high voltage rural overhead line networks. During these maintenance tasks there is serious risk of injury or even fatal electric shock when working on depleted or damaged earthing systems – specialist electrical safety equipment including insulated sticks, poles or rods, portable earth shorting leads, earthing clamps (substation or line-end), insulating footwear (shoes or boots) and insulating gloves depending on the voltage class of the substation earthing system.
T&D distribute a full range CATU Electrical Safety equipment including Arc Flash Kits, Insulating Boots & Safety Shoes and Voltage Detectors
High Voltage Substation Earthing 275kV
All images courtesy: Ian Forster (EHV Site Manager)
More Substation Earthing Applications
Fig.1 3 x Copper earth cables connected to main aluminium substation earth tape Fig.2 Copper earth tape connected to main aluminium earth tape Fig.3 Aluminium to aluminium tape connection
View the Earthing Products below for further information and technical details.