Nexans AFN Slip-On Termination | XLPE Indoor & Outdoor Single Core 12kV 24kV 36kV MV Cables
December 5th, 2018
Indoor & Outdoor Cable Termination | Cold Shrink | Single Core | 11kV 33kV 42kV
Cable Terminations
Nexans AFN are single core cold shrink cable terminations for use indoor/outdoor and specified to terminate medium/high voltage cables in the following voltage classes:
- 6/10 (12) kV
- 6.35/11 (12) kV
- 8.7/15 (17.5) kV
- 12/20 (24) kV
- 12.7/22 (24) kV
- 18/30 (36) kV
- 20.8/36 (42) kV
Slip-on terminations are cold applied terminations require no “hot-working” for safe use in potentially explosive atmospheres and hazardous area locations – the cable terminations are designed for use with polymeric insulated cables (XLPE & EPR). To enable the fault repair, extension, splicing and jointing of existing LV MV HV power cables up to 33kV we also stock a complete range of cold shrink joints.

Slip On Outdoor Cable Terminations 11kV 33kV 42kV Euromold AFN
Outdoor slip-on cold shrink cable termination kit list comprising:
- Cable lug (not included in the standard kit) – crimp lugs or shearbolt lugs are suitable
- Water sealing silicone sleeve
- Silicone housing with sheds and integrated conductive silicone rubber insert providing stress relief for the cable
- Water sealing mastic
- Earthing clamp
- Earthing lug (not included in the standard kit)
Nexans AFN COLD SHRINK TERMINATION SPECIFICATION
The following tables enable the selection of cable terminations using Cold Shrinkable technology manufactured by Nexans:
| Euromold Termination Slip-on Cold Shrink |
Voltage Um (kV) |
Conductor Sizes (sqmm) | |
| min | max | ||
| Nexans AFN 10 | 12kV | 25sqmm | 1200sqmm |
| Nexans AFN 20 | 24kV | 35sqmm | 1200sqmm |
| Nexans AFN 30 | 36kV | 50sqmm | 1000sqmm |
| Nexans AFN 36 | 42kV | 70sqmm | 1000sqmm |

PADS Approved by Network Rail | 25kV Switchgear Terminations
Nexans AFN36-6 42kV single core MV cable terminations are Network Rail PADS Approved – the cold-applied Slip-on cable termination is approved for use with Siemens ASG25 – 25kV air insulated switchgear for AC traction power supply systems.
Nexans AFN selection table
For Indoor MV HV Cable Terminations
Select the Euromold part number corresponding to both the system voltage and the cable insulation diameter in mm.
The complete kit comprises of 3 termination housings, installation instructions, special lubricant, wiper, adhesive tape and field control mastic.
| Voltage Um (kV) |
Conductor Sizes (sqmm) |
Diameter Over Core Insulation (mm) |
Number Of Sheds | L (mm) (max) |
Dia. D (mm) | Creepage Distance (mm) |
Nexans Ordering Part Number |
||
| min | max | min | max | ||||||
| 12kV | 25 | 95 | 12.7 | 21.0 | 3 | 210 | 90 | 369 | 3 x AFN 10-1 |
| 120 | 240 | 19.0 | 28.5 | 3 | 210 | 96 | 365 | 3 x AFN 10-2 | |
| 300 | 500 | 27.0 | 37.0 | 3 | 210 | 105 | 360 | 3 x AFN 10-3 | |
| 630 | 800 | 34.0 | 46.0 | 4 | 240 | 118 | 462 | 3 x AFN 20-4 | |
| 1000 | 39.0 | 50.0 | 7 | 405 | 127 | 755 | 3 x AFN 36-5 | ||
| 1200 | 46.0 | 58.0 | 7 | 405 | 127 | 755 | 3 x AFN 36-6 | ||
| 24kV | 35 | 70 | 18.0 | 23.5 | 4 | 240 | 100 | 480 | 3 x AFN 20-1 |
| 95 | 240 | 22.5 | 33.0 | 4 | 240 | 112 | 499 | 3 x AFN 20-2 | |
| 300 | 500 | 31.0 | 41.0 | 4 | 240 | 118 | 462 | 3 x AFN 20-3 | |
| 400 | 630 | 34.0 | 46.0 | 4 | 240 | 118 | 462 | 3 x AFN 20-4 | |
| 630 | 800 | 39.0 | 50.0 | 7 | 405 | 127 | 755 | 3 x AFN 36-5 | |
| 1000 | 1200 | 46.0 | 58.0 | 7 | 405 | 127 | 755 | 3 x AFN 36-6 | |
| 36kV | 50 | 70 | 23.5 | 29.0 | 6 | 300 | 115 | 695 | 3 x AFN 30-1 |
| 95 | 240 | 27.0 | 38.0 | 6 | 300 | 115 | 694 | 3 x AFN 30-2 | |
| 240 | 400 | 32.0 | 43.0 | 6 | 300 | 127 | 718 | 3 x AFN 30-3 | |
| 400 | 630 | 39.0 | 50.0 | 7 | 405 | 127 | 755 | 3 x AFN 36-5 | |
| 630 | 1000 | 46.0 | 58.0 | 7 | 405 | 127 | 755 | 3 x AFN 36-6 | |
| 42kV | 70 | 120 | 28.0 | 32.0 | 7 | 405 | 127 | 755 | 3 x AFN 36-3 |
| 150 | 300 | 31.5 | 41.0 | 7 | 405 | 127 | 755 | 3 x AFN 36-4 | |
| 400 | 630 | 39.0 | 50.0 | 7 | 405 | 127 | 755 | 3 x AFN 36-5 | |
| 630 | 1000 | 46.0 | 58.0 | 7 | 405 | 127 | 755 | 3 x AFN 36-6 | |
| For use in heavy polluted areas (cable terminations with an increased creepage length) | |||||||||
| 42kV | 70 | 120 | 28.0 | 32.0 | 11 | 535 | 127 | 1079 | 3 x AFNP 36-3 |
| 150 | 300 | 31.5 | 41.0 | 11 | 535 | 127 | 1079 | 3 x AFNP 36-4 | |
| 400 | 630 | 39.0 | 50.0 | 11 | 535 | 127 | 1079 | 3 x AFNP 36-5 | |
| 630 | 1000 | 46.0 | 58.0 | 11 | 535 | 127 | 1079 | 3 x AFNP 36-6 | |
Nexans
Thorne & Derrick distribute the complete range of medium/high voltage electrical equipment manufactured by Nexans – this includes Euromold bushings for use with oil fluid or gas insulated switchgear or transformers and associated screened separable connectors according to both IEC (Euromold) and IEEE (Elastimold) for the termination, connect+disconnect of MV-HV cables onto power distribution systems. To protect power systems against high voltage surges resulting from lightning or switching a complete range of surge arresters are available to be used with Euromold connectors in 11kV/12kV, 24kV and 33kV/36kV voltage classes.

Key Product Categories: Duct Seals | Cable Cleats | Cable Glands | Electrical Safety | Arc Flash Protection | Cable Jointing Tools | Cable Pulling | Earthing | Feeder Pillars | Cable Joints LV | Joints & Terminations MV HV
➡ Read: Thorne & Derrick Announce Distribution Agreement & Contract With Nexans

Nexans AIN Slip-On Termination | XLPE Indoor Single Core 12kV 24kV 36kV MV Cables
December 5th, 2018
Indoor Cable Termination | Cold Shrink | Single Core | 11kV 33kV 42kV
Cable Terminations
Nexans AIN are single core cold shrink slip-on cable terminations for use indoor and specified to terminate and connect medium/high voltage cables in the following voltage classes:
- 6/10 (12) kV
- 6.35/11 (12) kV
- 8.7/15 (17.5) kV
- 12/20 (24) kV
- 12.7/22 (24) kV
- 18/30 (36) kV
- 20.8/36 (42) kV
Slip-on terminations are cold applied terminations require no “hot-working” for safe use in potentially explosive atmospheres and hazardous area locations – the cable terminations are designed for use with polymeric insulated cables (XLPE & EPR). To enable the fault repair, extension, splicing and jointing of existing LV MV HV power cables up to 33kV we also stock a complete range of cold shrink joints.

Slip On Indoor Cable Terminations 11kV 33kV 42kV Euromold AIN – Design
Indoor slip-on cable termination kit list comprising:
- Cable lug (not included in the standard kit) – crimp lugs or shearbolt lugs are suitable
- High flexibility silicone rubber housing, allowing larger tolerances on cable insulation diameters, with integrated conductive rubber insert, providing stress relief
- Earthing lug (not included in the standard kit)
Nexans AIN COLD SHRINK TERMINATION SPECIFICATION
The following tables enable the selection of cable terminations using Cold Shrinkable technology manufactured by Nexans:
| Euromold Termination Slip On Cold Shrink |
Voltage Um (kV) |
Conductor Sizes (sqmm) | |
| min | max | ||
| Nexans AIN 10 | 12kV | 25sqmm | 1200sqmm |
| Nexans AIN 20 | 24kV | 35sqmm | 1200sqmm |
| Nexans AIN 30 | 36kV | 50sqmm | 1000sqmm |
| Nexans AIN 36 | 42kV | 150sqmm | 1000sqmm |
EUROMOLD AIN selection table
For Indoor MV HV Cable Terminations
Select the Euromold part number corresponding to both the system voltage and the cable insulation diameter in mm – the complete kit comprises of 3 termination housings, installation instructions, special lubricant, wiper, adhesive tape and field control mastic.
| Voltage Um (kV) |
Conductor Sizes (sqmm) |
Diameter Over Core Insulation (mm) |
Number Of Sheds | L (mm) |
Dia. D (mm) | Nexans AIN Ordering Part Number |
||
| min | max | min | max | |||||
| 12kV | 25sqmm | 95sqmm | 12.7 | 21.0 | 2 | 150 | 37 | 3 x AIN 10-1 |
| 120sqmm | 240sqmm | 19.0 | 28.5 | 2 | 150 | 43 | 3 x AIN 10-2 | |
| 300sqmm | 500sqmm | 27.0 | 37.0 | 2 | 150 | 60 | 3 x AIN 10-3 | |
| 630sqmm | 800sqmm | 34.0 | 46.0 | 3 | 225 | 68 | 3 x AIN 36-4 | |
| 1000sqmm | 39.0 | 50.0 | 7 | 405 | 98 | 3 x AIN 36-5 | ||
| 1200sqmm | 46.0 | 58.0 | 7 | 405 | 98 | 3 x AIN 36-6 | ||
| 24kV | 35sqmm | 70sqmm | 18.0 | 23.5 | 3 | 225 | 47 | 3 x AIN 20-1 |
| 95sqmm | 240sqmm | 22.5 | 33.0 | 3 | 225 | 56 | 3 x AIN 20-2 | |
| 300sqmm | 500sqmm | 31.0 | 41.0 | 3 | 225 | 68 | 3 x AIN 20-3 | |
| 400sqmm | 630sqmm | 34.0 | 46.0 | 3 | 225 | 68 | 3 x AIN 20-4 | |
| 630sqmm | 800sqmm | 39.0 | 50.0 | 7 | 405 | 98 | 3 x AIN 36-5 | |
| 1000sqmm | 1200sqmm | 46.0 | 58.0 | 7 | 405 | 98 | 3 x AIN 36-6 | |
| 36kV | 50sqmm | 70sqmm | 23.5 | 29.0 | 6 | 300 | 74 | 3 x AIN 30-1 |
| 95sqmm | 240sqmm | 27.0 | 38.0 | 6 | 300 | 74 | 3 x AIN 30-2 | |
| 240sqmm | 400sqmm | 32.0 | 43.0 | 6 | 300 | 81 | 3 x AIN 30-3 | |
| 400sqmm | 630sqmm | 39.0 | 50.0 | 7 | 405 | 98 | 3 x AIN 36-5 | |
| 630sqmm | 1000sqmm | 46.0 | 58.0 | 7 | 405 | 98 | 3 x AIN 36-6 | |
| 42kV | 150sqmm | 300sqmm | 31.5 | 41.0 | 7 | 405 | 98 | 3 x AIN 36-4 |
| 400sqmm | 630sqmm | 39.0 | 50.0 | 7 | 405 | 98 | 3 x AIN 36-5 | |
| 630sqmm | 1000sqmm | 46.0 | 58.0 | 7 | 405 | 98 | 3 x AIN 36-6 | |
Nexans
Thorne & Derrick distribute the complete range of medium/high voltage electrical equipment manufactured by Nexans – this includes Euromold bushings for use with oil fluid or gas insulated switchgear or transformers and associated screened separable connectors according to both IEC (Euromold) and IEEE (Elastimold) for the termination, connect+disconnect of MV-HV cables onto power distribution systems. To protect power systems against high voltage surges resulting from lightning or switching a complete range of surge arresters are available to be used with Euromold connectors in 11kV/12kV, 24kV and 33kV/36kV voltage classes.

Key Product Categories: Duct Seals | Cable Cleats | Cable Glands | Electrical Safety | Arc Flash Protection | Cable Jointing Tools | Cable Pulling | Earthing | Feeder Pillars | Cable Joints LV | Joints & Terminations MV HV
➡ Read: Thorne & Derrick Announce Distribution Agreement & Contract With Nexans

Nexans OTK Cold Shrink Termination | XLPE Outdoor Single Core 12kV 24kV MV Cables
December 5th, 2018
Cable Termination | Cold Shrink | Single Core | 11kV 24kV
Cable Terminations
Nexans OTK are single core cold shrink cable terminations for use indoor and specified to terminate and connect medium/high voltage cables in the following voltage classes:
- 6/10 (12) kV
- 6.35/11 (12) kV
- 8.7/15 (17.5) kV
- 12/20 (24) kV
- 12.7/22 (24) kV
Cold Shrinkable terminations require no “hot-working” for safe use in potentially explosive atmospheres and hazardous area locations – the cable terminations are designed for use with polymeric insulated cables (XLPE & EPR). To enable the fault repair, extension, splicing and jointing of existing LV MV HV power cables up to 33kV we also stock a complete range of cold shrink joints.

Cold Shrink Outdoor Cable Terminations 11kV 24kV Euromold OTK – Design
Outdoor cold shrink cable termination comprising:
- Cable lug (not included in the standard kit) – both crimp cable lugs and shearbolt lugs are suitable
- Water sealing mastic
- Sheds which be installed upwards or down
- Silicone tube with sheds
- Silicone cold shrink tube
- Stress control mastic
- Conductive EPDM ring
Nexans OTK COLD SHRINK TERMINATION SPECIFICATION
The following tables enable the selection of cable terminations using Cold Shrinkable technology manufactured by Nexans:
| Nexans Cold Shrink Cable Terminations | Voltage Um (kV) |
Creepage Distance A-B (mm) |
Strike Distance L (mm) |
Number Of Sheds |
Fig. No. |
Diameter Over Core Insulation (mm) |
Conductor Sizes (sqmm) | ||
| min | max | min | max | ||||||
| OTK 212 | 11kV 12kV | 420 | 300mm | 3 | 1 | 14 | 33 | 50sqmm | 400sqmm |
| OTK 312 | 11kV 12kV | 890 | 650mm | 6 | 2 | 30 | 50 | 400sqmm | 1000sqmm |
| OTK 224 | 20kV 24kV | 600 | 400mm | 5 | 3 | 14 | 33 | 25sqmm | 240sqmm |
| OTK 324 | 20kV 24kV | 890 | 650mm | 6 | 4 | 30 | 50 | 300sqmm | 800sqmm |
Nexans OTK selection table
For outdoor MV HV Cable Terminations
Select the Nexans part number corresponding to both the system voltage and the cable insulation diameter in mm.

Kit Contents For Euromold OTK Terminations
| Euromold OTK Cold Shrink Cable Terminations | Voltage Um (kV) |
Diameter Over Core Insulation (mm) |
Conductor Sizes (sqmm) | ||
| min | max | min | max | ||
| 3 x OTK 212 | 11kV 12kV | 14 | 33 | 50sqmm | 400sqmm |
| 3 x OITK 312 | 11kV 12kV | 30 | 50 | 400sqmm | 1000sqmm |
| 3 x OTK 224 | 11kV 24kV | 14 | 33 | 25sqmm | 240sqmm |
| 3 x OTK 324 | 11kV 24kV | 30 | 50 | 300sqmm | 800sqmm |

All commercialised European standard cable lugs can be used. Cable lugs should be within the dimensions specified (not applicable for Nexans OTK 312 and OTK 324).
Nexans
Thorne & Derrick distribute the complete range of medium/high voltage electrical equipment manufactured by Nexans – this includes Euromold bushings for use with oil fluid or gas insulated switchgear or transformers and associated screened separable connectors according to both IEC (Euromold) and IEEE (Elastimold) for the termination, connect+disconnect of MV-HV cables onto power distribution systems. To protect power systems against high voltage surges resulting from lightning or switching a complete range of surge arresters are available to be used with Euromold connectors in 11kV/12kV, 24kV and 33kV/36kV voltage classes.

Key Product Categories: Duct Seals | Cable Cleats | Cable Glands | Electrical Safety | Arc Flash Protection | Cable Jointing Tools | Cable Pulling | Earthing | Feeder Pillars | Cable Joints LV | Joints & Terminations MV HV
➡ Read: Thorne & Derrick Announce Distribution Agreement & Contract With Nexans

Nexans ITK Cold Shrink Termination | XLPE Indoor Single Core 12kV 24kV MV Cables
December 4th, 2018
Heat Shrink | Cold Shrink | Slip-on | Cable Terminations
Stocked by Thorne & Derrick UK & Export Sales | Nexans ITK224
Cable Terminations
Nexans ITK are single core cold shrink cable terminations for use indoor and specified to terminate and connect medium/high voltage cables in the following voltage classes:
- 6/10 (12) kV
- 6.35/11 (12) kV
- 8.7/15 (17.5) kV
- 12/20 (24) kV
- 12.7/22 (24) kV
Cold Shrinkable terminations require no “hot-working” for safe use in potentially explosive atmospheres and hazardous area locations – the cable terminations are designed for use with polymeric insulated cables (XLPE & EPR). To enable the fault repair, extension, splicing and jointing of existing LV MV HV power cables up to 33kV we also stock a complete range of cold shrink joints.

Cold Shrink Indoor Cable Terminations 11kV 24kV Nexans ITK – Design
Indoor cold shrink cable termination kit list comprising:
- Cable lug (not included in the standard kit) – both crimp cable lugs and shearbolt lugs are suitable
- Water sealing mastic
- Silicone cold shrink tube
- Stress control mastic
- Conductive EPDM ring
Nexans ITK COLD SHRINK TERMINATION SPECIFICATION
The following tables enable the selection of cable terminations using Cold Shrinkable technology manufactured by Nexans:
| Cable Termination Cold Shrink |
Voltage Um (kV) |
Strike Distance L (mm) |
Diameter Over Core Insulation (mm) |
Conductor Sizes (sqmm) | ||
| min | max | min | max | |||
| Nexans ITK 212 | 11kV / 12kV | 260mm | 14 | 33 | 50sqmm | 400sqmm |
| Nexans ITK 312 | 11kV / 12kV | 300mm | 30 | 50 | 400sqmm | 1000sqmm |
| Nexans ITK 224 | 20kV / 24kV | 260mm | 14 | 33 | 25sqmm | 240sqmm |
| Nexans ITK 324 | 20kV / 24kV | 300mm | 30 | 50 | 300sqmm | 800sqmm |
Nexans ITK selection table
For Indoor MV HV Cable Terminations
Select the Nexans part number corresponding to both the system voltage and the cable insulation diameter in mm.

Kit Contents For Nexans ITK Terminations
| Nexans ITK Cold Shrink Cable Termination | Voltage Um (kV) |
Diameter Over Core Insulation (mm) |
Conductor Sizes (sqmm) | ||
| min | max | min | max | ||
| 3 x Nexans ITK 212 | 11kV 12kV | 14 | 33 | 50sqmm | 400sqmm |
| 3 x Nexans ITK 312 | 11kV 12kV | 30 | 50 | 400sqmm | 1000sqmm |
| 3 x Nexans ITK 224 | 11kV 24kV | 14 | 33 | 25sqmm | 240sqmm |
| 3 x Nexans ITK 324 | 11kV 24kV | 30 | 50 | 300sqmm | 800sqmm |

All commercialised European standard cable lugs can be used. Cable lugs should be within the dimensions specified (not applicable for Nexans ITK 312 and ITK 324).
Euromold ITK cold shrink terminations covers voltages from 12kV to 24kV with a maximum conductor size of 1000sqmm. MV indoor termination suited for 11kV polymeric single core cables and will provide the necessary seal against moisture penetration and perfect electrical field control.
Nexans Euromold High Voltage Heat Shrink & Cold Shrink Cable Terminations up to 33kV.
Nexans
Thorne & Derrick distribute the complete range of medium/high voltage electrical equipment manufactured by Nexans – this includes Euromold bushings for use with oil fluid or gas insulated switchgear or transformers and associated screened separable connectors according to both IEC (Euromold) and IEEE (Elastimold) for the termination, connect+disconnect of MV-HV cables onto power distribution systems. To protect power systems against high voltage surges resulting from lightning or switching a complete range of surge arresters are available to be used with Euromold connectors in 11kV/12kV, 24kV and 33kV/36kV voltage classes.

Key Product Categories: Duct Seals | Cable Cleats | Cable Glands | Electrical Safety | Arc Flash Protection | Cable Jointing Tools | Cable Pulling | Earthing | Feeder Pillars | Cable Joints LV | Joints & Terminations MV HV
➡ Read: Thorne & Derrick Announce Distribution Agreement & Contract With Nexans

Cable Troughs & Troughing – A Network Rail Safety Alert
November 30th, 2018
-
uploaded by Chris Dodds - Thorne & Derrick Sales & Marketing Manager
TTS Green Trough is fast becoming the cable management product of choice and installation on Network Rail infrastructure and rail cable protection where versatility and speed of installation of a cable trough is paramount.
The ground level or elevated polymer cable trough management system comprising troughs and lids conforms to Network Rail NR/L2/TEL/00013 for protection and management of trackside cables including LV Low Voltage and HV High Voltage signal, telecoms and power cables up to 25kV.
In May 2014, Network Rail issued Safety Bulletin 323 which prohibited with immediate effect the manual lifting, carrying and team handling of C143 conventional concrete troughs and troughing.
In January 2015, Network Rail issued Safety Bulletin NRB 15/01 mandating a risk assessment policy for all troughing products by using the MAC tool together with the troughing elements risk chart. On 22 April 2015 ORR issued the following Notices:
Prohibition Notice PN40/22042015 prohibiting “single individual employees or contractors manually lifting or carrying 10 or more units of cable troughs or troughing weighing 40kg or more in a 12 hours period” anywhere on Network Rail Infrastructure.
Prohibition Notice PN70/22042015 prohibiting “two employees or contractors manually lifting or carrying 10 or more units of cable troughs or troughing weighing 70kg or more in a 12 hours period” anywhere on Network Rail Infrastructure.
Both of the Prohibition Notices apply immediately. Continuing the activity would be a criminal offence.
A further Improvement Notice IN/25/22042015 requires Network Rail to undertake a suitable and sufficient assessment of the risk to employees, and contractors working under their control, from manually handling rail cable troughing weighing 25kg and more. That assessment will need to identify the measures necessary to control the risks identified.
This additional work is required by 25 October 2015. Further information will be communicated when the work is complete.
Immediate Action Required
- Compliance with the requirements of the Prohibition Notices is required immediately.
- If you are about to manually handle concrete troughing products then you must have an approved, site-specific risk assessment. If you haven’t then stop, request that a risk assessment is undertaken by a competent individual and implement any resulting actions before continuing work
- All staff and contractors who specify, manage, plan, authorise and carry out manual handling activities relating to the delivery, installation, renewal or disposal of troughing materials must comply in full with the guidance of the HSE manual handling MAC assessment tool or a suitable equivalent
- If your work involves any equivalent risk with other loads that you move manually, apply the same controls, derived from risk assessment.
Cable Troughs & Troughing
Selection Table
| Concrete Trough Variants | Description | Full Weight Concrete (kg) | Full Weight Half Length Concrete (kg) | Reduced Weight Concrete (kg) | Reduced Weight Half Length Concrete (kg) | TSS Green Trough Variants | Full Weight Polymer (kg) | Full Weight Half Length Polymer (kg) |
| C/1/6 | Straight Trough | 37 | 19 | 24 | 12 | TS120S | 6 | |
| C/1/7 | Straight Trough | 49 | 25 | 32 | 16 | TS150S | 8 | |
| C/1/38 | Transition | 50 | 25 | 35 | 18 | TT150/200 | 1 | |
| C/1/8 | Straight Trough | 71 | 36 | 46 | 23 | TS200S | 14 | |
| C/1/9 | Straight Trough | 55 | 28 | 36 | 18 | TS200S | 14 | |
| C/1/31 | Trough Bend | 55 | 28 | 36 | 18 | TS430B | 12 | |
| C/1/35 | Transition | 58 | 29 | 38 | 19 | TT200/250 | 1 | |
| C/1/10 | Straight Trough | 62 | 31 | 40 | 20 | TS250S | 9 | |
| C/1/34 | Trough Tee | 60 | 30 | 39 | 20 | TS250T | 10 | |
| C/1/36 | Transition | 65 | 33 | 44 | 22 | TT200/250 | 1 | |
| C/1/33 | Transition | 66 | 33 | 43 | 22 | TT250/300 | 2 | |
| C/1/29 | Straight Trough | 70 | 35 | 46 | 23 | TS300S | 16 | |
| C/1/82 | Trough Tee | 76 | 38 | 49 | 25 | TS430T | 21 | |
| C/1/32 | Transition | 77 | 39 | 53 | 27 | TT300/150 | 2 | |
| C/1/82 | Transition | 77 | 39 | 50 | 25 | TT300/430 | 2 | |
| C/1/61 | Transition | 82 | 41 | 53 | 27 | TT430/120 | 3 | |
| C/1/80 | Trough Tee | 83 | 42 | 54 | 27 | TS300T | 13 | |
| C/1/62 | Transition | 85 | 43 | 55 | 28 | TT430/200 | 3 | |
| C/1/44 | Transition | 88 | 44 | 60 | 30 | TT300/430 | 3 | |
| C/1/63 | Transition | 88 | 44 | 57 | 29 | TT430/250 | 3 | |
| C/1/23 | Trough Tee | 89 | 45 | 64 | 32 | TS200T | 9 | |
| C/1/45 | Transition | 94 | 47 | 60 | 30 | TT200/430 | 3 | |
| C/1/43 | Straight Trough | 115 | 58 | 75 | 38 | TS430S | 15 | |
| C/1/81 | Trough Tee | 140 | 70 | 91 | 46 | TS430T | 21 |
SE MAC Tool Assessment of Concrete & Polymer Trough Products
| GREEN | The risks are low but you should further assess the manual handling activity considering the time duration, repetitiveness of task and the site environment. | |
| AMBER | You should examine and assess the planned manual handling activities closely giving full consideration to alternative mechanical means. | |
| PINK | There is a high level of risk from manual handling of these products. A full re-evaluation of the risks is required prior to any further activity. | |
| PURPLE | There is a very high level of risk and manual handling of these products is prohibited unless a detailed risk assessment demonstrates that this may be performed safely. | |
| RED XX | These items are now effectively obsolete for manual handling compliance with the Network Rail prohibition notices. | |

TSS 90 Series | TSS 135 Series | TSS 200 Series | TSS 150 Series | TSS 300 Series | TSS 430