ARCTIC GRADE Fire Resistant, Instrumentation Cable BFOU(c) 150/250(300)V, S4/S8

ARCTIC GRADE Fire resistant, Instrumentation Cable BFOU(c) 150/250(300)V, S4/S8

ARCTIC GRADE Fire resistant, Instrumentation Cable BFOU(c) 150/250(300)V, S4/S8

Prysmian draka cABLES

BFOU(c) 150/250(300)V Cable

MGT/EPR/EPR/TCWB/EVA Offshore Cables

Operating Temperature : 90°C

Operating Voltage : 150/250(300)V

Prysmian Draka BFOU Offshore Cable Applications

Instrumentation Cable nek ts 606

Fixed installation for instrumentation, communication, control and alarm systems in both EX- and safe areas, emergency and critical systems where requirement for fire resistance exists. Meets the OIL & MUD resistance requirement in NEK TS 606:2009. Meets the cold bend / cold impact requirement in CSA 22.2 0.3-01 and IEC 60092-350 Clause 8.9 & Annex E at – 40°C/-35°C.

Instrumentation Cable Core Identification
  • Pair – Black – Light Blue
  • Triple – Black – Light Blue – Brown
  • Quad – Black – Light Blue – Brown – Grey
BFOU Instrumentation Cable Construction Code Letter BFOU Instrumentation Cable Description
Conductor Tinned annealed stranded circular copper (STCC), IEC 60228 class 2
Insulation B Mica-tape + EP-rubber, IEC 60092-360 (EPR)
Pair/Triple/Quad twisting Color coded cores twisted together. Pairs/Triples are screened by copper backed polyester tape with tinned copper drain wire. Each pair/triple is wrapped with polyester tape to prevent electrical contact with adjacent pairs/triples. Pairs/triples are identified by numbers printed directly on the insulated conductors.
Inner covering F Flame retardant and halogen-free thermoplastic compound
Tape over inner covering PET tape
Cable armour/screen O Tinned annealed copper wire braid
Tape over armour/screen Rubberized Polyamide tape
Cable outer sheath U Flame retardant, halogen-free, mud and cold bend / cold impact resistant thermoset compound, SHF2 (IEC 60092-360)
Marking text Eg. “meter” “year” DRAKA 01 BFOU(C) 250V S4/S8 4PAIR 0.75mm2 FLEX – FLAME IEC 60092-376 IEC 60331-1*) or IEC 60331-2*) IEC 60331-21 IEC 60332- 3-22 ARCTIC GRADE Cold bend (-40 deg. C) / Cold impact (-35 deg. C)
Cable manufacturing unit DRAKA 01 = Draka Norsk Kabel (Prysmian Group)
Outer sheath colour Grey or blue
Cable Standards Applied
Cable Terminations Joints Cleats 6.6kV 11kV 33kV

Cable Joints, Terminations, Glands & Cleats – available for 6.6kV 11kV and 33kV medium voltage (MV) power cables.

  • IEC 60092-376 (2003-05) – Design IEC 60228 class 2 – Conductor
  • IEC 60092-360 – Insulation IEC 60092-360 – Sheath
  • IEC 60332-1-2 – Flame Retardant
  • IEC 60332-3-22 – Flame Retardant
  • IEC 60754-1,2 – Halogen Free
  • IEC 61034-1,2 – Low Smoke
  • CSA 22.2 0.3-01 (-40°C/-35°C) / IEC 60092-352 Annex E (-40°C/-35°C) – Cold Bend / Cold Impact
Cable Joints Cable Cleats Cable Glands - Prysmian Cables