Hydro Carbon Fire Resistant Instrument Cable BFOU-HCF(c) 150/250(300)V, S16

Prysmian Draka Cables

Prysmian Draka Offshore Cables – LV, MV & HV Instrumentation (RFOU BFOU to IEC / NEK 606)

Prysmian draka cABLES

BFOU-HCF(c) 150/250(300)V Cable

MGT/EPR/EPR/TCWB/EVA/HCF/SHF1 Offshore Cables

Operating Temperature : 90°C

Operating Voltage : 150/250(300)V

Prysmian Draka BFOU Offshore Cable Applications

Instrumentation Cable nek ts 606

Fixed installation for instrumentation, communication, control and alarm systems in both EX- and safe areas, emergency and critical systems where requirement for hydrocarbon fire resistance is vital.

Instrumentation Cable Core Identification
  • Pair – Black – Light Blue
  • Triple – Black – Light Blue – Brown
BFOU-HCF Instrumentation Cable Construction Code Letter BFOU-HCF Instrumentation Cable Description
Conductor Tinned annealed stranded circular copper (STCC), IEC 60228 class 2
Insulation B Mica-tape + EP-rubber, IEC 60092-360 (EPR)
Pair / Triple / Quad twisting Color coded cores twisted together. Pairs/Triples are screened by copper backed polyester tape with tinned copper drain wire. Each pair/triple is wrapped with polyester tape to prevent electrical contact with adjacent pairs/triples. Pairs/triples are identified by numbered tape or by numbers printed directly on the insulated conductors.
Inner covering F Flame retardant and halogen-free thermoset compound
Tape over inner covering PET tape
Cable armour/screen O Tinned copper wire braid
Tape over armour/scree PET tape
Cable outer sheath V Flame retardant, halogen-free and oil resistant thermoset compound (Therban), SHF2 (IEC 60092-360)
HCF Protection – HCF Extruded heatblock compound
Tape Lapped glassfibre tape
Cable outer sheath Flame retardant, halogen-free thermoplastic compound, SHF1 (IEC 60092-360)
Marking text Eg. “meter” “år” DRAKA NORSK KABEL BFOU-HCF(c) 250V S16 4 PAIR 1,5 mm² HCF 1100/30 FLEX – FLAME IEC 60331-21 IEC 60332-3-22
Outer sheath colour Grey, Blue or Black
Cable Standards Applied
Cable Terminations Joints Cleats 6.6kV 11kV 33kV

Cable Joints, Terminations, Glands & Cleats – available for 6.6kV 11kV and 33kV medium voltage (MV) power cables.

  • IEC 60092-376 (2003-05) – Design IEC 60228 class 2 – Conductor
  • IEC 60092-360 – Insulation IEC 60092-360 – Sheath
  • IEC 60332-1-2 – Flame Retardant
  • IEC 60332-3-22 – Flame Retardant
  • IEC 60331-21 – Fire Resistant
  • EN 1363-2 / ISO 834 – HC Fire resistance
  • IEC 60754-1,2 – Halogen Free
  • IEC 61034-1,2 – Low Smoke
  • Draka Norsk Kabel – HCF protection
Cable Joints Cable Cleats Cable Glands - Prysmian Cables

T&D distribute the complete range of Prysmian cable cleats, cable joints and cable glands for onshore and offshore LV-HV power, control and instrumentation cables.