Halogen-Free, Mud Resistant MV Power Cable, RFOU 18/30(36)kV, P20/P22

Prysmian Draka Cables

Prysmian Draka Offshore Cables – LV, MV & HV Power (RFOU BFOU to IEC / NEK 606)

Prysmian draka cABLES

RFOU 18/30(36)kV Cable

EPR/EPR/TCWB/EVA Offshore Cables

Operating Temperature : 90°C

Operating Voltage : 18/30(36)kV

Prysmian Draka RFOU Offshore Cable Applications

power Cable nek ts 606

Fixed installation for instrumentation, communication, control and alarm systems in both EX (hazardous area Zone 0, Zone 1 and Zone 2) and safe areas, general purposes. For installation in areas exposed to MUD and drilling/cleaning fluids. Meets the MUD resistance requirement in NEK TS 606:2009

RFOU Power Cable Construction Code Letter RFOU Power Cable Description
Conductor Tinned stranded and compressed copper (STCC), IEC 60228 class 2
Conductor screen semiconductive Semiconductive layer (EP-rubber)
Insulation R EP-rubber, IEC 60092-360 (EPR)
Insulation screen semicoductive Semiconductive layer (EP-rubber)
Lay up / Shielding Cores are laid up together. Cores are identified by Brown, Black or Grey threads under and over the metallic screen on each conductor.
Inner covering F Flame retardant and halogen-free thermoset compound
Tape over inner covering PET tape
Cable armour/screen O Tinned annealed copper wire braid
Tape over cable armour/screen PET tape
Cable outer sheath U Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-360)
Marking text E.g. “meter” “year” DRAKA 04 RFOU 18/30(36)KV P20/P22 3x 120/60 mm2 IEC 60332-3-22
Cable manufacturing unit DRAKA 04 = Draka Industrial Cable (Prysmian Group)
Outer sheath colour Red
Cable Standards Applied
Cable Terminations Joints Cleats 6.6kV 11kV 33kV

Cable Joints, Terminations, Glands & Cleats – available for 6.6kV 11kV and 33kV medium voltage (MV) power cables.

  • IEC 60092-354 – Design IEC 60228 class 2 – Conductor
  • IEC 60092-360 – Insulation IEC 60092-360 – Sheath
  • IEC 60332-1-2 – Flame Retardant
  • IEC 60332-3-22 – Flame Retardant
  • IEC 60754-1,2 – Halogen Free
  • IEC 61034-1,2 – Low Smoke
Cable Joints Cable Cleats Cable Glands - Prysmian Cables

T&D distribute the complete range of Prysmian cable cleats, cable joints and cable glands for onshore and offshore LV-HV power, control and instrumentation cables.