Hydraulic & Turbine Oils Resistant, Power Cable BFOV 0.6/1(1.2)kV

Prysmian Draka Cables

Prysmian Draka Offshore Cables – LV, MV & HV Power (RFOU BFOU to IEC / NEK 606)

Prysmian draka cABLES

BFOV 0.6/1(1.2)kV Cable

MGT/EPR/EPR/TCWB/HNBR Offshore Cables

Operating Temperature : 90°C

Operating Voltage : 0.6/1(1.2)kV

Prysmian Draka BFOV Offshore Cable Applications

Power Cable nek ts 606

Fixed installation for power, control and lighting in both EX- and safe areas, emergency and critical systems where requirement for fire resistance exists. Especially resistant to the following hydraulic oils: HydraWay HVXA 46, Nyco Turbonycoil 600, Nyco Turbonycoil 610, Mobil Glygoyle 11 and Turbway 32.

Power Cable Core Identification
  • Pair – Black – Light Blue
  • Triple – Black – Light Blue – Brown
  • Quad – Black – Light Blue – Brown – Grey
BFOV Power Cable Construction Code Letter BFOV Power Cable Description
Conductor Tinned annealed stranded circular copper (STCC), IEC 60228 class 2
Insulation B Mica-tape + EP-rubber, IEC 60092-360 (EPR)
Lay up, Shielding Cores laid up in concentric layers
Inner covering F Flame retardant and halogen-free thermoset compound
Tape over inner covering PET tape
Cable armour/screen O Tinned annealed copper wire braid
Tape over armour/scree PET tape
Cable outer sheath V Flame retardant, halogen-free and oil resistant thermoset compound (Therban), SHF2 (IEC 60092-360)
Marking text E.g. meter” “year” DRAKA NORSK KABEL BFOV 0.6/1kV 3 x 4/6mm² FLEX – FLAME IEC 60331-1*) or IEC 60331-2*) IEC 60331-21**) IEC 60332-3-22
Outer sheath colour Black

*) IEC 60331-1 for cables with an overall diameter exceeding 20 mm and IEC 60331-2 for cables with an overall diameter not exceeding 20 mm **) IEC 60331-21 also at enhanced temperature 1000°C for 180 minutes

Cable Standards Applied
Cable Terminations Joints Cleats 6.6kV 11kV 33kV

Cable Joints, Terminations, Glands & Cleats – available for 6.6kV 11kV and 33kV medium voltage (MV) power cables.

  • IEC 60092-353 – Design IEC 60228 class 2 – Conductor
  • IEC 60092-360 – Insulation IEC 60092-360 – Sheath
  • IEC 60332-1-2 – Flame Retardant
  • IEC 60332-3-22 – Flame Retardant
  • IEC 60331-1,-2 EN 50200:2006 Annex E – Fire Resistant
  • IEC 60754-1,2 – Halogen Free
  • IEC 61034-1,2 – Low Smoke
Cable Joints Cable Cleats Cable Glands - Prysmian Cables

T&D distribute the complete range of Prysmian cable cleats, cable joints and cable glands for onshore and offshore LV-HV power, control and instrumentation cables.