Halogen-Free, Unarmoured, Mud Resistant Power Cable, RU 0.6/1(1.2)kV, P18

Prysmian Draka Offshore Cables – LV, MV & HV Power (RFOU BFOU to IEC / NEK 606)
Prysmian draka cABLES
RU 0.6/1(1.2)kV Cable
EPR/EVA Offshore Cables
Operating Temperature : 90°C
Operating Voltage : 0.6/1(1.2)kV
Prysmian Draka RU Offshore Cable Applications
Power Cable nek ts 606
Fixed installation for power, control and lighting in both EX and safe areas, general purposes. For installation in areas exposed to MUD and drilling/cleaning fluids. Meets the OIL & MUD resistance requirement in NEK TS 606:2009. These cables are double-insulated and single core cables are used as battery cables.
Power CABLE CORE IDENTIFICATION
- Single core – Black
- Two cores Blue – Brown
- Three cores – Brown – Black – Grey
- Four cores – Blue – Brown – Black – Grey
- Five cores – Blue – Brown – Black – Grey – Black
- Seven cores and above – White with black numbers
- Two cores + earth (3G) – Yellow/green – Blue – Brown
- Three cores + earth (4G) – Yellow/green – Brown – Black – Grey
- Four cores + earth (5G) – Yellow/green – Blue – Brown – Black – Grey
- G / X in cable description – G = One of the cores are yellow/green – X = no yellow/green core
- Core identification – to HD308S2 – and IEC 60445 Ed 5.0 2010-08
RU Power Cable Construction | Code Letter | RU Power Cable Description |
Conductor | Tinned annealed stranded circular copper (STCC), IEC 60228 class 2 | |
Insulation | R | Mica-tape + EP-rubber, IEC 60092-360 (EPR) |
Lay up / Shielding | Cores laid up in concentric layers | |
Inner covering | No inner covering. (Additional tapes may be applied) | |
Cable armour/screen | No cable armour/screen | |
Cable outer sheath | U | Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-360) |
Marking text | E.g. “meter” “year” DRAKA 01 BU 0,6/1kV P17 1 x 70 mm² IEC 60331-21 IEC 60332-3-22 | |
Cable manufacturing unit | DRAKA 01 = Draka Norsk Kabel (Prysmian Group) | |
Outer sheath colour | Black |
Cable Standards Applied

Cable Joints, Terminations, Glands & Cleats – available for 6.6kV 11kV and 33kV medium voltage (MV) power cables.
- IEC 60092-353 – Design IEC 60228 class 2 – Conductor
- IEC 60092-360 – Insulation IEC 60092-360 – Sheath
- IEC 60332-1-2 – Flame Retardant
- IEC 60332-3-22 – Flame Retardant
- IEC 60331-1, -2, -21 – Fire Resistant
- IEC 60754-1,2 – Halogen Free
- IEC 61034-1,2 – Low Smoke

T&D distribute the complete range of Prysmian cable cleats, cable joints and cable glands for onshore and offshore LV-HV power, control and instrumentation cables.

Call T&D for Prysmian Draka Cables NEK 606/BFOU/RFOU/BU/RU