eXtended Fire Resistant, Instrumentation Cable BFOU-XFR(i) 150/250(300)V

Prysmian Draka Offshore Cables – LV, MV & HV Instrumentation (RFOU BFOU to IEC / NEK 606)
Prysmian draka cABLES
BFOU-XFR(i) 150/250(300)V Cable
MGT/EPR/EPR/TCWB/EVA Offshore Cables
Operating Temperature : 90°C
Operating Voltage : 150/250(300)V
Prysmian Draka BFOU Offshore Cable Applications
Instrumentation Cable nek ts 606
Fixed installation for instrumentation, communication, control and alarm systems in both EX- and safe areas, emergency and critical systems where requirement for fire resistance exists. Meets the mud resistant requirements in NEK TS 606:2009. Cables have extended fire resistant (XFR) properties to IEC 60331-1&2 including water spray according to EN 50200 Annex E (90 minutes).
Instrumentation Cable Core Identification
- Pair – Black – Light Blue
- Triple – Black – Light Blue – Brown
- Quad – Black – Light Blue – Brown – Grey
BFOU Instrumentation Cable Construction | Code Letter | BFOU Instrumentation Cable Description |
Conductor | Tinned annealed stranded circular copper (STCC), IEC 60228 class 2 | |
Insulation | B | Mica-tape + EP-rubber, IEC 60092-360 (EPR) |
Pair / Triple / Quad twisting | Color coded cores twisted together. Pairs/Triples are screened by copper backed polyester tape with tinned copper drain wire. Each pair/triple is wrapped with polyester tape to prevent electrical contact with adjacent pairs/triples. Pairs/triples are identified by numbered tape or by numbers printed directly on the insulated conductors. | |
Lay up, Shielding | Individually shielded pairs/triples/quads are laid up in concentric layers and wrapped with a PETP tape. | |
Inner covering | F | Flame retardant and halogen-free thermoplastic compound |
Tape over inner covering | PET tape | |
Cable armour/screen | O | Tinned annealed copper wire braid |
Tape over armour/scree | PET tape | |
Cable outer sheath | U | Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-360) |
Marking text | Eg. “meter” “year” DRAKA 01 BFOU-XFR(I) 250V 4PAIR 1.5mm² FLEX – FLAME IEC 60092-376 EN 50200:2006 Annex E IEC 60331-1*) or IEC 60331-2*) IEC 60332-3-22 | |
Cable manufacturing unit | DRAKA 01 = Draka Norsk Kabel (Prysmian Group) | |
Outer sheath colour | Grey or blue |
*) IEC 60331-1 for cables with an overall diameter exceeding 20 mm and IEC 60331-2 for cables with an overall diameter not exceeding 20 mm
Cable Standards Applied

Cable Joints, Terminations, Glands & Cleats – available for 6.6kV 11kV and 33kV medium voltage (MV) power cables.
- IEC 60092-376 (2003-05) – Design IEC 60228 class 2 – Conductor
- IEC 60092-360 – Insulation IEC 60092-360 – Sheath
- IEC 60332-1-2 – Flame Retardant
- IEC 60332-3-22 – Flame Retardant
- IEC 60331-1,-2 EN 50200:2006 Annex EÂ – Fire Resistant
- IEC 60754-1,2 – Halogen Free
- IEC 61034-1,2 – Low Smoke

T&D distribute the complete range of Prysmian cable cleats, cable joints and cable glands for onshore and offshore LV-HV power, control and instrumentation cables.

Call T&D for Prysmian Draka Cables NEK 606/BFOU/RFOU/BU/RU