This video by 3M Electrical shows how to apply 3M Cold Shrink tubing safely for underground cable jointing processes and applications.
3M Cold Shrink tubing is a series of open-ended, tubular rubber sleeves, which are factory expanded and assembled onto a removable core – Cold Shrink tubes are supplied for field installation in a pre-stretched condition.
The 3M Electrical video shows how to install the cold shrink tubing and the full underground cable jointing process which is explained below:
Position 3M Cold Shrink outer tube splice body and copper sleeve over the cable
Install connector – a number of the 3M kits come complete with connectors
Many connectors can be used providing they suit the requirements of the cable and fit within the Faraday cage
Once cleaned apply 3M P55 silicone grease leaving the connector until last to avoid contamination and smoothing out the grease to give an even coverage
Move the splice body into place over the connector before unwinding the removable core to install the tube allowing the tube to shrink and form a waterproof seal
Apply a layer of 3M Scotch Seal 5313 Tape to the end of the joint – a comfortable and durable mastic with excellent moisture and environmental seal
Now tape over with the 3M Scotch 2228 Mastic Tape – a conformable self amalgamating temperature stable mastic
Then reposition the copper sleeve over the joint fixing in place with 3M Constant Force Springs
Move the first 3M Cold Shrink Tube into place ensuring one end of the joint is completely covered
Apply 3M Scotch 2228 Mastic Tape in preparation for the last protection tube
Finally install the second 3M Cold Shrink Outer Protection Tube making sure to overlap the previous protection tube
Cold Shrink – invented by 3M over 40 years ago and now the preferred technology for heat-free jointing, terminating, sealing and abandonment of LV HV cables
We hope you find this video informative and educational, contact T&D for technical support, quotations and stock availability for 3M Cold Shrink Tubing.
âž¡ Visit 3M Electrical for further information about joints, terminations, tapes and insulation to seal, repair, splice and connect LV MV HV cables.
3M Cold Shrink cable caps environmentally seal and mechanically protect exposed low, medium and high voltage cable ends using no tools, mastics or tapes.
The 3M video shows how cables ends can be quickly and simply sealed – simply position the end cap over the cable end and unwind the core to install the Cold Shrink cap onto the exposed cables.
Cold Shrink – invented by 3M over 40 years ago and now the preferred technology for heat-free jointing, terminating, sealing and abandonment of LV HV cables
We hope you find this video informative and educational, contact T&D for technical support, quotations and stock availability for 3M Cold Shrink Cable End Caps.
3M Electrical Products Stocked By Thorne & Derrick InternationalÂ
3M Scotchcast Resins – Powerful Cable Joints
Uploaded by Chris Dodds – Thorne & Derrick Sales & Marketing Manager
Selection factors, specification considerations and application notes
Why Choose the Right Cable Joint?
A Failed Cable Joint
Since 1985, Thorne & Derrick International have stocked and distributed 3M Scotchcast cable joints. These joints have a strong field service record and are used to connect, repair and extend existing cable installations.
Scotchcast joints suit a range of cable types, including XLPE, EPR and PILC. They are also used for low voltage (LV) power, instrumentation and control cables.
The main purpose of an LV cable joint is to remove a damaged or faulty section of cable. The joint then restores the cable’s electrical performance as closely as possible to its original manufactured condition.
However, choosing and installing a low voltage resin cable joint requires careful consideration. The right specification depends on the industry, cable type and installation conditions.
Before selecting a cable joint, consider these key factors:
Cable function and application
Required cable reliability
Installation environment
The potential cost of power outages or downtime
Standard resin cable joints can create weak points in industrial cable networks if the specification does not match the application. Therefore, selecting the correct joint is essential for reliable cable connections.
3M Scotchcast Cable Joints
Applications Across Land, Air and Sea
3M Scotchcast resin cable joints provide reliable performance across a wide range of industries. These include construction, rail, renewable energy, airfield lighting, ports, offshore, marine, mining and utilities.
They are also used in hazardous areas, including oil, gas and petrochemical facilities.
The name Scotchcast has become widely recognised in cable jointing. 3M has developed a range of jointing resins to meet different installation needs.
Depending on the resin selected, the range offers properties such as:
Fire resistance
Flame retardancy
Low smoke zero halogen (LSZH) performance
Hydrocarbon resistance
As a result, installers can select a suitable resin for above-ground and underground cable applications.
Deep Underground: Mining Cable Joints
3M Scotchcast 82-F cable joints are designed for straight and branch connections on flexible mining and trailing cables. They use flexible, flame-retardant 3M Scotchcast 2131 resin, which carries Mine Safety and Health Administration (MSHA) Acceptance 07-KA060002-MSHA.
These flexible cable joints do not impair the bend radius of cables that are regularly coiled. In addition, the submersible cable joints offer seawater resistance.
This makes them suitable for connecting cables used by divers and remotely operated underwater vehicles (ROVs).
Seeing Beyond The Surface – Worker & Site Safety With 3M Cable Joints
The World’s Biggest Coalmine: Peabody Energy’s operations in the Powder River Basin of Wyoming, USA. 40% of America’s coal comes out of the North Antelope Rochelle Mine. Photograph: Mae Ryan for the Guardian
Offshore Cable Joints
Global oil and gas companies use 3M Scotchcast resin cable joints to connect low voltage power, instrumentation and control cables offshore.
3M LVI3 resin cable joints suit offshore and marine applications. They are designed for power, instrumentation and control cables, including BS6883, IEEE, UL, UK00A and NEK606 BFOU/RFOU types.
They also suit instrumentation cables in pair, triple and quad configurations. Installers typically use these joints to connect cables in Zone 1 and Zone 2 hazardous areas, where they support low voltage power distribution for lighting and other equipment in potentially explosive atmospheres.
3M LVI3 joints offer hydrocarbon resistance based on the specification performance of 3M Scotchcast 1402FR. They also resist degradation from drilling fluids (mud).
This resistance is important for offshore topside and shipboard installations. Hydrocarbons and drilling mud can damage cable joints over time, increasing the risk of cable faults.
3M: Specified By Global Oil & Gas Industry
Repairing Damaged Offshore Cables
Offshore cables face demanding conditions. Vibration, shock and movement on oil and gas platforms can all cause mechanical damage.
Over time, EPR rubber cable sheaths can also degrade. In some installations, replacing the entire cable can prove too costly or may not be practical.
In these situations, 3M LVI cable joints provide a repair or jointing solution for damaged offshore cables. They help restore the cable connection and reduce the risk of downtime caused by cable failure.
Saltwater atmospheres can react with cable braiding and conductors. This can lead to damage and short circuits if the cable does not have suitable protection.
The wraparound or snap-on, two-part joint moulds allow installers to repair or joint cables mid-span. They do not require disconnection from the remote end of the cable.
3M Cable Joints are installed on offshore oil and gas platforms, FPSOs, FPSs, oil tankers and carriers
Designed for Cable Jointers
Image: Lovink.
Cable jointing can be physically demanding, especially in underground trenches and difficult site conditions. Installers may need to work in confined spaces, handle heavy cables and deal with poor weather.
In the UK, wet weather can make these tasks even more challenging. That’s why practical joint design matters.
3M cable joints are designed with cable jointers in mind. For example, large-shell designs provide more room to work and can improve access during installation.
In addition, the joints support cross-core and transition jointing between multi-core XLPE and PILC cables.
Their impact-resistant shells can withstand trench backfill. This is important because backfill may contain sharp stones, clay and organic material.
Working Space Inside the Cable Joint
The space inside a cable joint shell affects how comfortably and safely an LV cable jointer can work. This is particularly important on demanding sites where access may be restricted.
A larger working area gives installers more room to complete tasks such as:
Armour bonding
Cross-core jointing
Transition jointing
Conductor connections
Large cable joint shells can also accommodate mechanical shearbolt connectors, such as Pfisterer Sicon. These connectors suit imperial, metric and AWG connections.
Furthermore, the additional space can help installers use hydraulic crimp tool heads in close working areas.
Watch: Is the cable joint shell large enough for crossing phased cores?
Reliable Performance in Tough Weather
Offshore cables must withstand harsh weather and demanding operating conditions. On oil and gas platforms, vibration, shock and movement can place extra strain on cable installations.
Weather conditions can also vary widely. Offshore assets may face hurricanes in the Gulf of Mexico or powerful Atlantic storms.
Closer to home, the UK continental shelf regularly experiences severe North Sea weather, including Force 10 storms with strong winds and waves.
Why Choose 3M Scotchcast Cable Joints?
3M Scotchcast low voltage cable joints are designed to make installation simpler, quicker and safer.
When selecting and specifying a cable joint, consider the following features:
Safety: 3M’s Advanced Delivery system provides an integrated resin pour. This helps the cable jointer avoid vapour inhalation and direct skin contact with the resin.
Simplicity: The one-piece, wraparound cable joint shell supports a straightforward installation process. It can also reduce installation time and labour costs during planned shutdowns.
Reliability: Selecting the correct cable joint helps reduce the risk of cable faults.
Choose and specify 3M Scotchcast cable joints to support safe installation and reliable cable connections.
3M Scotchcast Resin Advanced Delivery
How 3M Scotchcast Cable Joints Are Designed
One-Piece Cable Joint Mould Shell
The single-piece cable joint mould shell helps simplify installation. Installers do not need to cut or saw the mould to size.
Instead, range-taking foam seals at each end of the shell provide a tight seal around the cable. This adaptable sealing system removes the need to cut and tape the shell to fit.
The folding mould meets at the top of the cable joint rather than along both sides. This design reduces potential paths for resin leakage.
In addition, 3M cable joint moulds resist cracks and breaks, even at low temperatures. They are also suitable for direct burial.
Watch: Why don’t I need to cut a 3M cable joint shell to fit the cable?
Armour Continuity and Earthing
3M’s armour continuity earthing system suits several cable constructions, including:
Aluminium wire armoured (AWA) single-core cables
Steel wire armoured (SWA) multi-core cables
Copper and phosphor bronze wire-braided cables
Lead-sheathed cables
Traditional worm-drive clips can be difficult to fit when armour wires spread around the cable. To make installation easier, 3M uses constant force springs for earthing.
These springs offer advantages over single-wire earth continuity systems. For example, a single-wire system can fail if the wire sits incorrectly among spread armour cores.
Meanwhile, the flat, soft copper earth braid helps maintain good electrical contact.
Safe & Sound With Constant Force Springs: Cable joints can move and expand due to ground movement and heat from electrical current. Constant force springs respond to this movement and maintain a sound electrical connection between the steel wire armouring and the earth continuity braid
Mechanical Connectors
Mechanical connectors provide a fast and simple way to join copper and aluminium conductors. They suit stranded, sectoral and solid conductors.
They also support connections across metric, imperial and AWG conductor sizes.
Resin Selection
3M Scotchcast cable joint kits include high-quality resin with good moisture resistance. Each kit contains enough resin for the specified application, so installers do not need to top up the joint.
Different resins offer properties for specific installation environments:
Thorne & Derrick distribute a wide range of LV, MV and HV cable jointing, terminating, pulling and installation equipment. We support customers across the UK and worldwide.
Our customers work on underground cables, overhead lines, substations, switchgear and electrical construction projects. We supply equipment for LV, 11kV, 33kV and EHV transmission and distribution applications.
Thorne & Derrick invite you to join our LinkedIn group for professionals working across low and high voltage power, cabling, jointing and electrical engineering.
The group covers topics such as cable installation, cable jointing, substations, overhead lines and electrical construction at LV, 11kV, 33kV and EHV.
Connect with more than 10,000 industry members. You can share knowledge, build your network and promote your professional profile, company or products.
This video by 3M Electrical shows how to apply3M Cold Shrink Cable Joints safely to splice, repair and connect low voltage power cables, 600V/1000V.
3M Cold Shrink cable joints utilise tool free cold shrink technology where no heat or gas torch is required for jointing cable in onshore and offshore locations with polymeric type cable insulation construction including both XLPE and EPR.
Cold shrink is an effective alternative to resin cable joints and can be used indoors, outdoors, overhead or used in cable trays.
Jointing Cables
Ensure all cables and conductors are free from dirt, residue and contaminants using cable cleaning wipes prior to preparing the cable to install the joint.
Cold shrink tubes and copper wire sleeves are first positioned over the cable.
The cable cores are then cut in such a way to stagger the position of the connectors – either mechanical shearbolt or crimp splice connectors are compatible. Check the proposed conductor connector is of suitable physical dimensions to be used with the cold shrink joint – on larger conductors due to volume displacement of multiple mechanical type connectors it maybe preferable for the jointer to use crimp/compression splices due to smooth profile design overcoming any potential bulging or distortion of the cold shrink tubes.
Accepted brands include Cembre, Arcus and Pfisterer Sicon type connectors.
The cable insulation is then removed and connectors are installed.
Most connector technology can be used providing they suit the requirements of the cable voltage, conductor construction and fit dimensionally within the 3M cable joint.
Scotch Electrical Tapes
Scotch 23 self-amalgamating tape is used to over tape the connectors. Layers of Scotch 23 are applied tightly around each connector overlapping into the primary insulation on each side of the connector position.
A piece of cable jacketing that has been saved from the cable preparation is then wrapped around the connectors for added mechanical protection.
Scotch 33+ premium insulation tape is applied across the lengths of the cold shrink joint to improve electrical insulation and water sealing protection.
The copper wire sleeve is then repositioned over the joint and secured onto the cable armours (either wire or braid armour) with constant force springs providing a 360º earth screen around the cold shrink cable joint for added protection.
Scotch 23 self-amalgamating tape is used to tape over the constant force springs ensuring the application is in the same direction as the constant force springs.
Scotch 2228 mastic tape is wrapped over the constant force springs to ensure a smooth profile and to achieve the required cable seal.
The 3M cold shrink protection tube is then positioned over the cable joint. The coil is then removed by hand to install. The live memory action of the specially formulated material shrinks the cold tube into position and ensures a constant radial pressure and seal.
Cold Shrink Joints Selection Table For Power Cables
Selecting the correct 3M LC type cable joint for use with single and multi-core type power cables, typically BS5467 (SWA) or BS6883 (GSWB).Â
Standard 3M Cold Shrink cable joints in the LC range can be over-protected by using cable joint moulds and then filled by pouring resin into the mould to encapsulate the joint – for example the cold shrink joint can be modified to provide resistance to hydrocarbon damage in hazardous area locations by using 3M Scotchcast 1402FR resin.
Can 3M Cold Shrink Joints Be Used To Joint Halogen Free & Flame Retardant Cables?
3M cold shrink joints can be used in conjunction with 3M STFF outer-protection sleeve – the joint sleeve is designed to protect the joint from fire. STFF sleeve is halogen free/zero halogen, flame retardant and does not emit toxic fumes in fire situations. Specified for onshore, offshore and rail tunnel applications where fire resistant protection of the cable joint is critical to overall performance, safety integrity and operational fire performance of the electrical cable and power system.
Can 3M Cold Shrink Be Used For Cable Repair?
Where cables have been subject to sheath degradation overtime due to electrical and mechanical stresses whilst in service a cold shrink tube can be used to re-instate the levels of cable insulation – note this requires access to an open-end of the cable or disconnection of the cable due to the tubular design of the cold shrink. If disconnection or isolation of the power cable system is not possible a heat shrink wrap-around type cable repair can be carried out. Read more about this subject in our detailed Blog covering solutions for repairing damaged cables.
Cold Shrink – invented by 3M over 40 years ago and now the preferred technology for heat-free jointing, terminating, sealing and abandonment of LV HV cables
We hope you find this video informative and educational, contact T&D for technical support, quotations and stock availability for 3M Low Voltage Cold Shrink Cable Joints.
âž¡ Visit 3M Electrical for further information about joints, terminations, tapes and insulation to seal, repair, splice and connect LV MV HV cables.
Learn more about the benefits and applications of Cold Shrink:
This video by 3M Electrical shows in what situations you would require a hazardous area joint such as 3M Scotchcast LVI/3 for jointing power cables in Zone 1 and Zone 2 hazardous areas and potentially explosive atmospheres according to the ATEX Directive.
3M LVI-3/x hazardous area resin cable joint kits are designed to be used for multi-core, armoured polymeric insulated, low voltage energy cables.
The 3M video explains how hazardous area cable joints are designed for applications where the cable joints must be flame retardant, halogen free and hydro carbon resistant.
3M have been supplying cable accessories and electrical insulating Scotchast resins for use in hazardous areas for more than 25 years and have carried out extensive research into the effects of hydrocarbons in chemical solvents and resin encapsulants.
3M products have been successfully installed in areas such as mines and quarries, underground applications, petrochemical sites and offshore areas where there is a risk of flame or explosion due to the atmospheric presence of flammable gases.
A specialised joint shell which is flame retardant, hydro carbon resistant and halogen free is filled with a 3M 1402FR resin which has been highly modified by the inclusion of various chemical additives. These additives make the resin flame retardant, halogen free and virtually unaffected by immersion and hydro carbons or chemical solvents.
Cold Shrink – invented by 3M over 40 years ago and now the preferred technology for heat-free jointing, terminating, sealing and abandonment of LV HV cables
We hope you find this video informative and educational, contact T&D for technical support, quotations and stock availability for 3M Hazardous Area Cable Joints.
Selecting Hazardous Area Cable Joints
Conductor CSA (mm2)
3M LVI-3 Scotchcast Resin Kit Reference For Jointing Power Cables In Hazardous Areas
What Is Arc Flash PPE and Why Is It Important? Arc flash PPE is specialist personal protective equipment designed to help protect electrical workers against the thermal hazards of an electric arc. It includes arc-rated clothing, protective helmets, face...
Voltage detectors are electrical safety instruments used to identify the presence or absence of voltage on electrical equipment and conductors. They are used by electricians, electrical engineers, utilities and maintenance teams working on low voltage (LV), medium voltage (MV)...