Jointing, Terminating & Installation of 11kV Substation Cables
Guest Post from Mick Beeby - Technical & Operations Manager at UK Power Solutions Ltd
Uploaded by Chris Dodds - Thorne & Derrick Sales & Marketing Manager
“I spent a couple of days on site this week with one of our team of Operations Engineers, connecting 4 new ESP adopted 11kV high voltage substations on Phase 2B of the Ballymore Royal Wharf Development in London.
UKPS have provided the electrical infrastructure for Phase 1, 2A and now 2B to date.
This includes 1 x UKPN 11kV boundary substation with 2 RMUs, 1 x SSE 11kV boundary substation with 2 RMUs, 11 x ESP 11kV permanent distribution substations and 1 x ESP 11kV TBS installed and disconnected again, 1 x UKPN 11kV metered TBS to private high voltage transformer.
There are more ESP 11kV distribution substations to install in Q1 2018. This now takes us to 10 of a final 12 total on this ESP 11kV ring.
An IEC was received from SSE for the DNO/iDNO boundary end of the ESP 11kV circuit, which was made Dead, Isolated and Earthed before the 11kV cables were identified and cables spiked under a Sanction-for-Test. A Permit-to-Work was then issued for the 11kV cable jointing, followed by pressure testing under another Sanction-for-Test and final energisation and 11kV phase checks to bring 4 new 11kV high voltagew substations onto the system.”
1 of 4 new ESP 11kV high voltage substations connected on this visit, taking the total on this ESP 11kV ring to 4 substations, and 11 on the Ballymore Royal Wharf development so far.
2 x 3c 11kV polymeric SSE specification straight cable joints of TE Connectivity MXSU series, to loop 4 high voltage substations into the existing ring of 4, making 8 total.
5 Way Transformer Mounted Cabinet post energisation testing. 5 outgoing LV circuits to the multi-occupancy buildings on Phase 2b of the Royal Wharf development.
1 of the 4 new ESP adopted substation internally, comprising Schneider RN2C SF6 Ring Main Unit, Schneider 11000V/400V transformer and Schneider 5 Way Transformer Mounted Fuse Cabinet with incoming high voltage 3c 11kV XLPE polymeric cables.
About Mick Beeby
With over 25 years of experience in the UK Electricity Distribution sector, coming from an apprentice electrician, through Electrical Fitter, Project Manager and Senior Authorised Person roles. Familiar with many types of low voltage, medium voltage and high voltage switchgear, transformers and cables. In depth familiarity of Schneider Genie Evo 11kV switchgear, switchgear cable terminations including complete stripping, re-build and testing.
In depth theoretical and practical knowledge of MV-HV testing and commissioning, cable fault location and cable repair, including test equipment application and limitation.
Experience of all aspects of medium voltage distribution substation testing and commissioning; cable sheath testing, cable/switchgear IR testing, over voltage testing (DC/AC/VLF), primary and secondary injection testing, transformer testing, CT mag curves, CT polarity, soil resistivity and earth electrode systems testing.
Unlike the Distribution Network Operator, we can design & install your private High Voltage network downstream of your HV metering point, providing a more complete package of works to save you time & money. pic.twitter.com/7GtXGzSefH
The Schneider GenieEvo concept is an evolution from the extremely successful Genie philosophy which offers increased levels of flexibility and greater choice for the distribution of medium/high voltage power – this is achieved by allowing separate selection of the MV-HV switchgear and protection and control modules. GenieEvo extends the concept of Genie by offering a gas free circuit breaker to the MV-HV product portfolio.
Schneider GenieEvo comprises
Cast resin encapsulated MV medium voltage system
Demountable vacuum circuit breaker
Controlled air, resin encapsulated series disconnector
Flexible pre-engineered protection and control modules
 1. Vacuum circuit breaker 2. Controlled air disconnector 3. Top entry pilot box 4. Internal arc protection 5. CT chamber 6. Cast resin insulated busbar system with optional earth shielding 7. Multi functional protection and control unit 8. Unit fascia with active operating mimic display 9. Front access cable and vacuum test facility 10. Rear entry MV medium voltage cable box 11. Internal arc vented via dedicated cable trunking for operator safety 12. Mechanical operations counter 13. Circuit potential indicator as standard 14. VT chamber
Medium & High Voltage Switchgear
Thorne & Derrick International
T&D distribute the most extensive range of MV & HV Jointing & Terminating, Installation & Cable Pulling Equipment – we service UK and international clients working on underground cables, overhead lines, substations and electrical construction at LV, 11kV, 33kV and EHV transmission and distribution voltages.
T&D distribute MV-HV Switchgear Cable Terminations to suit 11kV/33kV connections into air, oil and gas insulated switchgear or transformers including heat shrink, cold shrink and separable connectors for both inner cone and outer cone bushings from leading manufacturers including Nexans Euromold, 3M and Pfisterer.
Featured Manufacturer:Â Prysmian 132kV Click Fit Cable Terminations XLPE
Featured Product: Thorne & Derrick Drum Heater HF5-D
Extra High Voltage Cable Type: 132kV Prysmian Single Core XLPE 800sqmm
Terminating 132kV Cables
Cable Oil & Drum Heating
Drum Heaters
Cable heating jackets are initially used to heat the EHV cable to enable relaxing and straightening of the high voltage power cable prior to cable preparation and stripping using cable jointing tools – typically the cable heaters provide a stable temperature of 85 degrees Celsius (185F) for at least 12 hours to the XLPE cable to improve cable manipulation for the HV jointer.
Straightening tubes are then applied to the heated cable and allowed to cool.
The following day cable jointing commences.
The drum heating jacket is applied around the oil drum (silicone oil) and heated to a temperature between 105 – 115 degrees Celsius.
This is done firstly and most importantly to ensure there is no moisture in the oil and secondly to make the oil thinner so it can be pumped into the high voltage cable termination. Once the oil has reached a temperature exceeding 105 degrees Celsius the cable jointer can check with a flash light the condition of the oil.
The heated oil should remain clear with no signs of bubbles, white clouds or foaming.
The oil is then pumped from the drum into the cable terminations insulator to a measurement given on the drawing/ cable jointing instruction. Once the insulator is full to the required measurements, the top is then bolted on and then the cable jointer must press crimp the connector using hexagonal process (HEX) at the correct positions.
T&D supply an extensive range of High Voltage Jointing & Electrical Equipment to enable cable lubrication, cable pulling and installation of 66kV/132kV power cable systems – this includes 132kV surge arresters for electrical protection against overvoltages caused by lightning strike and switching operations.
Pictured: T&D drum heater providing consistent and stable electric surface heating to oil drums for EHV cable termination installations.
In order to achieve the required drum heating temperature of 100+ degrees Celsius the heater jacket was used in conjunction with a base drum heater to accelerate the high temperature heating requirement of the oil – you can see the plate of the base drum heater in the photo below.
Cable Repair Services Ltd
CRS are predominately a reactive cable faults and services team specialising in repairing high voltage fluid filled cables.
CRS have a wealth of experience maintaining, repairing, jointing, terminating and fault-finding on all types of HV fluid filled cable systems ranging from 33kV to 400kV.
All CRS operatives have been trained to the highest standards by companies such as BICC, Prysmian and Balfour Beatty and are able to undertake jobs safely and efficiently while remaining cost effective. Their highly skilled Cable Jointing and Oil Technicians have the capability to joint both polymeric (XLPE) and fluid filled cables up to and including 400kV.
Additional cable services include PILC cable jointing (11kV-66kV), HP gas jointing (66kV-132kV), pilot cable jointing, joint bay refurbishment, cable sheath repairs, serving faults, cable fluid leak locating, gauge calibration and circuit fluid pressurisation.
CRS Cable Repair Services Ltd (CRS Ltd) – trained staff have completed course training to comply with UK Power Network (UKPN) types A,B & C confined spaces.
3M Cold Shrink Terminations (QTIII) are shown terminating 12kV 3 core XLPE (polymeric insulated) cables onto copper busbar with double hole compression cable lugs – the Nexans LC (longitudinally corrugated copper) type cable without screen wires is effectively terminated “cold” i.e. without need for naked flames associated with conventional heat shrink type cable terminations.
3M medium voltage primary distribution cable terminations are extensively used in substations and cable vaults with confined spaces where the presence of potentially explosive atmospheres and flammable gas preclude “hot-working”.
“Skirted” cable terminations feature integral rain sheds suitable for indoor (substation switchgear and transformer) or outdoor (pole-top mounted) installation. The 3 phases are clearly labelled using cable tags (Red, Yellow Blue) attached with conventional cable ties.
The MV feeder replacement project required the removal of an existing 400sqmm PILC medium voltage cable and installation of new 500sqmm XLPE single core cable system – the previous MV system under the cable terminations for grounding is obsolete and out of service.
Note the NEMA pad bolted connection – there is a ball stud on it which is used for applying your working grounds.
MV Shielding For Substation Cables
Longitudinal Corrugated Tape Shielding – a flat copper tape is corrugated at right angles to its length and then formed into a cylinder around the medium voltage cable core or inner cable sheath/jacket. LCT shield design enables rapid stripping and termination by the cable jointer. 3M GSK Shield Grounding Accessory Kits convert concentric neutral (CN) or jacketed concentric neutral (JCN) QT-II or QT-III Cold Shrink termination kits for use on longitudinally corrugated (LC) and tape shielded power cables.
Contact T&D to discuss your next MV Cable Jointing or Terminating application using 3M Cold Shrink.
Medium Voltage Primary UD LCT Shielded Cable
Allteck Line Contractors – specialised services for the high voltage electric power industry.
3M Termination Installation – sealing the cold shrink cable breakout and rejacketing the phases on 3 core medium and high voltage power cables without ground wires.
Should you require any assistance with the selection or specification of cable joints or terminations using 3M Cold Shrink on MV-HV cables please do not hesitate to contact us.
T&D distribute the most extensive range of LV, MV & HV Cable Jointing, Terminating, Installation & Cable Pulling Equipment – we service UK and international clients working on underground cables, overhead lines, substations and electrical construction at LV, 11kV, 33kV and EHV transmission and distribution voltages.
Northern Powergrid distribute electricity to 3.9million homes and businesses across the Northeast, Yorkshire and North Lincolnshire ensuring that 8 million people’s phones are charged and kettles are boiled. Â NPG use the slogan “keeping your power flowing….”
NPG network consists of over 63,000 substations, 60,000 miles of overhead power lines and underground cables spanning 9,650 square miles. Simply the DNO makes sure that the electricity that is bought from their energy supplier gets to the source safely and whenever needed.
Employing around 2,500 people NPG also operate two subsidiaries –Â Integrated Utility Services and CalEnergy Resources Limited.
Integrated Utility Services offers turnkey engineering solutions to customers, including other electricity distributors, across the UKÂ and Ireland.
CalEnergy Resources Limited participates in upstream oil and gas projects in Australia, Poland and the UK.
Thorne & Derrick are Approved Vendors of Northern Powergrid Approved Materials List & Assessed Products to enable the cable jointing, termination, distribution and installation of LV, MV (11kV-33kV) & HV cables onto NPG cable network from manufacturers including:
âž¡ Contact us to discuss your requirements for Northern Powergrid LV, MV & HV Cable Installation, Jointing, Termination, Substation & Electrical Equipment including the following LV-HV Product Categories– our internal NPG commodity code database is constantly updated with new Northern Powergrid products.
Thorne & Derrick distribute DNO approved MV HV Cables including 11kV 33kV – this includes single and 3 core XLPE, EPR and Triplex cables plus suitable cable joints, cable cleats, terminations and connectors in heat shrink, cold shrink, cold applied and plug-in technology.
Cable Pulling & Laying Equipment LV HV
T&D supply Utilities & Approved Contractors with cable pulling products including cable rollers, cable socks and drum lifting jacks to enable the installation of low voltage and high voltage cables intro trench or duct: this includes single core, 3 core and Triplex 11kV/33kV power cables and LV waveform, mains and service cables.
T&D are Specialist Distributors to the UK Distribution Network Operators (DNO’s), NERS Registered Service Providers, ICP’s and High Voltage Jointing Contractors of an extensive range of Cable Joints, Substation, Distribution, Tooling & Installation Equipment approved by the utilities:
by Chris Dodds T&D - estimated reading time 5 minutes
Trefoil Cables
Before we demonstrate an effective duct seal solution for trefoil cables let us first define trefoil and cover the importance of selecting correct cable cleats to prevent short-circuit inflicted damage to power systems and electrical infrastructure.
Cable installations for 3 phase power installations, whether LV or MV (600/1000 Volts to 11kV/33kV) utilise single conductor cables typically in flat or trefoil cables formation – trefoil cable cleats are used to restrain 3 single core cables installed in the “shamrock” style formation, commonly referred to as trefoil.
Where a 3 phase cable system design is based on trefoil cables formation The 17th Edition Wiring Regulations (BS7671) can be consulted to provide current ratings and voltage drop values for the installation.
Trefoil cable formation refers to the installed method for low, medium and high voltage power cables where three single core (phases) distribute the electricity supply rather than a single 3 core cable cable.
Typically, at low voltage (LV) this would be single core XLPE/AWA armoured power BS5467 cables or at medium/high voltage (11kV/33kV) polymeric (XLPE or EPR insulated) single core BS6622 cables.
MV HV Single Core – 11kV Single Core Conductor Cables BS6622
Depending upon the short circuit calculation according to IEC 61914 the appropriately fault-rated cable cleats should be used to provide cable restraint depending on whether the LV, MV or HV power cable system generates short, medium or high short circuit levels.
According to the installation application and environmental conditions trefoil cleats are available in a selection of materials including nylon, stainless steel and aluminium.
Clearly cleating cables is essential, as is effective sealing of cable ducts to prevent flood damage to substations and buildings or the spread of potentially flammable gases.
Sealing Trefoil Cables In Substation Ducts
Single core 11kV-33kV cables in “triplex formation” according to British Standard BS7870 require effective sealing of cable duct entries against water, gas and fire on medium/high voltage substations as well as cleating to protect against short circuit situations. Triplex cables are characterised by the appearance of 3 core cables twisted around each other.
Trefoil cable arrangements entering substation ducts can be difficult to seal using traditional mastic or inflatable cable duct sealing systems, however the FiloSeal+HD duct sealing system effectively seals single, trefoil or multiple cables in duct. The single core cables are carefully separated and supported using the FiloSeal+HD hexagonal tubes – note the central positioning of the hexagonal tubes to establish the required HV cable separation and allow maximum flow of the duct sealant into the trefoil cable formation.
The hexagons separating the pictured 11kV cables must have the smaller hexagonal tubes nested in the large one to create additional strength.
Sealing Cable Ducts With Single, Trefoil & Multiple Cables | LV MV HV 11kV 33kV
Where the cable ducts are located in a designated hazardous area according to the ATEX Directive we can provide expert advice and product recommendations for sealing cables in potentially explosive atmospheres.
Filoform – Water, Gas & Fire Protection | Duct Seals In Industrial & Hazardous Areas
Since 1985 Thorne & Derrick based in the UK have been specialist distributors of LV, MV & HV Cable Installation, Jointing, Substation, Arc Flash Clothing & Electrical Safety Equipment – customers include UK and worldwide contractors, specifiers, traders and end-users involved in cable installations, cable jointing, substation, overhead line and electrical construction at Low, Medium & High Voltages.
We are specialist stockists and distributors of 11kV-33kV Cable Joints, Terminations & Connectors from manufacturers including 3M, Pfisterer, Prysmian and Nexans Euromold in a selection of jointing technologies including heat shrink, cold shrink and push-on.
MV HV | Medium & High Voltage Power Products, Tools, Cables & Electrical Equipment
What Is Arc Flash PPE and Why Is It Important? Arc flash PPE is specialist personal protective equipment designed to help protect electrical workers against the thermal hazards of an electric arc. It includes arc-rated clothing, protective helmets, face...
Voltage detectors are electrical safety instruments used to identify the presence or absence of voltage on electrical equipment and conductors. They are used by electricians, electrical engineers, utilities and maintenance teams working on low voltage (LV), medium voltage (MV)...