Blog
Pot Ending LV SWA PVC Sheathed Service Cables – Engineering Guide UKPN
November 24th, 2020-
uploaded by | Chris Dodds (Sales Marketing Manager at Thorne & Derrick)
PVC Sheath Removal
- Clean the outer PVC sheath of the cable and abrade for 60mm with a rasp, to form moisture seal

- Remove 300mm of the outer PVC sheath
- Refer to the UKPN LV Manual Section 3.5.1 removing the outer PVC Sheath
Steel Wire Armour Opening
- Apply a wire binder around the steel wire armours 25mm from the outer sheath cut at both end of the cable
- Install the service temporary earth bond, consisting of a length insulated braid and two constant force springs, around the steel wires between the sheath removal point and the wire binders
- Using a plastic small wedge and insulated side cutters, cut the individual armour wires around in the centre of the cable joint

- Fold the wires back against the binder at both ends, so they are away from the working area of the cable joint
- PVC tape the cut steel wire armours to the PVC either side of the cable joint
PVC Bedding Removal
- Shroud the exposed armours and the continuity bond connections at both cable ends
- 25mm from the folded back armours, ring round the PVC bedding with a plastic Mini-Hepnyf
- Note: The Mini-Hepnyf needs to be new with a clean sharp edge to ensure that the bedding can be removed without causing damage to the insulation on the cores below
- Remove the bedding between the two bedding removal points, by applying gentle heat to the bedding
- Note: Excessive heat will make the bedding too soft and make it more difficult to remove. Refer to Section 3.5.1 of the LV Jointing Manual
- If the bedding layer is difficult to remove or if it is bonded to the core insulation, then the cable shall be made dead, prior to continuing with the bedding removal process

Core Cutting & Capping
- Refer to Section 3.7.3 of the LV Jointing Manual
- A PILC two or four core heatshrink pot end kit should be utilised depending on the number of cores in the SWA cables
- Once the cores are exposed, test the cores to prove live and neutral
- Insert a plastic cutting wedge between the cores and cut each live core in turn centrally and install a temporary cap

- Finally cut the neutral core and install a temporary cap


- Cut each of the live core(s) 70mm from the bedding and install the heatshrink cap provided in the joint kit, as per Section 4.10.4 of the LV Jointing Manual
- Cut each of the neutral core 70mm from the bedding and install the heatshrink cap provided in the joint kit, as per Section 4.10.4 of the LV Jointing Manual

Completing The Pot End
- Remove the temporary earth continuity bond and any temporary shrouding
- Allow the heat caps to cool, apply two half lap layers of PVC tape over the cores
- Fold the steel wires back over the previously applied PVC tape, trim them to the same length as the phase and neutral cores
- Apply two half lap layers of PVC tape over the wire armours and tinned copper mesh, make sure all sharp edges are covered

- Slide the mastic coated heatshrink tube over to the 60mm of sheath abrasion and shrink into place ensuring a good water seal. As per Section 4.10.4 of the LV Jointing Manual
- Slide the mastic coated large heat shrink cap over the previously shrunk tube and shrink in place, starting at the sealed end, before working towards the open end. To prevent the
cap sliding off hold in place using an insulated wedge

- Allow to cool before fitting the yellow plastic safety bag in place

- Once the pot end has cooled, place the yellow bag over the joint, ensure that the hazard symbol is on the top and fix in place with PVC tape

LV HV Electrical Cable & Power Distribution Systems up to 66kV – we are highly customer responsive and absolutely committed to providing a world-class service.
Contact our UK Power Team for competitive quotations, fast delivery from stock and technical support or training on all LV-HV products.
Key Product Categories: Duct Seals | Cable Cleats | Cable Glands | Electrical Safety | Arc Flash Protection | Cable Jointing Tools | Cable Pulling | Earthing | Feeder Pillars | Cable Joints LV | Joints & Terminations MV HV
Raychem Terminations for Medium Voltage Power Connections
November 24th, 2020Image Courtesy of: John Perrott (Director of Power at AIS)
Pictured Below: Raychem Terminations
Jointer: Ernie Briones

Accurate Infrastructure Solutions
Accurate Infrastructure Solutions is a dynamic contracting and consultancy business with expertise across a multitude of industries, including:
Offshore Support – quickly and reliably meeting all client’s short, medium or long-term, technical and general support requirements via ‘virtual’ / ‘remote’ assistance from qualified, globally experienced professionals based in AIS’s Philippines offices.
Construction – providing skilled construction professionals and solutions within the civil, commercial, residential, infrastructure, and engineering industries by way of labour only or full contract basis.
Power – providing skilled, qualified, & experienced tradesman & professionals as well as full contract solutions to the power industry within the civil, generation, transmission, distribution sectors.
Recruitment – bringing together end to end domestic & international recruitment and mobilisation solutions within any industry by offering diverse & flexible methods of engagement.

Jointers blog
Subscribe now to our POWER NEWSLETTER– a monthly email circulation packed with news, projects, videos, technical tips, training information, promotions, webinars, career opportunities and white papers.
Includes access to our popular JOINTERS BLOG with contributions from utility professionals, linesmen and cable jointers working on MV HV EHV cables and overhead lines typically at 11kV, 33kV, 66kV and up to 132kV.
Arc Flash Clothing Saves Lives | Watch Eddies Story
November 23rd, 2020
Saving Lives | Arc Flash Clothing & Protection
Article uploaded by Chris Dodds – Thorne & Derrick Sales & Marketing Manager
Lifesaving Arc Flash Clothing – Eddie’s Story
“If I wasn’t wearing my PPE, it probably would have been a different story.”
These are the words of Eddie Smith, a construction worker who survived a serious arc flash incident after his jackhammer struck a live underground electrical cable.
Eddie was wearing suitable arc flash protective clothing at the time. His PPE helped reduce the extent of his injuries.
His experience shows why electrical safety precautions matter when working around buried services. It also highlights the importance of selecting and wearing the correct PPE.
Thorne & Derrick met Eddie and his colleagues at Clancy Docwra to learn more about the incident and its impact.
What Happened During the Cable Strike?
Eddie was using a jackhammer when the tool struck an underground low voltage electrical cable.
The contact caused an electrical incident involving an arc flash. Eddie suffered burns to exposed areas of his body.
However, his protective clothing helped shield other areas from the thermal effects of the incident.
The experience had a lasting effect on Eddie, his family and his colleagues.
Underground Cable Safety – Avoiding Danger from Buried Services
Excavation and ground-breaking work can expose workers to underground electrical hazards.
For example, cables may be buried beneath roads, footpaths and construction sites. Their position or depth may not always be obvious.
Striking a live electrical cable can cause electric shock, arc flash, burns and other serious injuries.
For this reason, workers must take appropriate precautions before starting work.
HSE HSG47 – Avoiding Danger from Underground Services
The Health and Safety Executive provides guidance in HSG47 – Avoiding Danger from Underground Services.
This guidance is relevant to people planning, managing and carrying out work near buried services.
These services include:
- Underground electricity cables.
- Gas pipes and associated equipment.
- Water and sewerage infrastructure.
- Telecommunications cables.
- Other buried utility services.
Safe working requires proper planning, locating and identifying services, and using suitable excavation methods.
Furthermore, workers must follow the applicable site procedures and risk assessments.
Arc flash PPE provides additional protection, but it cannot replace these precautions.
Watch Eddie’s Arc Flash Incident Story
ProGARM worked with Clancy Docwra to produce a video about Eddie’s experience.
The film was created to support workforce training and raise awareness of electrical hazards.
Eddie and his colleagues explain what happened, how the incident affected them and why wearing the correct protective clothing matters.
Watch the video below to hear their account.
Clancy Docwra – The Impact of Eddie’s Accident
The incident affected not only Eddie but also his colleagues and family.
Several members of the Clancy Docwra team described their reactions in the original video.
Jim Eldred – Operations Manager
Jim Eldred recalled receiving the news that Eddie had been injured.
“I received a phone call mid to late morning from Eddie’s teammate. He informed me that Eddie had had an accident and that he had suffered injuries. I was informed that it was electric and that an ambulance was on route.
For me I was scared, I was pretty worried.”
The call made it clear that the incident was serious. At that stage, Jim did not know the full extent of Eddie’s injuries.
Stephen Bainbridge – Field Performance Manager
Stephen Bainbridge described his immediate concern for Eddie and his family.
“The first thing that runs through your mind is, is Eddie okay? And then you start thinking about his children – because he had a young family and a wife. having children myself, that was my concern for Eddie, is he going to come back from this, is he going to work again? As a team we took it quite badly..”
His words show how a serious workplace accident can affect an entire team.
Eddie Smith – Surviving an Arc Flash Incident
Eddie described the moment the arc flash occurred and how quickly everything happened.
“When the Arc Flash hit me – it went so fast. And then everything that happened after seemed to go in slow motion. There were these thoughts running through my head; the first one being obviously my little boy, but also my family and my job, and worry about the physical injuries.”
He also explained where he suffered burns.
“I had burns all the way up my hands, down my neck, inside my nose, mouth and around my face. But because I wear this PPE it didn’t touch my chest, legs or arms.”
Why Wearing Arc Flash PPE Made a Difference
Eddie’s protective clothing helped limit the injuries to areas covered by the garments.
However, he still suffered burns to other parts of his body.
His account demonstrates why workers need a complete, task-appropriate PPE arrangement, including consideration of exposed areas.
It also shows why protective clothing must be worn correctly.
“You Think It’s Never Going to Happen to You”
Eddie reflected on the shock of experiencing an accident despite his years of work experience.
“It’s one of those things you think is never going to happen to me, I know what I’m doing I’ve been doing it years – when it does its a massive shock to you and your family.”
Experience is valuable, but it does not remove electrical hazards.
Therefore, even experienced workers must follow the required safety controls for every task.
The Importance of Wearing the Correct Arc Flash PPE
Stephen Bainbridge emphasised that worker safety must come before productivity.
“We need to get across that it’s not about money, it’s not about how many jobs you get done in a day – it’s about doing that job safely. Mostly. You have to wear this PPE. If you don’t wear it you could be dead with just one cable strike.”
His message reinforces an important principle: workers must have the correct protection and follow safe working procedures.
However, PPE must never become a reason to accept avoidable electrical risks.
Arc Flash PPE Is the Last Line of Defence
Arc flash clothing helps protect workers against specified thermal hazards.
Nevertheless, it cannot prevent an electrical cable strike or eliminate every injury risk.
Before starting work near underground services, employers and workers must implement suitable risk controls.
These include identifying hazards, assessing risks and using approved working methods.
Only then should the required PPE be selected as part of the overall protection arrangements.
Eddie’s Message to Other Workers
Eddie summed up the importance of his protective equipment in one sentence.
“If I wasn’t wearing my PPE, it probably would have been a different story.”
His experience is a reminder that safety procedures and correctly selected PPE can make a critical difference during an accident.
ProGARM Arc Flash Clothing – Performance in a Real Incident
Following the accident, ProGARM reviewed the protective clothing Eddie had been wearing.
Mark Lant, a Technical Expert at ProGARM, commented on the garment’s performance.
“Obviously, we’d prefer it if Arc Flash incidents never occurred. However, the fact is they do, and we’re pleased to see our polo shirt performing as effectively in the field as it did in the lab. We wish the operative a speedy recovery from his other injuries.”
The original article also included photographs of the PPE after the incident.

The arc flash PPE worn by Eddie during the incident.
Why Tested Arc Flash Clothing Matters
Arc flash garments are tested to assess their performance against defined thermal exposure conditions.
For example, a garment may carry an arc rating expressed in cal/cm².
However, that rating does not mean the clothing protects against every possible incident.
Workers must select PPE according to the relevant arc flash risk assessment and required protection level.
Furthermore, clothing must be worn as instructed and kept in a suitable condition.
ProGARM’s Response
The original article also included the following statement about the importance of real-world protection.
“It’s only when you see ProGARM’s Arc Flash garments in action like this that you realise how vital they are to saving lives in the field. We can perform every test available on our range of protective clothing, but to see real garments in real situations saving real lives is the ultimate proof of our success. When an Arc Flash incident occurs, we know that our protective garments are up to the job.”
This statement reflects ProGARM’s response to the incident. PPE performance must still be assessed against the specific hazard and the applicable product standards.
Eddie’s Recovery – A Reminder About Electrical Safety
Thankfully, the original case study reported that Eddie made a full recovery and returned to work.
His story highlights the importance of preventing electrical incidents wherever possible.
It also demonstrates why suitable PPE matters when an accident occurs despite the precautions taken.
Always follow approved safe working procedures. Never compromise electrical safety to complete a job more quickly.
Further Reading About Arc Flash
Learn more about electrical hazards and appropriate protective equipment through our related articles.
- Arc Flash PPE – 7 Top Considerations.
- Arc Flash – The Basics.
- 5 Arc Flash Risks for Solar Industry Personnel.
ProGARM – Arc Flash Protective Clothing
ProGARM manufactures protective workwear for electrical and industrial applications.
The product range includes arc flash garments for workers exposed to specified electrical thermal hazards.
For example, suitable clothing may include coveralls, trousers, jackets and polo shirts.
Additional PPE may be required to protect the head, face, hands and other exposed areas.
Choosing Suitable Arc Flash Clothing
Arc flash clothing must be selected according to the task and the assessed hazards.
For example, the required protection depends on the potential thermal exposure and working conditions.
The correct garment arrangement must also provide suitable body coverage.
In addition, employers should consider comfort, movement and other workplace hazards.
Explore our arc flash clothing and electrical PPE.
Thorne & Derrick – ProGARM Arc Flash Clothing Distributors
Thorne & Derrick supply ProGARM arc flash clothing and electrical protective equipment.
Our customers include electrical contractors, utilities and industrial maintenance teams.
For example, suitable protective workwear may be required for tasks involving:
- LV cable installation and maintenance.
- MV and HV cable jointing.
- Substation maintenance.
- Switchgear operation.
- Overhead line work.
- Electrical testing and inspection.
- Underground utility construction.
- Electrical distribution equipment maintenance.
However, the correct PPE must always be selected for the specific task and identified hazards.
Our technical sales team can assist with product information and availability enquiries.
ProGARM Arc Flash Clothing – Featured Products
The following products appeared in the original article.
They include arc flash coveralls, trousers and polo shirts for different workwear applications.
Product references and images are retained from the original article. However, current specifications, ratings and availability should be confirmed before purchase.
ProGARM Coveralls, Trousers and Polo Shirts
|
|
|
|
|
|
|
|
|
|
Download Your Guide to Arc Flash Protection
Understanding arc flash hazards is important when selecting protective equipment.
Our guide provides further information about arc flash risks and PPE.
DOWNLOAD YOUR GUIDE TO ARC FLASH
Electrical Safety and Cable Installation Equipment
Thorne & Derrick also supply specialist equipment for low, medium and high voltage cable installations.
Our product offering includes cable joints, terminations, connectors and installation tools.
We support electrical contractors, utilities and infrastructure businesses working across LV, 11kV, 33kV, 66kV and EHV systems.
MV and HV Cable Joints, Terminations and Connectors

HV Cable Joints, Terminations & Connectors | 3M Electrical (Cold Shrink) | Nexans Euromold | PFISTERER CONNEX | 11kV 33kV 66kV
Enquire About ProGARM Arc Flash PPE
Need arc flash clothing for your electrical team?
Contact Thorne & Derrick to discuss the required garments, product specifications and availability.
For effective protection, always base your PPE selection on the relevant electrical risk assessment and applicable standards.
VIEW ARC FLASH CLOTHING AND PROTECTION
STRUTSLAYR from RIDGID | The Strongest Most Powerful Strut Channel Cutter
November 16th, 2020
STRUTSLAYR | Stocked by Thorne & Derrick
The NEW RIDGID STRUTSLAYR™ strut channel cutter is the latest accessory that makes the world’s most popular press tool even more valuable.
Strut channels are used in a wide variety of applications such as Plumbing, HVAC, Fire Protection, Electrical and Solar for structural support of pipes, ventilation/air-conditioning/sprinkler systems as well as cable trays and solar panels. Before they are installed, each strut channel needs to be cut and deburred; this activity can be a very time-consuming task when it is done with traditional cutting tools like an angle grinder, cold cutting and recip saw.
Introducing StrutSlayr
STRUTSLAYR Strut Shear Head attaches to, and is compatible with, RIDGID 32kN press tools – delivering excellent shop quality with a burr-free cut in less than 5 seconds.

The StrutSlayr offers a shearing operation, where the material gets displaced rather than directly cut. This means that there are no grinding or sawing sparks with this Strut Cutter – just a clear consistent SHEAR cut with a pull of a trigger.
The RIDGID® STRUTSLAYR™ delivers shop quality, burr-free strut channel cuts on the jobsite in 5 seconds or less. Compatible with RIDGID 32kN press tools, the STRUTSLAYR strut cutter offers a clean, consistent cut with a simple pull of a trigger.
*NOTE: Press tools are not included. Not compatible with RIDGID 320-E or CT-400.

STRUTSLAYR Strut Channel Cutter FEATURES
- Fab Shop Quality: Burr-free cuts eliminate the need for extra filing
- Increased Efficiency: Clean, consistent cuts in 5 seconds or less
- Shear Cut: no grinding or sawing sparks
- Portable: Easy to move around the job site and mounts to RIDGID TRISTANDs
- Built-in Measuring Guide: allows accuracy of cut on job site
![]() Choose from the RIDGID STRUTSLAYR™ kit 64053 or 64058 depending on die shear size. Available from stock for fast delivery. |
![]() Request a UK demo of the RIDGID STRUTSLAYR today. |
StrutSlayr Specification
Portability – The StrutSlayr Head weighs only 5.4 kg and is supplied in a sturdy and compact blow-molded case for easy and safe transportation to any jobsite. Cut everywhere, anywhere!
Long-lasting– Approximately 140 cuts can be expected from a single full battery charge with StrutSlayr Head mounted.
Flexibility – StrutSlayr is highly versatile. It can be easily used on a workbench, on a RIDGID TRISTAND, on the ground or even on a platform.
Accuracy – A built-in measuring guide is displayed on the RIDGID StrutSlayr to accurately measure the size of the strut that needs to be cut. The integrated Strut Support prohibits deformation of the Strut channel and provides a straight cut every time. The strut channel cutter offers reduced risk of sparking when compared to grinders and chop saws and still manages to produce a clean, consistent cut.
Size & wall-thickness – StrutSlayr strut cutter features field-replaceable dies and it is supplied with either a 41×41 or 21×41 shearing die, covering the most important two strut channels sizes. StrutSlayr can be used for cutting Strut Channels with wall-thickness up to 2.5 mm. A minimum amount of 2000 cuts can be expected from each new die set. Efficiency never seen before!
Press Tool Compatibility – RIDGID® Standard Series 32kN Press Tools (such as the RIDGID RP 350-B Tool Kit)
*Not for use with RIDGID 320-E and CT-400 Press Tools
For the full technical specification, visit Strut Shear Head


Klauke Orange | World‘s first battery hydraulic crimping and cutting tools with Tri-Insulation Barrier technology to provide jointers, linesmen and electrical engineers with 1000V protection against electrical shocks
LV, MV & HV Jointing, Earthing, Substation & Electrical Eqpt

Thorne & Derrick International are specialist distributors of LV, MV & HV Cable Installation, Jointing, Duct Sealing, Substation & Electrical Equipment – servicing UK and global businesses involved in cable installations, cable jointing, substation, overhead line and electrical construction at LV, 11kV, 33kV and EHV.
THORNE & DERRICK Product Categories: Duct Seals | Cable Cleats | Cable Glands | Electrical Safety | Arc Flash Protection | Cable Jointing Tools | Cable Pulling | Earthing | Feeder Pillars | Cable Joints LV | Joints & Terminations MV HV

Thorne & Derrick | Stockists & Suppliers | Joints Terminations Connectors up to 66kV
Roxtec Sealing Solutions For Cables & Pipes | Process Industry Whitepapers
November 13th, 2020
Roxtec are global-market leaders in the innovation and manufacture of cable transits and pipe penetration sealing systems to the process and hazardous area industries.
Roxtec solutions seal cables, cable ducts and pipes against water ingress, gas migration and fire hazards into safety critical and sensitive electrical equipment and buildings.
Whitepapers
- Whitepaper: EMP/EMI Protection In Control Rooms/Centres In Critical Infrastructure
- Whitepaper: Roxtec Multi-Cable Transit Devices
- Whitepaper: Modular Integration of Process Equipment Packages for Oil and Gas Facilities
- Whitepaper | Modular Cable Termination Design By Roxtec

Hazardous Areas & Explosive Atmospheres (Gas & Dust) | Ex e and Ex tb Explosion Protection Certified by ATEX & IECEx | Zone 1/21 & Zone 2/22
Process Industry
Typical Applications
Buildings & E-houses
Wall entries
Floor entries
Underground entries
Control rooms
Analyzer shelters
Substations
Remote instrument buildings (RIB)
Field auxiliary rooms (FAR)
Local equipment rooms (LER)
Terminal Boxes, Cabinets & Enclosures
Remote I/O cabinets
Hazardous locations (Ex e)
Ordinary locations
Electric heat tracing systems
Automation and control cabinets
DCS panels
Motor control cabinets
Safety instrumented systems (SIS)
Fire and gas detection control cabinets
Machine monitoring systems
Lighting panels

Thorne & Derrick are distributors for Roxtec, the leading manufacturer of sealing solutions for cables and pipes, – protecting cables and pipes in the process industry sector against water, gas and fire.
CONTACT US WITH YOUR ENQUIRY
Specialist Distributors of Industrial & Hazarodus Area Equipment to provide Power, Heat, Light & Ventilation to the explosive atmospheres and process industries.
Control Panels | Plugs | Isolators | Enclosures & Junction Boxes | Lighting | Control Stations | Motor Starters | Heat Trace | Gas Detection | Flame Detection | Process Instrumentation | Process Heating | Ventilation Fans | Security Access Control

Competitive Prices | Extensive Stocks | Technical Support | Express Delivery