➡ Richard Emery IEng MIET MIHEEM Authorising Engineer (E) IHEEM AE(E) at Green Building Design Consultants. Its a cooling medium. The oil circulates around the core and out to radiators on the sides, so aiding the cooling of the transformer core
Blog
Bunding – Oil Filled Transformers, To Bund or Not to Bund?
April 25th, 2019
Transformer Bunds | Bunds for oil-filled transformers manufactured from steelwork on reduced lead time and at competitive prices from Thorne & Derrick | Contact us with your requirements | Stock, Service & Product Support
How Can We Help?
Thorne & Derrick can provide design and manufacturing services for Transformer Bunds with optional oil filters, drain valves, filter systems and ancillaries in both mild and galvanised steel (painted or unpainted) – innovative, efficient, safe and cost-effective solution for protection against leakages of insulating liquid to BS EN 61936-1:2010.
BS EN 61936-1:2010
Power Installations Exceeding 1kV a.c. Common Rules

Oil Filled Transformers
Guest Contribution: Carl A. Watkin IMEMME (Hons) I.Eng MIMMM MIET AIOSH
Carl has over 40 years experience as a Projects Director, Electrical Engineer & Project Manager in the highly regulated HSE HID hazardous and heavy industry sectors – this includes global ATEX and IECEx hazardous environment and area industries, civil tunnelling, LV MV HV utility sectors and the renewables sector.
In this original post from LinkedIn, the business and employment-oriented social media network, Carl discusses transformer bunds with gathered opinions from industry peers featured in the thread of comments below.
Bunding – Oil Filled Transformers
To Bund or Not To Bund?
by Carl A. Watkin
Question to all my fine Engineering contacts regarding oil filled distribution transformers – transformers are exempt from the UK oil storage regulations, as they are oil using (cooling) rather than storing, unless they have a conservator, holding in excess of 201lts, connected by single pipe – I see many transformer installs, including DNO installations, that do not have bunds around the transformers.
See: BundGuards | Substation & Transformer Oil Spills & Leaks Containment
What are your thoughts on bunding, or not, of oil filled transformers? What criteria would you use to assess whether to bund, or not?
➡ Neil Denbow (Director at Eden Transformer Oil). For distribution transformers yes you can but the process should be carried out by an accredited MIDEL Service Partner (we were the first). For power transformers yes but with referral to M&I Materials. There have been many successful retrofills around the world – MIDEL 7131
➡ Usually sealed distribution transformers up to 630-800 kVA don’t need to be bunded.
➡ Neil Denbow (Director at Eden Transformer Oil). Manuel, BS EN 61936-1:2010 doesn’t differentiate between breathing and hermetically sealed transformers, it is defined by the volume of oil in the transformer.
➡ (Richard Emery IEng MIET MIHEEM Authorising Engineer (E) IHEEM AE(E) at Green Building Design Consultants). I get the transformer bunding problem, and even if you don’t have an oil storage problem, and the environment agency have incorrect information there is the risk assessment? Is a spillage going to cause secondary contamination, disruption and damage? How do we deal with external transformers/ bunding and rain water? I have seen some bunded walls with 300mm of water in them others with drain taps left on.
➡ Neil Denbow (Director at Eden Transformer Oil). Richard, larger 11kV transformers will have oil/water separation systems, smaller transformers will have valve with a oil/water capture filter that allows water to pass through but trap oil. We sell the latter on our website www.edenoil.co.uk and have a partner for the lager systems:- When a bund has not been maintained or doesn’t have filter system, we offer a bund emptying service.
➡ We’ve put in from full on concrete swimming pools, active filters to perspex shields around the rads to stop fluid spraying past the bund. Most of the time midel is used these days which doesn’t have the same environmental issues, a bund with a filter seems to be what we do most though.
➡ Neil Denbow (Director at Eden Transformer Oil). Dan, you are right that MIDEL is readily biodegradable but BS EN 61936-1:2010 doesn’t differentiate between oil, synthetic or natural esters. However, insurance companies do.
➡ This has been debated many times in the Rail industry. With respect to Environmental Agency website error, certain parties in Rail industry have received same letter from Environmental Agency but certain representatives contradict each other in their response.
➡ Derrick Stableford P.Tech.(Eng.) (Electrical, Instrumentation and Controls Designer at Associated Engineering). Funny I had a containment question at work this week. Sorbweb matting would be my answer for leak control. Most trannys at this level have level switches as options, the hard part is the comms back to the control centre, without creating a cyber security intrusion risk. The sorbweb Mat adsorbs oil, and repels water. No need for a shed. Using food grade oil will also help with environmental risks. You could fry your lunch with a drawn off sample, or bang it in your diesel. The bunding and double wall systems have their own cost adders and maintenance issues, Inc water pump outs and disposal. Mechanical separators can freeze and fail, esp. here at severely minus temps.
➡
➡
➡ Karl R (Functional Safety & Systems Engineer). Watch out for an error in the HSE publicised “Hierarchy of Controls” leaflet. The vitally important area of physical isolation was missed. The hierarchy is actually: 1 Eliminate – do it a different way that doesn’t use the hazardous methods or substances. There’s no risk if there’s no hazard. No need to mitigate for a non existent hazard. Save effort, money and time for use elsewhere. 2 Substitute – use something non/less hazardous 3 Isolation – Physical separation. Barriers, bunds, locked areas and vessel containment. Dual layers. 4 Design – Automation, control, monitor, report and safely shutdown/reroute. Engineered solutions to mitigate hazardous situations and prevent hazardous material release. Control and safety systems to look after the process. Switchgear protection. 5 Admin – Enforcement and training. Emergency Response Procedures. Authorised areas, Competency, Risk Assessments, Design Reviews, Method Statements, verification and validation, maintenance, etc. 6 PPE
➡ There’s a regulation in the 18th edition where it covers transformers containing oil shall be bunded or pitted to distinguish any potential fires
Thorne & Derrick stock and supply the DrainEezy range of transformer bund filters for use with LV MV HV Oil-Filled Transformers providing passive, self-regulating environmental protection and preventing bunds from overflowing during rainfall events; the DrainEezy Bund Filter System is field-ready to fit and retrofittable allowing clean water to drain freely while automatically blocking and retaining insulating oil in the event of a leak or catastrophic transformer failure.

600/1000V | 11kV | 33kV | 66kV Transformer Bund Filters
Lucy Zodion Titan2 Street Lighting Cut Outs – Single & Double Pole
April 16th, 2019
-
Uploaded By - Chris Dodds (Thorne & Derrick Sales & Marketing Manager)
Street Lighting Cut Outs
Lucy Zodion Ltd, are the leading UK manufacturer of street lighting cut-outs, controls, feeder pillars and street lighting isolators – their street light cut outs (SLCOs) are also part of the G81 specification framework.
Lucy Zodion Titan2 cut outs are supplied as standard with features that ensure the street lighting technicians task is considerably easier.
The Lucy Titan2 cam lever handle enables effortless release of the Lucy fuse carrier in one movement and there is plenty of cabling space to terminate a wide variety of conductor types and sizes.
Insulated or brass cable gland plates are also available for when dual or triple entries are required.
High quality engineering thermoplastics make the Lucy Zodion Titan2 range the ideal choice to withstand heavy use in demanding locations.

Lucy Zodion Titan2
Street Lighting Cut Outs Range
- Single or double pole cut outs
- Single or twin fuse cut outs
- Brass or insulated gland plate options
- Extensive trough options
- 1 up, 2 up, 1 up 1 down circuit arrangements

Street lighting Cut Outs – Titan2
TITAN2 SINGLE & DOUBLE POLE CUT OUTS
PRODUCT SPECIFICATION
Should you require any technical support and advise in order to select the correct street lighting cut out please do not hesitate to contact us.
| Lucy Cut Out Part No | Fuseways | Components | Description | Cable Entry | Image |
| Titan2 (NT06) double pole single fuse cut out, complete with earth block, and brass plate with: | |||||
| THM0006032 | 1 | 2 x 20mm grommets | NT06-TT-NG12 | ![]() |
|
| THM0010170 | 1 | 2 x BW20 brass glands | NT06-TT-NG18 | ||
| THM0010121 | 1 | 2 x 20mm tubes | NT06-TT-NG25 | ||
| THM0031147 | 1 | 2 x 25mm tubes | NT06-TT-NG26 | ||
| Titan2 (NT06) double pole single fuse cut out, complete with earth block, small extension trough, and brass plate with : | |||||
| THM0010657 | 1 | 2 x 20mm grommets | NT06-TT-NEF-NG12 | ![]() |
|
| THM0017257 | 1 | 2 x 20mm grommets | NT06-TT-NEF-NG13 | ||
| THM0013678 | 1 | 2 x BW20 brass glands | NT06-TT-NEF-NG18 | ||
| THM0010211 | 1 | 2 x 20mm tubes | NT06-TT-NEF-NG25 | ||
| THM0010212 | 1 | 2 x 25mm tubes | NT06-TT-NEF-NG26 | ||
| Titan2 (NT06) double pole single fuse cut out, complete with earth block, large extension trough, and brass plate with : | |||||
| THM0036546 | 1 | 2 x 25mm grommets | NT06-TT-NED-NG13 | ![]() |
|
| THM0037191 | 1 | 2 x 20mm tubes | NT06-TT-NED-NG25 | ||
| THM0028975 | 1 | 2 x 25mm tubes | NT06-TT-NED-NG26 | ||
| THM0016546 | 1 | 2 x BW25 glands and 1 x 25mm grommet | NT06-TT-NEE-NG82 | ||
| Titan2 (NT08) double pole twin fuse cut out, complete with earth block, and brass plate with : | |||||
| THM0009901 | 2 | 2 x 20mm grommets | NT08-TT-NG12 | ![]() |
|
| THM0012689 | 2 | 2 x BW20 brass glands | NT08-TT-NG18 | ||
| THM0013303 | 2 | 2 x 20mm tubes | NT08-TT-NG25 | ||
| THM0014521 | 2 | 2 x 25mm tubes | NT08-TT-NG26 | ||
| Titan2 (NT08) double pole twin fuse cut out, complete with earth block, small extention trough, and brass plate with : | |||||
| THM0010563 | 2 | 2 x 20mm grommets | NT08-TT-NEF-NG12 | ![]() |
|
| THM0029334 | 2 | 2 x 25mm grommets | NT08-TT-NEF-NG13 | ||
| THM0014659 | 2 | 2 x BW20 brass glands | NT08-TT-NEF-NG18 | ||
| THM0011708 | 2 | 2 x 20mm tubes | NT08-TT-NEF-NG25 | ||
| THM0010841 | 2 | 2 x 25mm tubes | NT08-TT-NEF-NG26 | ||
| Titan2 (NT08) double pole twin fuse cut out, complete with earth block, large 2-way extention trough, and brass plate with : | |||||
| THM0037298 | 2 | 2 x 25mm grommets | NT08-TT-NED-NG13 | ![]() |
|
| THM0037316 | 2 | 2 x 20mm tubes | NT08-TT-NED-NG25 | ||
| THM0037323 | 2 | 2 x 25mm tubes | NT08-TT-NED-NG26 | ||
| Titan2 (NT10) double pole twin fuse cut out, complete with earth block, 3-way extension trough, and brass plate, with : | |||||
| THM0027135 | 2 | 3 x 25mm tubes | NT10-NED-NEE-NT6-NG61 | ![]() |
|
| THM0012093 | 2 | 3 x 20mm grommets | NT10-NEC-NT6-NG68 | ||
| THM0010786 | 2 | 2 x 25mm grommets, 1 x 20mm grommet | NT10-NEC-NT6-NG52 | ||
Lucy Zodion Titan2
Specifications
| Specifications |
|
| Options |
|

Lucy DNO Cut Outs Offer Street Lighting Contractors Improved Cable Termination Access
Lucy Lighting Titan SLF
Single Pole Cut Outs
With its low body split line to maximise cabling access, the Lucy Lighting Titan SLF is the simplest exponent of the single pole cut outs.
Tough, engineering grade thermoplastics and fully electroplated brass componentry ensure that the Lucy SLF street lighting cut out will have a long, reliable service life.
The Lucy Zodion Titan MC040SLF cam operated fuse handle ensures that electrical disconnection takes place prior to the fuse carrier being extracted by the street lighting contractor.
Lucy Zodion MC040SLF Single Phase Cut Out Specifications
- Cut out designed and tested in accordance with BS 7654:1997
- 25A maximum fuse rating
- Accepts fuse links to BS 88 Part 1, AC 16 tag type
- IP22 rating
- Single pole isolation
- Single fuse
- Electroplated brass terminals with serrated bores
- Max. cable size; 16sqmm stranded copper, 25sqmm solid aluminium
- Cable entry via PVC grommets as standard
- Outgoing cables exit below horizontal to form drip loop
- Sealing wire facility
| Lucy Zodion Titan MC040SLF Single Phase Cut Out Dimensions | |
| Height | 150mm |
| Width | 76mm |
| Depth | 60mm |
| Order Details For MC040SLF Street Lighting Cut Out | |
| Order Code | Description |
| MC040SLF 25A SLCO TYPE 1 (SNE) | Separate Neutral and Earth |
| MC040SLF 25A SLCO TYPE 2 (CNE) | Combined Neutral and Earth |
➡ For further information about how Lucy Zodion provide control and power distribution products for street lighting applications, please review the Lucy Titan (Cut-outs) and Lucy Trojan (Isolators) ranges of products.
- Further Reading: Street Lighting Cut Outs From Lucy Zodion – WPD Approved (G81)
Complete range of LV Cable Accessories ➡
Cable Breakouts | Cable Caps | Cable Lugs | Cable Cleats | Cable Trough | Cable Duct | Feeder Pillars | for 11kV/33kV/66kV networks see MV HV Joints & Terminations

Pfisterer | Nexans Euromold | Prysmian | Cable Joints & Terminations MV HV

Cold Shrink by 3M | Joints | Abandonment | Terminations | Low Voltage LV Cables
Lead Wiping | A Disappearing Cable Jointers Skill Video Tutorial
April 16th, 2019
How to Wipe Lead Cables
Prior to Cable Jointing
-
uploaded by - Chris Dodds Thorne & Derrick Sales & Marketing Manager
Heat shrink cable joints for jointing paper or polymeric insulated cables (PILC or XLPE) with lead sheaths are specified for Low Voltage power distribution systems in the oil, gas and petrochemical industries where underground cables are exposed to waterlogging and corrosive liquids and vapours – cable construction including the lead sheath cover or jacket protects against penetration and degradation of electric cable insulation by hydrocarbon contaminants (whether underground or airborne).
Today, lead wiping has virtually disappeared from the cable jointers skill-set as more modern techniques, such as constant force spring armour and lead earthing continuity kits, which are integral to 3M hydrocarbon resistant cable joint kits have become commonplace. The modern day trend towards the manufacture and adoption of Polymeric (XLPE EPR insulated) cables has further reduced the demand for jointers with competency to work, maintain and splice using PILC type cables.
Cable Jointing & Lead Wiping
Credit: ThunderboltNZ
Lead Sheath Cutting & Removal From Paper Insulated Cables
Due to Occupational Health & Safety problems with handling lead and associated fumes, lead wiping has been replaced by jointing the cable sheaths using copper earth braid and constant force springs.

Lead Sheath Wiping
Pictured : A cable repair being conducted on a 200 pair (400 wire) lead-sheathed, paper-insulated cable (PILC). The photo illustrates the difficult conditions under which cable jointers often have to work. The gas lantern is required for both lighting and heating as it is important that the paper insulation of the individual wires do not become damp.
The joining of paper-insulated, lead-sheathed cables is not an easy task. Each 200 pair joint can take over two days to complete. The wires are identified by a colour code and are layered in a particular way: a common mistake when repairing these cables is to join pair number 1 to pair number 200 (i.e. 180 degrees out of phase). Each wire is individually joined together and covered by a paper sleeve. The photo below shows a close-up of the cable being spliced with some pairs having been joined and the remainder temporarily folded back out of the way.

Cable Splicing
LV Cable Joints (Low Voltage Cables)
Thorne & Derrick stock and distribute LV Joints in Cold Shrink, Heat Shrink or Resin Cast technologies – multicore and multi-pair cable joints are available for immediate backfill and energisation of Low Voltage power, control and instrumentation cables 600V/1000V 3.3kV.
Further Reading
- LV Cable Diversion 4 Core PILC to 4 Core Wavecon Straight Joint
- PILC Replacement & Cable Longevity
- Cable Splicing At The Lazy Q Ranch
Complete range of LV Cable Accessories ➡
Cable Breakouts | Cable Caps | Cable Lugs | Cable Cleats | Cable Trough | Cable Duct | Feeder Pillars | for 11kV/33kV/66kV networks see MV HV Joints & Terminations

Pfisterer | Nexans Euromold | Prysmian | Cable Joints & Terminations MV HV

Cold Shrink by 3M | Joints | Abandonment | Terminations | Low Voltage LV Cables
Fire Walls & Fire Risk Hazards Of Electrical Equipment – BS EN 61936-1 : 2010
April 16th, 2019BS EN 61936-1:2010 Fire Walls
The following information and clauses concerning fire walls is extracted from BS EN 61936-1:2010.
Power Installations Exceeding 1kV a.c. Common Rules
8.7 Protection Against Fire 8.7.1 General
Relevant national, provincial and local fire protection regulations shall be taken into account in the design of the installation.
NOTE: Fire hazard and fire risk of electrical equipment is separated into two categories: fire victim and fire origin.
Precautions for each category should be taken into account in the installation requirements.
- precautions to fire victim:
- space separation from origin of fire;
- flame propagation prevention:
physical layout of the substation,
liquid containment,
fire barriers (e.g. REI fire-resistant materials 60/90),
extinguishing system;
- precautions to fire origin:
- electrical protection;
- thermal protection;
- pressure protection;
- fire resistant materials.
Care shall be taken that, in the event of fire, the escape and rescue paths and the emergency exits can be used (see 7.1.6).
The user or owner of the installation shall specify any requirement for fire extinguishing equipment. Automatic devices to protect against equipment burning due to severe overheating, overloading and faults (internal/external) shall be provided, depending on the size and significance of the installation.
Equipment in which there is a potential for sparks, arcing, explosion or high temperature, for example electrical machines, transformers, resistors, switches and fuses, shall not be used in operating areas subject to fire hazard unless the construction of this equipment is such that flammable materials cannot be ignited by them.
If this cannot be ensured, special precautions, for example fire walls, fire-resistant separations, vaults, enclosures and containment, are necessary.
Consideration should be given to separating different sections of switchgear by fire walls. This can be achieved by means of bus ducts which penetrate the fire wall and which connect the sections of the switchgear together.
8.7.2 Transformers, Reactors
In the following sub-clauses, the word ‘transformer’ represents ‘transformers and reactors’.
For the identification of coolant types, see 6.2.2.IEC 61100 classifies insulating liquids and transformer oils according to:fire point and net caloric value (heat of combustion).
Three classes have been defined:
Class O, if the fire-point is less than or equal to 300 °C. (e.g Mineral Oil).
Class K, if the fire-point is above 300 °C. (e.g MIDEL 7131 and MIDEL eN 1024).
Class L, if the insulating liquid has no measurable fire-point.(e.g. Xiameter PMX-561).
IEC 60076-11 classifies dry-type transformers in terms of their behaviour when exposed to fire. The fire hazard associated with transformers of outdoor and indoor installations is dependent on the rating of the equipment, the volume and type of insulating mediums, the type and proximity and exposure of nearby equipment and structures.
The use of one or more recognized safeguard measures shall be used in accordance with the evaluation of the risk.
♦ IEC 60076-11:2018 Power Transformers – Part 11: Dry-type Transformers
NOTE: For definition of risk, see ISO/IEC Guide 51.
Common sumps or catchment tanks, if required, for several transformers shall be arranged so that a fire in one transformer cannot spread to another. The same applies to individual sumps which are connected to the catchment tanks of other transformers; gravel layers or pipes filled with fluid can, for example, be used for this purpose.
Arrangements which tend to minimize the fire hazard of the escaped fluid are preferred.
8.7.2.1 Outdoor Transformer Installations
The layout of an outdoor installation shall be such that burning of a transformer with a liquid volume of more than 1,000 litres will not cause a fire hazard to other transformers or objects, with the exception of those directly associated with the transformer. For this purpose, adequate clearances, G, shall be necessary.
Guide values are given in Table 3. Where transformers with a liquid volume below 1,000 litres are installed near combustible walls, special fire precautions may be necessary, depending on the nature and the use of the building.
If automatically activated fire extinguishing equipment is installed, the clearance G can be reduced.
If it is not possible to allow for adequate clearance as indicated in Table 3, fire-resistant separating walls with the following dimensions shall be provided:-
a) between transformers (see Figure 6) separating walls. For example EI 60 in accordance with the Official Journal of the European Community, No. C 62/23:
height: top of the expansion chamber (if any), otherwise the top of the transformer tank;
length: width or length of the sump (in the case of a dry-type transformer, the width or length of the transformer, depending upon the direction of the transformer);
b) between transformers and buildings separating walls. For example EI 60; if additional fire separating wall is not provided, fire rating of the building wall should be increased, for example REI 90 (see Figure 7) in accordance with the Official Journal of the European Community C 62/23.
Table 3 – Guide Values For Outdoor Transformer Clearances
| Transformer Type | Liquid Volume | Clearance G to | ||
| Other transformers or non-combustible building surface (m) | Combustible building surface (m) | |||
| Oil insulated transformers (O) | 1000 <…..< 2000 | 3 | 7.5 | |
| 2000 <…..< 20000 | 5 | 10 | ||
| 20000 <…..< 45000 | 10 | 20 | ||
| < 45000 | 15 | 30 | ||
| Less flammable liquid insulated transformers (K) without enhanced protection | 1000 <…..< 2000 | 1.5 | 7.5 | |
| ≥3800 | 4.5 | 15 | ||
| Clearance G to building surface or adjacent transformers | ||||
| Less flammable liquid insulated transformers (K) without enhanced protection | Horizontal (m) | Vertical (m) | ||
| 0.9 | 1.5 | |||
| Dry-type transformers (A) | Fire behaviour class | Clearance G to building surface or adjacent transformers | ||
| Horizontal (m) | Vertical (m) | |||
| F0 | 1.5 | 3.0 | ||
| F1 | None | None | ||
NOTE 1: Enhanced protection means:
- tank rupture strength
- tank pressure relief
- low-current fault protection
- high-current fault protection
For an example of enhanced protection, see Factory Global standard 3990 (33) or equivalent.
NOTE 2: Sufficient space should be allowed for periodic cleaning of resin-encapsulated transformer windings, in order to prevent possible electrical faults and fire hazard caused by deposited atmospheric pollution.
Three classes have been defined:
Class O, if the fire-point is less than or equal to 300 °C. (e.g Mineral Oil)
Class K, if the fire-point is above 300 °C. (e.g MIDEL 7131 and MIDEL eN 1024)
Class L, if the insulating liquid has no measurable fire-point.(e.g. Xiameter PMX-561)
8.7.2.2 Indoor Transformer Installation In Closed Electrical Operating Areas
Minimum requirements for the installation of indoor transformers are given in Table 4.
Table 4 – Minimum Requirements For The Installation Of Indoor Transformers
| Transformer Type | Class | Safeguards |
| Liquid Volume | ||
| ≤ 1000 I | El 60 respectively REI 60 | |
| ≤ 1000 I | El 90 respectively REI 90 or El 60 respectively REI 60 and automatic sprinkler protection | |
| Less flammable liquid insulted transformers (K) | Nominal power/max | |
| Without enhanced protection | (no restriction) | El 60 respectively REI 60 or automatic sprinkler protection |
| With enhanced protection | ≤ 10 MVA and UM ≤ 38 kV | El 60 respectively REI 60 or separation distances 1.5m horizontally and 1.5m vertically |
| Dry-type transformer (A) | Fire behaviour | |
| F0 | El 60 respectively REI 60 or separation distances 0.9m horizontally and 1.5m vertically | |
| F1 | Non combustible walls | |
NOTE 1: REI represents the bearing system (wall) whereas El represents the non-load bearing system (wall) where R is the load bearing capacity, E is the fire integrity, I is the thermal insulation and 60/90 refers to time in minutes.
NOTE 2: Enhanced protection means:
- tank rupture strength
- tank pressure relief
- low-current fault protection
- high-current fault protection
For an example of enhanced protection, see Factory Global standard 3990 (33) or equivalent.
NOTE 3: Sufficient space should be allowed for periodic cleaning of resin-encapsulated transformer windings, in order to prevent possible electrical faults and fire hazards caused by deposited atmospheric pollution.
Doors shall have a fire resistance of at least 60 min. Doors which open to the outside are adequate if they are of low flammability material. Ventilation openings necessary for the operation of the transformers are permitted in the doors or in adjacent walls. When designing the openings, the possible escape of hot gases shall be considered.
8.7.2.3 Indoor Transformer Installations In Industrial Buildings
For all transformers in industrial buildings, fast-acting protective devices which provide immediate automatic interruption in the event of failure are necessary.
Transformers with coolant type O require the same provisions as in 8.7.2.2.
For all other liquid-immersed transformers, no special arrangements in respect of fire.
protection are required, except for the provisions for liquid retention in case of leakage and the provision of portable fire extinguishing apparatus suitable for electrical equipment.
Dry-type transformers (A) require the selection of the correct fire behaviour class depending on the activity of the industry and on the material present in the surroundings. Fire extinguishing provisions are advisable, particularly for class F0.
NOTE: For all transformers in industrial buildings, additional fire precautions may be necessary, depending on the nature and use of the building.
8.7.2.4 Indoor Installations In Buildings Which Are Permanently Occupied By Persons
In high-voltage installations, located in public or residential buildings, special conditions shall be observed in accordance with existing standards or national regulations.
8.7.2.5 Fire in the vicinity of transformers
If there is an exceptional risk of the transformer being exposed to external fire, consideration shall be given to
- fire-resistant separating walls;
- gas-tight vessels capable of withstanding the internal pressure generated;
- controlled release of the hot liquid; fire extinguishing systems.
8.7.3 Cables
The danger of the spread of fire and its consequences shall be reduced, as far as possible, by selecting suitable cables and by the method of installation.
The cables may be assessed by reference to the following categories:
- cables without particular fire performance characteristics;
- cables (single) with resistance to flame propagation (IEC 60332 series);
- cables (bunched) with resistance to flame propagation (IEC 60332 series);
- cables with low emission of smoke (IEC 61034-1);
- cables with low emission of acidic and corrosive gases (IEC 60754-1 and IEC 60754-2);
- cables with fire-resisting characteristics (IEC 60331-21 or IEC 60331-1).
Cables in trenches and buildings shall be laid in such a way that the regulations regarding fire safety of the building are not adversely affected. For example, to avoid fire propagation, holes or cable ducts through which the cables go from one room to another shall be sealed with suitable fire proof and resistant material.
A physical separation or different routing of power circuits from the control circuits for high voltage equipment is recommended if it is necessary to preserve the integrity of the latter as long as possible following damage to the power circuits.
Where necessary, a fire alarm and fire extinguishing systems shall be installed in cable tunnels and in cable racks in the basement of control buildings.
8.7.4 Other Equipment With Flammable Liquid
For all equipment, such as switchgear which contains more than 100 l of flammable liquid in each separate compartment, special fire precautions as specified for transformers may be necessary, depending on the nature and use of the installation and its location.
Figure 6 – Separating Walls Between Transformers

Figure 7 – Fire Protection Between Transformer & Building

Key
For Clearance G. see Table 3
a) The wall in this area shall be designed to avoid a spread of fire
Further Reading
Transformer Oils – 11kV 33kV 66kV Substation Transformer Oil Refilling, Sampling & Analysis
Utilising Distribution Transformers To Optimise Solar
11kV Transformers | Introducing Amorphous Core HV Transformers
VIDEO How To Verify Total Absence of Voltage By The Push Of a Button
THORNE & DERRICK SPECIALIST ELECTRICAL DISTRIBUTOR
The 11kV Specialists
Thorne & Derrick distribute the most extensive range of 11kV Cable Jointing, Terminating, Pulling & Installation Equipment – we service UK and international clients working on underground cables, overhead lines, substations and electrical construction at 11kV and up to and EHV transmission and distribution voltages.
- Key 11kV Products: MV-HV Cable Joints & Terminations, Cable Cleats, Duct Seals, Cable Transits, Underground Cable Protection, Copper Earth Tapes, Cable Jointing Tools, Feeder Pillars, Cable Ducting, Earthing & Lightning Protection, Electrical Safety, Cable Glands, Arc Flash Protection & Fusegear.
- Distributors for: 3M Cold Shrink, ABB, Alroc, Band-It, Catu, Cembre, Centriforce, CMP, Elastimold, Ellis Patents, Emtelle, Furse, Lucy Zodion, Nexans Euromold, Panduit, Pfisterer, Polypipe, Prysmian, Roxtec.

LV – Low Voltage Cable Joints, Glands, Cleats, Lugs & Accessories (1000 Volts)

MV HV – Medium & High Voltage Cable Joints, Terminations & Connectors (11kV 33kV EHV)

Cable Laying – Underground Cable Covers, Ducting, Seals & Cable Pulling Equipment

T&D, CATU Electrical Safety & Arc Flash Protection Specialists for SAP’s, Linesmen, Jointers & Electrical Engineers – Largest UK Stockist
ALVIN by EA Technology | Identify LV Electrical Equipment Faults
April 15th, 2019
ALVIN by EA Technology – Identifying Low Voltage Electrical Equipment Faults
Uploaded by Chris Dodds – Thorne & Derrick Sales & Marketing Manager
ALVIN Reclose by EA Technology – Low Voltage Fault Detection
ALVIN (Automatic Low Voltage Intelligent Network) is an intelligent network technology developed by EA Technology. It helps electricity network operators identify faults, analyse electrical disturbances and restore supplies.
Finding intermittent faults on low voltage networks can be difficult. However, accurate fault information helps engineers locate problems and reduce lengthy investigations.
For this reason, EA Technology developed ALVIN Reclose to combine fault detection with automatic supply restoration.
In addition, the equipment provides diagnostic information that supports maintenance decisions and network planning.
Consequently, ALVIN can help Distribution Network Operators improve customer service while managing ageing electrical infrastructure.
What Is ALVIN Reclose?
ALVIN Reclose is an automatic low voltage network device designed to detect faults and support electricity supply restoration.
The system combines switching, monitoring and diagnostic functions within a compact unit.
Unlike conventional protective devices, ALVIN can record electrical conditions associated with intermittent faults. Furthermore, it supports automatic restoration following suitable fault events.
As a result, network operators can investigate developing electrical problems while reducing certain manual interventions.
The device also provides a foundation for additional network automation and communication functions.
Supporting Low Voltage Network Reliability
Electricity distribution networks contain equipment that may remain in service for many years.
Over time, ageing cables and electrical connections can develop intermittent faults. These disturbances may affect customers without immediately causing a permanent outage.
However, identifying the underlying cause can require repeated site investigations.
ALVIN provides additional information about these events. Consequently, engineers can analyse electrical conditions and investigate likely fault locations more effectively.
In addition, automatic reclose functionality can support restoration where operating conditions permit.

ALVIN Reclose
ALVIN Reclose – Western Power Distribution Case Study
Western Power Distribution (WPD) used ALVIN equipment to investigate intermittent faults on its low voltage electricity networks.
At the time of the case study, Steve Weddell was the Stoke Plant Team Manager at WPD.
His team used ALVIN when conventional equipment could not identify the cause of recurring electrical disturbances.
In addition, the device provided power quality information that helped engineers understand underlying network problems.
Identifying Intermittent LV Cable Faults
Intermittent faults can be difficult to locate because electrical conditions may return to normal before an engineer arrives.
For example, a temporary cable fault may cause a brief disturbance without operating the network fuse.
Consequently, conventional investigations may not capture enough information to identify the cause.
ALVIN records electrical measurements during these events. As a result, engineers can review fault activity and investigate the affected network more effectively.
Steve Weddell’s team worked closely with EA Technology for approximately 12 months.
According to the original case study, the team reported a 100% success rate in detecting issues on the known problem circuits where ALVIN was deployed.
This result reflected the team’s reported project experience rather than a guaranteed detection rate for every installation.

Western Power Distribution Using ALVIN on Intermittent Faults
ALVIN Fault Detection – Alrewas Case Study
Stoke Engineering Specialist David Phillips described an example of ALVIN fault detection in Alrewas.
In early 2018, Western Power Distribution received reports of flickering lights in the area.
Initially, engineers installed power quality monitoring devices to investigate the disturbance. However, the equipment did not identify a meaningful cause.
As a result, the electrical problem continued for several months.
Using ALVIN to Locate the Electrical Fault
During a visit to EA Technology, David Phillips and a colleague discussed the ongoing problem.
They subsequently decided to install ALVIN as an investigation tool.
According to the case study, the device identified the problem immediately after installation.
Furthermore, engineers were able to rectify the electrical fault within two days.
This example demonstrates how additional network monitoring information can help engineers investigate difficult intermittent faults.
Recording Voltage and Current Waveforms
ALVIN records voltage and current waveforms associated with brief electrical faults.
Some disturbances clear automatically before a conventional fuse operates. Therefore, they may be difficult to detect using traditional equipment.
However, the recorded waveforms provide information about the electrical conditions during these events.
As a result, engineers can examine the characteristics of repeated faults and investigate possible causes.
How Does ALVIN Reclose Work?
ALVIN Reclose is designed to fit within a standard low voltage fuse holder arrangement.
When the device detects a qualifying fault, it disconnects the affected circuit.
Following the interruption, the device waits for approximately 30 seconds before attempting to reclose.
If the relevant operating conditions are satisfied, the circuit can then be reconnected.
Consequently, certain temporary fault events can be cleared without requiring manual supply restoration.
However, automatic restoration depends on the device configuration, fault characteristics and applicable operating requirements.
Automatic Supply Restoration
The automatic reclose function is intended to support continuity of electricity supply.
For example, some transient electrical disturbances may disappear after a brief interruption.
In these situations, ALVIN can attempt to restore the circuit automatically.
Furthermore, its monitoring functions provide diagnostic information about the recorded event.
As a result, network operators can combine supply restoration with fault investigation.
EA Technology LV Cloud Monitoring
In 2017, EA Technology introduced an LV Cloud data service for low voltage network monitoring.
The service allowed users to access voltage and current waveform information.
In addition, it supported the analysis of recorded fault events and associated network conditions.
Consequently, engineers could examine electrical disturbances without relying solely on observations made during site visits.

Identifying LV Electrical Equipment Faults with ALVIN
ALVIN Deployment Across Nottingham and Stoke
Western Power Distribution had been using several ALVIN units since 2016.
According to the case study, the company later purchased communications equipment to connect the devices to LV Cloud.
The units were distributed between its Nottingham and Stoke depots.
As a result, engineers could deploy ALVIN systems to investigate problematic low voltage circuits across different locations.
Furthermore, the communications equipment helped users access recorded information for fault analysis.
Monitoring Pre-Fault Electrical Activity
David Phillips explained that ALVIN captured waveform data associated with electrical disturbances.
In addition, the system could confirm the status of customer supplies through text or email notifications.
The frequency and severity of pre-fault activity provided further diagnostic information.
For example, repeated disturbances could suggest a developing fault or a possible interruption to customer supplies.
Furthermore, this information could help engineers decide when additional investigations were worthwhile.
These investigations might include thermal checks or methods used to detect gases associated with cable faults.
Consequently, monitoring data could help teams focus their attention on suspected problem areas.
David also highlighted the equipment’s versatility and WPD’s continued collaboration with EA Technology on further development.

ALVIN Reclose
ALVIN Reclose – Business Benefits
ALVIN Reclose combines electrical fault detection with automatic network restoration capabilities.
As a result, it offers several potential benefits for electricity distribution network operators.
- Transient fault detection: Identifies temporary electrical disturbances and overload events.
- Automatic restoration: Supports supply restoration without manual intervention for suitable faults.
- Reduced investigation time: Provides information that can help engineers locate intermittent problems.
- Retrofit installation: Designed for installation within compatible existing low voltage fuse holders.
- Future adaptability: Supports additional communication and monitoring functions.
- Improved asset management: Provides diagnostic information for maintenance planning.
- Network reliability: Helps operators manage fault activity and improve customer service.
- Operational efficiency: Can reduce engineering time associated with certain fault investigations.
Furthermore, the system provides information that may help operators understand recurring faults.
Consequently, maintenance teams can use recorded events to support more informed decisions.
ALVIN Automatic Low Voltage Intelligent Network Features
The ALVIN Reclose system combines switching, monitoring and diagnostic functions within one device.
Its original product features include:
- Automatic clearing of suitable transient and overload faults.
- Supply restoration without manual intervention where conditions permit.
- Integrated testing and switching functions.
- SafeON technology for controlled power restoration.
- Self-contained construction without auxiliary components for basic operation.
- Network analysis and diagnostic information through an external data port.
- Support for future communication and monitoring accessories.
- Arc-less switching functionality for network protection.
- Retrofit compatibility with suitable 92mm fuse holders.
- Factory programming for different customer requirements.
- Training and technical support.
In addition, the device provides electrical measurements that can support network condition monitoring.
Therefore, ALVIN offers both immediate protection functions and opportunities for wider network analysis.
SafeON Technology
ALVIN incorporates SafeON technology to support controlled restoration of electricity supplies.
This feature is designed to limit current when making onto a faulty cable.
According to the original technical specification, SafeON provides current limiting to 2.4kA.
Consequently, it forms part of the device’s protective switching arrangement.
ALVIN Reclose Technical Specifications
The following table summarises the electrical ratings and monitoring capabilities included in the original ALVIN technical specification.
However, specifications may differ between product versions. Therefore, the relevant manufacturer documentation should be checked before equipment selection.
| Technical Specification | Rating / Performance |
| Rated Operating Voltage | 275V phase to neutral on either pole; 440V across poles |
| Rated Insulation Voltage | 690V |
| Rated Operating Current | 400A or 500A as thump option for ALVIN RecloseIT version |
| Operating Frequency | 50Hz |
| Rated Making Capacity | 80kA |
| Rated Breaking Capacity | 80kA |
| Overcurrent Trip Characteristic | Inverse time based on 315A and 400A BS88-2 It zones |
| Ambient Air Temperature | -25°C to +45°C |
| Operating Cycles | 1,000 |
| Voltage Measurement | ±1.5%, 50V to 253V AC RMS |
| Current Measurement | ±1% above 200A; ±2A at or below 200A |
| Harmonic Monitoring | Yes |
| Directional Fault Indicators | Yes |
| Fault Location Ready | Yes |
| Making on Faulty Cable | SafeON with current limiting to 2.4kA |
| Standards Applied | IEC 60947-2, IEC 61000, IEC 60255 |
Understanding the Electrical Ratings
The device’s rated operating voltage and current define its specified electrical operating limits.
In addition, the rated making and breaking capacities describe its switching capabilities under defined conditions.
The original specification lists an 80kA making capacity and an 80kA breaking capacity.
Furthermore, voltage and current measurement functions provide data for electrical network analysis.
These measurements can help operators investigate load conditions and fault activity.
However, suitability must be confirmed against the complete technical specification and the network’s protection requirements.
About EA Technology
EA Technology provides specialist power engineering products and services for electricity networks.
Its activities include engineering consultancy, electrical monitoring instruments and technical training.
In addition, the company supports utilities with technology for fault detection and network condition assessment.
These services help organisations investigate electrical problems and improve their understanding of network performance.
Consequently, EA Technology’s products and expertise support the operation and maintenance of electrical infrastructure.

Thorne & Derrick – Specialist Electrical Distributors
Established in 1985, Thorne & Derrick supply specialist electrical equipment for cable installation, jointing and power distribution.
Our range supports LV, MV and HV electrical networks across the UK and international markets.
In addition, we supply cable accessories and installation tools for utilities, contractors and industrial applications.
Customers can contact our team for product information, technical assistance and quotations.
Electrical Equipment and Cable Accessories
Thorne & Derrick supply an extensive range of electrical installation and maintenance products.
- MV and HV Cable Joints and Terminations
- Cable Cleats
- Cable Duct Seals
- Cable Transits
- Cable Jointing Tools
- Electrical Feeder Pillars
- Cable Pulling and Installation Equipment
- Earthing and Lightning Protection
- Electrical Safety Equipment
- Cable Glands
- Arc Flash Clothing and Protection
Leading Electrical Manufacturers
We supply products from established manufacturers across the electrical industry.
These include 3M, Pfisterer, Nexans Euromold, Elastimold, CATU, Roxtec, Cembre, Ellis Patents and ABB.
Explore selected specialist ranges:
- Pfisterer CONNEX Connectors
- Elastimold Cable Accessories
- Lucy Zodion Electrical Equipment
- Cembre Tools and Cable Lugs
- Ellis Patents Cable Cleats
- Furse Earthing and Lightning Protection
Furthermore, our product range supports electrical network construction, cable preparation and substation maintenance.
Contact Thorne & Derrick to discuss your electrical equipment requirements or request a quotation.

Thorne & Derrick – Cable Jointer Training Courses with Pfisterer CONNEX and Nexans Euromold












➡ James Hoare (LHW Partnership – Electrical & Energy Engineers). I thought the only way to get round was outdoor enclosure with class C or cast resin – when cast resin were first coming in they were welcome in buildings as an alternative to MIDEL as no need to bund the transformer.
➡ Neil Denbow (Director at Eden Transformer Oil). James, Class K insulating liquids such as the MIDEL range have the higher fire protection and are also readily biodegradable (unlike oil). However BS EN 61936-1:2010 doesn’t distinguish between the different liquids. By the way, as MIDEL Service Partners, we offer a mineral oil to MIDEL 7131 retrofill service.
➡ James Hoare (LHW Partnership – Electrical & Energy Engineers). Neil – thank you – I used to work for GEC many …moons ago and we used to make distribution transformers dry and liquid – in those days Midel was a GEC group company so know it well . GEC became Alstom and think it’s now Schneider at this volts !!!
➡ Carl A. Watkin Neil, can you directly replace oil with MIDEL, one for one? I was told by Schneider that retrofit would involve fitting larger rads to the transformer as the volume of Midel required, per transformer KVA unit, to achieve the same cooling properties was higher?