UK Power Networks, UKPN, are a UK Distribution Network Operator distributing low and high voltage electricity covering South East England, the East of England and London –  we overview current UKPN recommendations and specifications for Cable Protection Tapes & Covers using Tile Tape and Stokbord cable protection products.
Note these are subject to change: check with Thorne & Derrick Sales.
This should assist LV-HV Cable Jointing, Installation & Civil Engineering Contractors installing the appropriate level of LV-HV Cable Protection for underground power cables.
T&D are Approved Vendors to UKPN and their contractors providing competitive prices and technical support for LV, MV & HV Cable Installation, Jointing, Substation & Electrical Equipment including low voltage electrical distribution feeder pillars manufactured by Lucy Zodion from the Fortress range.
All cables and cable ducts shall be protected by a cable protection tape or a Stokbord, the tape used depends upon the highest cable voltage to be protected:
- LV Service Cables – Tile Tape (40m x 200mm x 2.5mm) – UKPN Stores Code = 04040C
- LV Mains Cables – Tile Tape (40m x 200mm x 2.5mm) – UKPN Stores Code = 04040C
- 11kV MV Cables  – Tile Tape (40m x 200mm x 2.5mm) – UKPN Stores Code = 04040C
- 22kV MV Cables  – Tile Tape (40m x 200mm x 2.5mm) – UKPN Stores Code = 04040C
- 33kV MV Cables – Stokbord (1000mm x 244mm x 9mm) – UKPN Stores Code = 04041M
- 66kV HV Cables – Stokbord (1000mm x 244mm x 9mm) – UKPN Stores Code = 04041M
- 132kV HV Cables – Stokbord (1000mm x 244mm x 9mm) – UKPN Stores Code = 04041M
Cable protection tape or covers shall be installed so that they fully cover the width of the cable or cable duct installed below them.
- Excerpt from UKPN Engineering Construction Standard ECS 02-0019
- Installation of Underground Cables – LV to 132kV
- Document Number: ECS 02-0019
- Version: 10.0
- Date: 02/06/2015
Summary: The ECS 02-0019 Standard details the minimum requirements acceptable for the installation of new LV, 11kV, 20kV, 33kV, 66kV and 132kV cables plus associated pilot and telephone cables.
âž¡ View our complete range of LV-HV Cable Protection.
Cable Pulling & Laying Equipment LV HV
T&D supply Utilities & Approved Contractors with cable pulling products including cable rollers, cable socks and drum lifting jacks to enable the installation of low voltage and high voltage cables intro trench or duct: this includes single core, 3 core and Triplex 11kV/33kV power cables and LV waveform, mains and service cables.