3M Wraparound Heat Shrink Cable Repair Kits Used For LV HV Mining Cable Sheaths
February 7th, 2019
Heat Shrink Wraparound Cable Sheath Repair & Jacketing Sleeves – 3M HDCW
Uploaded by Chris Dodds – Thorne & Derrick Sales & Marketing Manager
3M HDCW Wraparound Heat Shrink Cable Repair Kits
3M HDCW heat shrink wraparound sleeves provide a practical solution for damaged cable sheaths and jackets. They help restore cable insulation and protect exposed areas from moisture and corrosion.
These sleeves form part of a wider range of cable repair solutions. Other options include heat shrink and 3M Scotch electrical tapes, as well as Cold Shrink products and resin-based repair systems using 3M Scotchcast.
Installers can also use these sleeves with cable joints. In addition, they provide extra corrosion protection for undamaged cables.
Thorne & Derrick supply 3M Heat Shrink Cable Repair Kits to the mining industry. These kits help restore insulation on damaged low and high voltage cable sheaths. Common causes of damage include mechanical stress, third-party accidents and cable corrosion, particularly in damp underground mining environments.

Image: International Banker
3M Wraparound Heat Shrink Cable Repair Sleeves
3M wraparound heat shrink sleeves provide a quick way to repair damaged cable jackets. They also protect cable joints and splices. Furthermore, installers can use them as an additional corrosion protection layer.
The sleeves suit demanding environments, including hazardous areas and underground or surface mining installations.
How 3M HDCW Sleeves Work
3M HDCW sleeves use modified cross-linked polyolefin. The inner surface features a hot-melt adhesive coating.
During installation, heat causes the sleeve to shrink around the cable. At the same time, the adhesive melts and bonds the sleeve to the cable sheath. This creates a secure, watertight seal.
A corrosion-resistant metal clip then closes the sleeve and holds it in position.
The wraparound design also allows installers to repair cable jackets and re-jacket in-line cable splices. As a result, they can carry out repairs without needing access to an open cable end.
Voltage Applications and Installation
3M HDCW wraparound sleeves provide insulation for cables and splices up to 1000 volts. They can also repair cable jackets on cables up to 35kV.
Furthermore, the wraparound design makes installation easier in restricted spaces. Installers can use standard heating equipment, such as a heat shrink torch.
Thorne & Derrick International are the UK’s largest stockist of 3M Electrical Cable Accessories.

Mining Cable Repair Solutions
We supply cable repair kits for BS6708 underground mining cables. These include the following cable types:
- Type 11
- Type 7, Type 7S and Type 7M
- Type 307, Type 307S and Type 307M flexible trailing cables for coalcutters and similar face equipment
- Type 211
- Type 201
- Type 62
- Type 63
- Type 64
- Type 321
- Type 331 flexible trailing cables with galvanised steel wire pliable wire armouring, used as mine extension cables in quarries and coalface lighting
3M HDCW Wraparound Sleeve Features and Benefits
3M HDCW sleeves offer several benefits for cable repair and protection:
- Quick and easy installation.
- A cost-efficient cable repair solution.
- Thick-wall heat shrink material for strength and durability.
- A wraparound design that allows repairs without opening the cable.
- Strong bonding to PE and PVC cable sheaths and jackets.
- Protection against mechanical stress.
- Resistance to harsh and hazardous environments.
- A sealed finish that helps prevent moisture entering damaged cables.
How to Install 3M Wraparound Cable Repair Sleeves
Installers can follow three main steps to fit a 3M HDCW wraparound sleeve:
- Position the sleeve: Place the heat shrink sleeve over the damaged cable section, joint or splice. Then close the metal channel to secure the sleeve.
- Apply heat: Use a suitable heat shrink gas torch to shrink the sleeve around the cable sheath. The heat also melts the adhesive liner.
- Allow the sleeve to cool: Once the sleeve has cooled, the adhesive forms a moisture-resistant and corrosion-resistant seal.

Cable Repair Sleeves – Installation
3M HDCW Heat Shrink Wraparound Repair Sleeve Specifications
The table below shows the available 3M HDCW repair kits, including their lengths, conductor sizes and sleeve dimensions.
Heat Shrink Wraparound Repair Sleeves
| 3M Cable Repair Kit Part Number | Length Inches (Metres) | Primary Insulation 600/1000V Conductor Size AWG/MCM | Jacket Repair Use Range max./min inches (mm) | Sleeve Dimensions | |
| Expanded Diameter inches (mm) | Recovered Diameter inches (mm) | ||||
| HDCW 35/10-250 HDCW 35/10-1200 |
9.8 (250) 47.2 (1200) |
#8-2/0 #8-2/0 |
1.38-0.39 (35-10) 1.38-0.39 (35-10) |
1.97 (50) 1.97 (50) |
0.32 (8) 0.32 (8) |
| HDCW 55/10-500 HDCW 35/10-1200 |
19.7 (500) 47.2 (1200) |
3/0-400 3/0-400 |
2.17-0.59 (55-15) 2.17-0.59 (55-15) |
2.95 (75) 2.95 (75) |
0.51 (13) 0.51 (13) |
| HDCW 80/25-750 HDCW 80/25-1200 |
29.5 (750) 47.2 (1200) |
500-1000 500-1000 |
3.15-0.98 (80-25) 3.15-0.98 (80-25) |
3.94 (100) 3.94 (100) |
0.91 (25) 0.91 (25) |
| HDCW 110/30-1000 HDCW 110/30-1200 |
39.4 (1000) 47.2 (1200) |
1000-2000 1000-2000 |
4.33-1.18 (110-30) 4.33-1.18 (110-30) |
5.20 (132) 5.20 (132) |
0.98 (25) 0.98 (25) |
| HDCW 140/40-1000 HDCW 140/40-1200 |
39.4 (1000) 47.2 (1200) |
N/A N/A |
5.51-1.57 (140-40) 5.51-1.57 (140-40) |
5.71 (145) 5.71 (145) |
1.26 (32) 1.26 (32) |
3M HDCW Series Dimensions

| 3M HDCW Cable Repair Kit Part Number | H/mm | F/mm | T/mm |
| HDCW 35/10 | 155 | 18 | 0.9 |
| HDCW 55/15 | 175 | 18 | 0.9 |
| HDCW 80/25 | 260 | 30 | 0.9 |
| HDCW 110/30 | 355 | 30 | 0.9 |
| HDCW 140/40 | 455 | 30 | 0.9 |
Cold Shrink Cable Repair
Some hazardous area locations do not permit hot-working because flammable gases may be present. In these situations, Cold Shrink tubes may provide an alternative for cable repair.
However, installers must have access to the open end of the cable circuit. Cold Shrink tubes are not suitable for repairing cables mid-circuit or mid-span unless the cable can be isolated, uncoupled and disconnected from the mains power supply.
For flexible cable repairs, we can also supply 3M Scotchcast resin-based solutions. These products are specified for marine and offshore applications. They offer resistance to seawater, submersion and exposure.
Read more: Repairing Damaged Cables, Cable Sheath & Jackets

3M HDCW – Heat Shrink Wraparound Cable Sheath Repair & Jacketing Sleeves
3M Cable Accessories and Technical Support
Need help selecting or specifying cable accessories? Contact Thorne & Derrick for customer service and technical support across LV, MV and HV applications.
Our team can help you explore the following products and solutions:

3M Cold Shrink
LV Cable Joints – Low Voltage Cables
Thorne & Derrick stock and distribute a wide range of low voltage cable joints. Our range includes Cold Shrink, Heat Shrink and resin cast technologies.
We supply multicore and multi-pair cable joints for power, control and instrumentation cables. These products support applications at 600V, 1000V and 3.3kV, with options for immediate backfill and energisation where suitable.
Explore our LV cable accessories:
Cable Breakouts |
Cable Caps |
Cable Lugs |
Cable Cleats |
Cable Trough |
Cable Duct |
Feeder Pillars
For 11kV, 33kV and 66kV networks, explore our MV and HV cable joints and terminations.

Pfisterer | Nexans Euromold | Prysmian | Cable Joints & Terminations MV HV

Cold Shrink by 3M | Joints | Abandonment | Terminations | Low Voltage LV Cables
Fireproof Cable Joints For BS7846 Fireproof Mains & Control Cables (LSZH)
February 7th, 2019
-
uploaded by Chris Dodds - Thorne & Derrick Sales & Marketing Manager
BS7846 Cables
Thorne & Derrick International distribute fireproof cable joints for LV Low Voltage fire resistant armoured (SWA) power cables to British Standards BS6387 and BS7846.
The BS7846 British Standard enhanced fire performance cable is specified for fire alarms and emergency lighting in both indoor and outdoor installations – general fire resistant power cables are used to protect emergency plant including sprinkler pumps, smoke extractors and fire dampers.
The British Standards
BS6387:2013 : Test Method For Resistance To Fire Of Cables Required To Maintain Circuit Integrity Under Fire Conditions.
BS 7846:2015 : Electric Cables. Thermosetting Insulated, Armoured, Fire-Resistant Cables Of Rated Voltage 600/1000 V For Fixed Installations (having low emission of smoke and corrosive gases when affected by fire).
BS7846 Cable Construction
| Conductor | Annealed plain or tinned copper (Class 2) |
| Insulation | GP6 or GP8 with levels of HCI no greater than 0.5% |
| Bedding | Polymeric materials with levels of HCI no greater than 0.5% |
| Armour | Galvanised steel wires or galvanised interlocking steel tape |
| Outersheath | Polymeric material conforming to the requirements for LTS 1 contained in BS7655-6.1 |
BS7846 Cable Core Identification
| Number of Cores | Identification |
| Two-core | Brown and blue |
| Three-core | Brown, black and grey |
| Four-core | Blue, brown, black and grey |
| Five-core | Green and yellow, blue, brown, black and grey |
BS7846 Cable Fire Resistance Categories
The cables under the British Standard are categorised according to their special fire resistance characteristics:
| F2 | Resistance to fire, resistance wear, resistance to fire with mechanical shock, assessed separately when tested in accordance with this Standard |
| F30 | Resistance to fire with direct mechanical impact and fire assessed in combination for 30mins when tested in accordance with British Standard BS8491 for 30mins |
| F60 | As per F30 for 60mins |
| F120 | As per F30 for 120mins |
Fire Resistant Armoured Power Cable For Essential Services


BS7846 fire resistant cable manufactured by Prysmian features a plain annealed stranded copper conductor, XLPE insulation, MICA fire resistant tape, polyester tape low smoke zero halogen bedding, fire barrier tape and black low smoke zero halogen outer sheath with a galvanised steel wired armour (SWA).
Low smoke zero halogen (LSZH) heat shrink cable joints with additional fireproof or fire resistant properties are available – typically used to connect, repair or joint Prysmian FP600S or Prysmian FP400 cables. The cable joints feature low smoke and corrosive gas emissions (LSOH) and are moisture resistant with LUL Approvals.
See also : Low Smoke Zero Halogen (LSOH) Cable Accessories
- BS6387/BS7846 Cable Enhanced Fireproof Mains Cable
2, 3 & 4 Core 4sqmm – 400sqmm. Plain annealed stranded copper conductor, mica fire resistant tape, XLPE insulated, polyester tape, low smoke zero halogen (LSZH) bedding, fire barrier tape, galvanised steel wire armour, low smoke zero halogen (LSZH) outer sheath. Sheath Colour Black. 600/1000 grade volts.
Manufactured to meet the following standards – circuit integrity: BS8519-2010 120 minutes/BS8491, acid gas emission to IEC 60754, BS EN 50267, flame propagation to IEC 60332-3, BS EN 50265, BS EN50266 and smoke emission to IEC 61034, BS EN 50268.
Cable Joints
SPS fireproof cable joints utilise LSF zero halogen heat shrink tubes and fire barrier tubes – the joints incorporate mica tape over each of the conductor cores. Micaca tape is a slit silica tape constructed from 96% pure silica fibre, coated one side with a pressure adhesive backing that facilitates installation of the joint kit.
➡ Watch the Installation Video for Fire Resistant & Zero Halogen Cable Joints HERE.
Fire resistant cable joints ensure vital emergency circuit integrity in fire conditions – cable joint kit contents include fire protection sleeve, stainless steel clamping spring, inner and outer sealing sleeve, tinner copper earth braid, tinned copper earth mesh, insulation tubes, mica pads and crimp ferrules.
LONDON UNDERGROUND APPROVED
Developed specifically for London Underground Limited (LUL) and for use within underground rail tunnels and above surface at platform and station level, the low smoke zero halogen cable joint incorporates flame retardant, non halogen polyolefin heat shrink tubing with a meltable inner liner providing excellent flame retardant properties with reduced acid gas emission and smoke generation.
A complete range of multicore and multipair cable joints are available with LU approval for rail power, signals and telecoms cables.

Fire Resistant Cable Accessories
Thorne & Derrick International distribute the complete range of Fire Resistant Cable Accessories to preserve and power low voltage electrical systems without compromising the manufacturing standards according to BS7846 – complete ranges of cable clips, cleats (including claw cleats) and glands are also available to support the installation of Prysmian FP specification cables.
| Clips | Firefix | Claw Cleat (Single hole – stackable) | 2 Bolt Cleat (Stackable) | Traditional FP Gland | FP Easy Fit Gland | Brass Gland | |
| FP600S | – | – | BICON 370CG | BICON 370CG | – | – | BICON LSF-CW |
| FP200 GOLD | AP Clips | FP Firefix Single or Double | – | – | 251, 252, 254 | FP2520 | BICON A1/A2 423 L |
| FP PLUS | AP Clips | FP Firefix Single or Double | – | – | 251, 252, 254 | FP2520 | BICON A1/A2 423 L |
| FP400 | – | – | BICON 370CG | BICON 370CG | – | – | BICON LSF-CW |

Cable Breakouts | Cable Caps | Cable Lugs | Cable Cleats | Cable Trough | Cable Duct | Feeder Pillars | for 11kV/33kV/66kV networks see MV HV Joints & Terminations
Prysmian JEM Resin | Cable Jointing Resins LV MV HV
February 6th, 2019
Cable Jointing Resins
-
uploaded by Chris Dodds - Thorne & Derrick Sales & Marketing Manager
Prysmian JEM Resin
LV MV HV Cable Jointing Resins
Prysmian JEM Resin was developed to meet the growing concerns regarding Jointer exposure to isocyanates in the workplace, especially when using cable joints for jointing utility cables in confined spaces and cable trenches with inadequate ventilation.
JEM Resin developed by Prysmian is a non-isocyanate cable jointing resin with all the technical performance characteristics of conventional jointing resins but with additional features and benefits for the encapsulation of LV, MV or HV joints typically operating at 600V/1000V, 11kV and 33kV.
Changing Legislation For Cable Joint Resins
From December 1st 2010 cable jointing resins containing MDI (Methylene diphenyl diisocyanate) are re-classified as Carcinogen Category 3, suspected of causing cancer and will carry new labelling to this effect.
Subsequently, Prysmian is advising utilities, cable jointing contractors and specifiers to adopt a “Substitute it Now (SIN)” philosophy when it comes to choosing which resin products to use for jointing cables.
This applies to the vast majority of cable jointing resins on the market, except for Prysmian’s JEM resin cable jointing solutions which are 100% MDI free and present none of the health and safety risks associated with other jointing resins containing hazardous chemicals. From December 1st all Prysmian resin cable joint kits will be JEM resin only.
JEM Resin Pack Quantities & Order Codes
Contact Thorne & Derrick Sales for stock availability and current pricing for JEM:
| Prysmian Resin Order Code | Description | Colour |
| JEM400 Prysmian | Cold Pour Resin Compound 4 Litre (8 x 0.5 Litres | Green |
| JEM600 9X Prysmian | Cold Pour Resin Compound 6 Litre (3 x 2 Litres) | Green |
| JEM200P Prysmian | Cold Pour Resin Compound 6 Litre (3 x 2 Litres) | Green |

Cable Jointing Resins. Joint Encapsulating Material (JEM).
Prysmian JEM Resin Cold Pour Compound Features & Benefits
- Low viscosity resin (very searching, no voids, easier mixing by the Jointer)
- Easy mixing by the Jointer at low ambient temperatures (e.g. -15°C)
- Curing reaction not sensitive to moisture (will cure underwater and in wet cable trenches or joint holes)
- Filled cable joints with Prysmian JEM resin may be energised immediately if undisturbed
- JEM resin supplied in clear pouches which allows mixing to be observed in process
- Excellent adhesion to XLPE, PVC, Lead type cables
- Type approved in LV cable joints (ENA TS C81/3 and BS EN 50393)
- Cable jointing resin is tested in accordance with HD631.1
- Re-enterable cable jointing compound resin version available
➡ Watch & Learn from this video by Prysmian Group on how to Mix, Pour & Deliver the JEM range of cable jointing resins:

Prymsian JEM Resin
Prysmian JEM Resin
Performance Data
| Properties Of JEM Resin | |
| Type | Low hazard, isocyanate free |
| Appearance / Colour | Grey / brown fluid when mixed |
| Viscosity Of Mixture @ 5°C | 3700 mPa.s |
| Relative Density | 2g/cm³ @ 25°C |
| Flash Point | >110°C |
| Non-volatile Content | 85% |
| Storage Conditions | Away from direct sunlight <50°C |
| JEM Resin Application Properties | |
| Mixing Ratio – by weight | 5.6 powder: 1 liquid |
| Flash Point | >110°C |
| Pot Life | 16mins @ 5°C |
| 5mins @ 40°C | |
| Gel Time | 15mins (0.5 litre @ 25°C) |
| Peak Exothermic Temperature 0.5litres | 35°C @ 5°C |
| 70°C @ 40°C | |
| Complete Cure Time | 24 hours @ 25°C |
| JEM Resin Performance Properties | |
| Colour Of Mixture | Grey / Brown |
| Class Of Resin | Methacrylate |
| Water Absorption Rate | 0.011% @ 24hrs, 25°C |
| 0.8% @ 42days, 50°C | |
| Hardness | 74 Shore A |
| Volume Shrinkage After Curing | <1.0% |
| Tensile Strength | 2.5 N/mm² |
| Ultimate Elongation | 50% |
| Impact Strength | No break |
| Volume Resistivity | 5 x 10¹³ Ohm.cm @ 20°C |
| 7.4 x 10¹¹ Ohm.cm @ 90°C | |
| Surface Resistivity | 1 x 10¹³ Ohms |
| Dielectric Strength | 9.3 KV/mm |
| Thermal Conductivity | 1.31 W/m.K |
| Maximum Continuous Operating Temperature | 95°C |
| Time To Energise LV Joints (Undisturbed) | Immediately |
| Time To Energise LV Joints (Backfilled Or Moved) | 2hrs |
Prysmian JEM Resin
Cold Pour Compound Mixing Instructions
The Jointer must take care when mixing the JEM Resin prior to pouring into the cable joint shell or mould.
![]() |
![]() |
| Step 1: Open container and remove JEM Resin Kit. The Jointer should check the resin bag for any signs of damage before proceeding | Step 2: Aerate the powder by gripping the pouch at each end and tumbling the powder for up to thirty seconds, this will facilitate mixing of the JEM Resin |
![]() |
![]() |
| Step 3: To start the mixing process, hold the JEM Resin bag as shown above, so that the liquid is forced onto the powder | Step 4: Squeeze the liquid through the membrane seal and onto the powder |
![]() |
![]() |
| Step 5: Make sure that the membrane seal is completely open before mixing the powder and liquid together | Step 6: Before mixing the Jointer should rotate and shake at the corners to free the powder |
![]() |
![]() |
| Step 7: Tumble mix and knead the JEM Resin bag for up to two minutes, to ensure that there are no lumps in the bag | Step 8: Finally cut one corner and pour the contents into the cable joint shell |
Customer Question…
“I’m supervising electrical connections on Scottish Power’s LV network – service joints of varying types. We have a cable jointer query regarding curing time of the Prysmian JEM resin you supply which I need to get completely right. Many cable jointers say leave the joint for 24 hours to cure, some say 2 hours. What is your standard curing time for service joints? Let’s assume it’s a single phase service off a 300sqmm PILC cable. Please bear in mind that we want to backfill and compact the joint bay in order to reinstate the joint bay, so assume we’re using a rammer. Obviously we will not backfill/reinstate if it compromises the cable joint’s integrity, however, we do have pressures to reinstate said joint bays as soon as possible.
Prysmian Answer…
“Full cure is not achieved for 24 hours but Prysmian JEM resin joints can be energised immediately provided they are not being moved.”
Cable Jointing Resins

3M Scotchcast resin insulated cable joint kits are designed for indoor, outdoor (weather exposed), direct buried or submersed applications.
3M brand Scotchcast Resins are 100% solids, electrical grade, hydrolytically stable insulating resins. The unique electrical and physical properties of 3M Resins make them ideal for insulating and protecting electrical/ electronic parts and assemblies. Their physical features also make them suitable for non-electrical, general use applications, for example as adhesives or sealants.
A Safe, Clean, Simple & Reliable Joint Solution
• High quality range of cable jointing resins for low and medium voltages
• Unique Patented Close Mixing and Pouring (CMP) system from 3M Electrical
• Transparent Mould for better control of the job by the Jointer
• Resin packed in transparent 2-chamber mixing bags for delivery into the cable joints
• Cable jointing resins with approvals according to VDE 0291 part 2
♦ G38A Compund | Prysmian BICC Cable Joint, Termination & Cable Box Filling Compounds
3M Cold Shrink Cable Abandonment Kit – Selection Guide
February 6th, 2019
-
uploaded by Chris Dodds - Thorne & Derrick Sales & Marketing Manager
Cable Abandonment
Thorne & Derrick International, the UK’s leading distributor and largest stockist for 3M Hazardous Area & Cold Shrink Cable Accessories have despatched over one thousand 3M CSCAK abandonment kits to the North Sea Forties Pipeline System and Kinneil Terminal.
3M CSCAK cable abandonment kits are used to safely decommission redundant LV low voltage power cable circuits in the oil, gas and petrochemical industry.
3M Electrical cable abandonment kits using Cold Shrink, are suitable for Zone 1 and Zone 2 hazardous area electrical installations without need for heat shrink, “hot-working” and naked flames in potentially explosive environments – CSCAK abandonment kits suit EEMUA 133 XLPE lead sheathed power cables (600/1000v and 3.3kV) for safe installation in hazardous area locations according to the ATEX Directive.
3M Cold Shrink Cable Abandonment Kit
Cold Shrink product features at a glance :
- Simple and quick to install – no heat shrink torches or heating required to install cold shrink abandonment kits
- Permanent cable abandonment for LV power cables
- No requirement for additional mastic tapes or greases
- No hot work permits required for hazardous area locations (HAZLOC) or potentially explosive atmospheres
- Widely used in onshore and offshore environments, including hazardous area locations Zone 1 & Zone 2
- 3M Cold Shrink rated up to and including 1.9/3.3kV
3M Cable Abandonment Kits suit XLPE/PVC Insulation, Lead Sheath, Steel Wire Armour, PVC Sheathed – including Shipwiring cables (EPR GSWB Wire Braided) and Unarmoured cables up to and including 3.3kV single and multi-core cables.
CABLE ABANDONMENT KIT LIST
The cable abandonment kit uses a 3M Cold Shrink cable end cap, pre-stretched cold shrink tubes, Scotch 2228 Mastic Tape, Scotch 23 Self Amalgamating Tape and Scotch 24 Electrical Shielding Braid (tinned copper mesh tape) and constant force springs.

Cable Abandonment Kits
Cable abandonment kits are often used when cable is left underground but it is not intended to be left live. If by mistake it has power connected to it, the cable abandonment kit is designed to create a short circuit to earth so that it will trip out, thus it will render the circuit dead to enable the engineer or cable jointer to realise power was switched to it by mistake.
In this design by 3M Electrical, there are no provisions for stress control tapes or systems and screening because it is just not meant to be left live.
The range-take of 3M CSCAK Cold Shrink products according to both outside cable diameters (around outer cable sheath) and conductor cross section areas (core) for both single and multi-core cables are as follows:
- 3M Cold Shrink Cable Abandonment Kit – 12 to 18mm Dia – 3M CSCAK-1
- 3M Cold Shrink Cable Abandonment Kit – 18 to 25mm Dia – 3M CSCAK-2
- 3M Cold Shrink Cable Abandonment Kit – 25 to 42mm Dia – 3M CSCAK-3
- 3M Cold Shrink Cable Abandonment Kit – 42 to 55mm Dia – 3M CSCAK-4
- 3M Cold Shrink Cable Abandonment Kit – 56 to 81mm Dia – 3M CSCAK-5
CABLE ABANDONMENT KIT SELECTION TABLE
| Cable Abandonment CSCAK Kit | XLPE AWA Single Core | XLPE SWA 2 Core | XLPE SWA 3 Core | XLPE SWA 4 Core | 3.3kV XLPE SWA Lead 3 Core |
| 3M CSCAK/1 | – | 1.5-6sqmm | 1.5-6sqmm | 1.5-4sqmm | – |
| 3M CSCAK/2 | 70-120sqmm | 10-35sqmm | 10-16sqmm | 6-16sqmm | – |
| 3M CSCAK/3 | 150-500sqmm | 50-150sqmm | 25-120sqmm | 25-95sqmm | 25-95sqmm |
| 3M CSCAK/4 | 500-630sqmm | 185-400sqmm | 150-185sqmm | 120-150sqmm | 120-185sqmm |
| 3M CSCAK/5 | 800-1000sqmm | – | 240-400sqmm | 185-400sqmm | 240-400sqmm |
Why Play With Fire? Keep Your Cool with 3M Cold Shrink……
Heat shrink cable joints, terminations and cable accessories require naked flames.
But hot-working poses serious dangers with respect to ignition sources in industrial and hazardous areas – air, naked flames and the presence of atmospheric combustible substances trigger the Ignition Triangle.
Install 3M Cold Shrink for a first class safety and service record without any hidden dangers.
3M Cold Shrink products include cable joint kits, cable termination kits, cable abandonment kits and cold shrink tubing – extensively specified for offshore oil, gas, petrochemical, rail, utility and construction projects at low and high voltages.
Video : 3M Cold Shrink Cable Abandonment Kits ➡
Should you require customer service or technical support on the selection or specification of LV MV HV Cable Accessories please contact us – view the full range of 3M Cold Shrink Cable Abandonment Kits below.
Cable Joints For Low Voltage Cables
Thorne & Derrick stock and distribute LV Joints in Cold Shrink, Heat Shrink or Resin Cast technologies – multicore and multi-pair cable joints are available for immediate backfill and energisation of Low Voltage power, control and instrumentation cables 600V/1000V 3.3kV.
Complete range of LV Cable Accessories ➡
Cable Breakouts | Cable Caps | Cable Lugs | Cable Cleats | Cable Trough | Cable Duct | Feeder Pillars | for 11kV/33kV/66kV networks see MV HV Joints & Terminations

Pfisterer | Nexans Euromold | Prysmian | Cable Joints & Terminations MV HV

Cold Shrink by 3M | Joints | Abandonment | Terminations | Low Voltage LV Cables
3rd Arc Flash & Isolation Safety Conference in Manchester on May 21st & 22nd 2019
February 6th, 2019
Article by Chris Dodds – Thorne & Derrick Sales & Marketing Manager
Arc Flash & Isolation Safety Conference – Manchester 2019
The 3rd Arc Flash & Isolation Safety Conference took place in Manchester on 21–22 May 2019.
The two-day event brought together electrical safety professionals to discuss arc flash hazards, safe isolation and practical risk management.
Its programme focused on real workplace experiences, technical developments and the challenges faced by electrical engineers.
Delegates had the opportunity to hear from specialists, review case studies and discuss ways to improve electrical safety.
The event also examined relevant standards, risk assessment methods and the selection of appropriate arc flash protective equipment.
Why Is Arc Flash Safety Important?
An arc flash is a dangerous electrical event that can release intense heat, light and pressure.
It may occur when an electrical fault produces an arc through the surrounding air.
Workers exposed to an arc flash can suffer severe burns and other injuries.
Effective risk management therefore requires suitable electrical system design, safe working procedures and appropriate protective measures.
Where a residual thermal hazard remains, correctly selected arc-rated PPE can provide an additional layer of protection.
Arc Flash Conference – Technical Topics
The conference addressed several important areas of electrical safety.
Its programme included the following technical subjects:
- The human factor in electrical safety: Reducing errors and improving workplace performance.
- Arc flash risk assessments: Understanding the UK approach to electrical hazard evaluation.
- Arc-rated clothing programmes: Developing and implementing suitable protective clothing arrangements.
- Maritime electrical safety: Managing arc flash hazards through vessel electrical system design.
- IEC 62271-200: Internal arc classification of relevant high voltage switchgear.
- IEC 61439: Improving safety in low voltage switchgear assemblies.
- Electrical safety training: Identifying gaps in worker knowledge and competence.
- Arc flash PPE: Understanding when protective clothing is required.
- Nuclear industry risk assessment: Lessons from a Swedish nuclear power plant.
- Protective clothing design: Understanding the construction and performance of arc flash PPE.
- IEEE 1584: Methods used to calculate arc flash incident energy.
- Practical workplace case studies: Applying arc flash assessments to real electrical installations.
- PPE selection methods: Comparing approaches to electrical arc hazard assessment.
Together, these sessions explored both the technical and human aspects of electrical safety.
Legal Responsibility and Electrical Safety Management
One of the conference sessions focused on the legal responsibilities associated with electrical installations.
Anthony Smith, CEO of Lantei Compliance Services and The Electrical Safety Network, delivered the presentation.
The Electricity at Work Regulations 1989
Anthony’s session examined the legal requirements for maintaining electrical systems and equipment.
It covered low, medium and high voltage installations, with particular attention to the responsibilities of duty holders.
The presentation included discussion of:
- The Electricity at Work Regulations 1989.
- The Health and Safety at Work etc. Act 1974.
- The IET Code of Practice for Electrical Safety Management.
- Electrical maintenance responsibilities.
- Workplace compliance and safety management.
The aim was to help duty holders understand their responsibilities and manage electrical safety more effectively.
This presentation appeared as Session 14 in the original conference programme.
Electrical Safety Equipment
Safe electrical working may require specialist testing and protective equipment.
For example, appropriate voltage detectors and portable earthing arrangements can form part of approved isolation procedures.
Thorne & Derrick supply electrical safety equipment for suitable LV, MV and HV applications.

Voltage Detectors | Portable Earthing | Insulating Sticks | Insulating Gloves | CATU Electrical Equipment
Arc Flash Conference – Day 1 Highlights
The first day explored electrical safety culture, risk assessments, protective equipment and switchgear design.
Speakers also shared case studies from different industries.
Day 1 Speakers and Presentations
| Speaker | Presentation |
|---|---|
| Jim Pollard | The Human Factor in Electrical Safety – Ways to Reduce Error and Improve Performance |
| John Maplesden | Arc Flash Risk Assessment from a UK Perspective – What’s New? |
| Derek Sang | Building and Implementing a Flame-Resistant/Arc-Rated Clothing Programme |
| Shaun White | Arc Flash in the Maritime Industry – Hazard Mitigation Through System Design on a New-Build Vessel |
| Andy Seccombe | Internal Arc Classification According to IEC 62271-200 |
| Lutz Graufmann | Improving the Safety of LV Switchgear Assemblies According to IEC 61439 |
| Kevin Hann | Electrical Training Gaps and Their Arc Flash Safety Implications |
| Anthony Long | Arc Flash PPE – Do You or Don’t You Need It? |
| Thomas Winter | Arc Flash Risk Assessment – Case Study from Sweden’s Largest Nuclear Power Plant |
International Keynote Speaker – Jim Pollard
Jim Pollard, an arc flash specialist associated with Unlimited PPE Inc., was featured as an international keynote speaker.
His presentation focused on the human factors that influence electrical safety.
For example, working practices, decision-making and training can all affect how workers respond to electrical hazards.
Addressing these factors can help organisations improve safety performance.
Arc Flash Conference – Day 2 Highlights
The second day focused on arc flash PPE, calculation methods and practical risk assessment.
It also included a session on electrical safety responsibilities.
Day 2 Speakers and Presentations
| Speaker | Presentation |
|---|---|
| Jim Pollard | The Anatomy of Arc Flash PPE |
| Alan O’Kelly | IEEE 1584 – Guide for Performing Arc Flash Hazard Calculations |
| Pay Mynett | Three Case Studies Exploring Practical Arc Flash Risk Assessment in the Workplace |
| Thomas Jordan | PPE Selection – Practical Experience and Comparison of Arc Assessment Methods |
| Anthony Smith | Duty Holder Responsibility and Electrical Safety Management |
IEEE 1584 and Arc Flash Calculations
The conference included a presentation about IEEE 1584 and arc flash hazard calculations.
Arc flash calculations help engineers estimate the incident energy associated with certain electrical faults.
These results can support risk assessment and protective measures within the method’s defined scope.
However, calculations require accurate electrical system information and the appropriate calculation standard.
Download the 2019 Arc Flash Conference Brochure
The original conference brochure contains details of the event programme, speakers and registration arrangements.
Although the event has concluded, the document remains a useful historical reference.
What Could Delegates Learn?
The conference aimed to help electrical professionals develop their understanding of arc flash safety.
Its original programme highlighted several learning objectives.
- Understand developments in UK, European and international electrical safety standards.
- Review case studies involving arc flash hazard mitigation.
- Explore methods of assessing electrical arc flash risks.
- Understand the potential injuries associated with an arc flash.
- Learn about electrical safety responsibilities and workplace compliance.
- Compare approaches to arc flash assessment.
- Understand the selection, testing and maintenance of arc flash PPE.
- Explore electrical safety training requirements.
- Share experience with electrical safety specialists and other delegates.
The original programme also referenced NFPA 70E, CSA Z462, BS 7671 and IEEE 1584.
These references reflect the standards discussed during the 2019 event. Current projects must use the applicable editions and requirements.
Who Was the Conference Designed For?
The event targeted professionals involved in electrical engineering, workplace safety and industrial risk management.
Its intended audience included:
- Electrical technicians, engineers and managers.
- Engineering and maintenance managers.
- Electrical risk assessors.
- Electrical design engineers.
- Manufacturers of PPE and safety equipment.
- Safety advisers and facilitators.
- Instrumentation and control engineers.
- Process safety and loss prevention managers.
- Government safety regulators and inspectors.
- Occupational health and safety managers.
- Electrical training managers.
- Tradespeople working in potentially explosive environments.

2019 Arc Flash Conference – Event Details
The following details are retained from the original event announcement for historical reference.
| Conference | 3rd Arc Flash & Isolation Safety Conference |
| Start Date | 21 May 2019 |
| End Date | 22 May 2019 |
| Venue | Marriott Manchester – Victoria & Albert Hotel |
| Original Registration Start | 1 February 2019 |
| Original Listed Cut-Off Date | 31 May 2019 |
| Standard Delegate Price | £750 |
| Early Booking Price | £675 until 23 April 2019 |
| Listed Group Price | £1,500 |
Historical event: The conference has finished, and the registration prices and discounts are no longer active.
Original Delegate Discounts
The original event announcement included an early booking discount of 10%, equivalent to £75 per delegate.
It also advertised a three-for-two delegate offer.
These promotions applied only to the 2019 conference.
Arc Flash Statistics and Electrical Safety Awareness
The original conference article featured historical arc flash statistics from ISHN.
These figures included:
- 30,000 reported arc flash incidents per year.
- 7,000 burn injuries per year.
- 2,000 hospitalisations per year.
- 400 fatalities per year.
However, the original article did not establish a consistent reporting geography, timeframe or independently verified dataset for these figures.
Therefore, they should be regarded as historical claims rather than current annual statistics.
For electrical safety planning, organisations should use reliable incident information alongside site-specific risk assessments and applicable guidance.

Historical Arc Flash Statistics – Source: ISHN
Thorne & Derrick – Arc Flash and Electrical Safety Equipment
Thorne & Derrick International supply specialist equipment for electrical installation, maintenance and power distribution.
Our product range includes arc flash protection and electrical safety equipment for LV, MV and HV applications.
We support utilities, electrical contractors and industrial businesses working on power infrastructure projects.
Electrical Safety Product Categories
Explore our specialist product ranges:
- Arc Flash Clothing and Protection.
- Electrical Safety Equipment.
- Cable Duct Seals.
- Cable Cleats and Supports.
- Cable Glands.
- Cable Jointing Tools.
- Cable Pulling Equipment.
- Earthing and Lightning Protection.
- Electrical Feeder Pillars.
- LV Cable Joints.
- MV and HV Cable Joints and Terminations.
Electrical Equipment Manufacturers
Our original article featured electrical equipment manufacturers including 3M, CMP, Ellis Patents, Nexans Euromold, Elastimold, PFISTERER, Prysmian, Alroc, CSD, Roxtec, CATU, Cembre, Lucy Zodion, ABB and Emtelle.
These manufacturers supply different products for cable installation, electrical distribution and related applications.

Power Cable Jointing and Installation
Thorne & Derrick also provide technical product information for electrical cable installation work.
Our Cable Jointers Photo Blog features contributions from electrical professionals working on LV, MV and HV installations.
For further information about our product offering, explore the Thorne & Derrick Power Brochure.


Thorne & Derrick – Joint | Terminate | Connect